Subject to change without notice. Published in U.S.A.
359319-BTG-G-0509
Copyright
©
2009 by Johnson Controls, Inc. All rights reserved.
Supersedes: 359319-FTG-F-0309
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGD60S41S1
INDOOR COIL MODEL NO.
FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1600
1800
2000
ID
DB
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID
WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
55.8 63.8 62.1 65.2 71.9 60.3 65.7 62.8 66.7 69.8 64.8 67.5 63.5 68.2 67.8
S.C.
54.7 51.6 41.4 41.1 34.1 58.4 54.2 43.9 42.6 31.9 62.1 56.8 46.5 44.2 29.6
KW
3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.1 3.0 3.1 3.0 3.1 3.1
75
T.C.
56.9 61.1 58.9 62.7 69.7 59.2 63.0 59.9 64.3 67.9 61.4 64.9 61.0 65.9 66.0
S.C.
53.9 50.4 40.5 40.0 33.5 55.8 53.1 43.1 41.8 31.5 57.7 55.7 45.6 43.6 29.5
KW
3.4 3.5 3.5 3.5 3.6 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
85
T.C.
58.0 58.4 55.7 60.3 67.6 58.0 60.4 57.1 61.9 65.9 58.1 62.4 58.5 63.6 64.1
S.C.
53.2 49.3 39.7 39.0 32.9 53.3 52.0 42.2 41.0 31.2 53.4 54.7 44.8 42.9 29.4
KW
3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0
95
T.C.
59.1 55.7 52.5 56.9 65.5 56.9 57.8 54.3 57.0 63.9 54.7 59.8 56.0 61.2 62.2
S.C.
52.4 48.1 38.8 37.9 32.3 50.7 50.9 41.4 38.8 30.8 49.0 53.6 43.9 42.3 29.4
KW
4.3 4.3 4.3 4.4 4.5 4.3 4.3 4.3 4.4 4.4 4.3 4.3 4.3 4.4 4.4
105
T.C.
56.4 52.2 48.8 54.0 60.1 54.0 54.3 50.5 55.7 59.7 51.6 56.3 52.2 57.4 59.4
S.C.
49.7 45.9 37.5 36.5 29.7 47.9 48.3 40.0 38.7 29.4 46.2 50.6 42.5 40.9 29.0
KW
4.9 4.9 4.9 4.9 5.0 4.9 4.9 4.9 5.0 5.0 4.9 4.9 4.9 5.0 5.0
115
T.C.
53.8 48.8 45.2 50.2 54.8 51.2 50.9 46.8 51.9 55.7 48.7 53.0 48.5 53.6 56.6
S.C.
47.1 43.8 36.2 35.0 27.3 45.3 45.7 38.6 37.3 27.9 43.5 47.7 41.1 39.6 28.6
KW
5.5 5.4 5.4 5.5 5.6 5.5 5.5 5.4 5.5 5.6 5.4 5.5 5.4 5.5 5.6
125
T.C.
51.2 45.4 41.6 46.5 49.4 48.5 47.5 43.2 48.2 51.6 45.7 49.7 44.8 49.8 53.8
S.C.
44.5 41.7 34.9 33.6 24.9 42.6 43.2 37.3 35.9 26.5 40.7 44.7 39.7 38.3 28.2
KW
6.1 6.0 5.9 6.1 6.2 6.0 6.0 6.0 6.1 6.2 6.0 6.0 6.0 6.1 6.2
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC62
1.00 1.00 1.00
–
HC60
1.00 1.00 1.00
–
UC60
1.00 1.00 1.00
AHP/SHP60
–
1.00 1.00 1.00
AHX60
–
1.00
1.00
0.98
AV/SV*60
–
1.00 1.01 1.00
MV20D
FC/MC60D
1.00 1.01 1.00
MA20D
FC/MC60D
1.00 1.00 1.00
MV20D
FC/MC62D
1.00 1.01 1.00
MA20D
FC/MC62D
1.00 1.00 1.00
F5FP060
–
1.00 1.00 1.00
F6FP060
–
1.00
1.00
0.96
F4FV060 –
1.00
1.00
0.99
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)X*C16
FC/PC60C
0.99
0.98
0.99
T*(8,L)X*C20
FC/MC/PC60D
1.00
0.98
1.00
T*9X*C16
FC/PC60C
0.98
0.98
0.98
T*9X*C20
FC/PC60C
0.98
0.98
0.98
T*9X*D20
FC/MC/PC60D
0.99
0.98
0.99
T*9X*C20
FC/MC/PC60D
0.99
0.98
0.99
T*(8,L)X*C20
FC/MC62D
1.00
0.98
1.00
T*(8,L)X*C16
UC60C
0.98
0.97
0.98
T*(8,L)X*C20
UC60D
0.99
1.00
0.99
T*9X*C16
FC/PC60C
0.98
0.97
0.98
T*9X*C20
FC/PC60C
0.98
0.97
0.98
T*9X*D20
UC60D
0.98
0.97
0.98
T*(8,L)X*C20
UC60D
0.99
1.00
0.99
T*9X*C20
UC60D
0.98
0.97
0.98
(T*9C/T*9V)*D20 FC/MC/PC60D
0.97 0.95 0.96
T*(8,L)C*C20
FC/MC62D
0.99 0.97 0.94
(T*9C/T*9V)*C20 FC/MC62D
0.98 0.96 0.97
(T*9C/T*9V)*D20 FC/MC62D
0.99 0.96 0.96
T*(8,L)C*C20
FC/PC60C
0.98 0.96 0.94
(T*9C/T*9V)*C20 FC/PC60C
0.97 0.95 0.96
(T*9C/T*9V)*D20 HC60
0.94 0.93 0.95
T*(8,L)C*C20
UC60C
0.95 0.91 0.93
(T*9C/T*9V)*C20 UC60C
0.94 0.90 0.96
(T*9C/T*9V)*D20 UC60D
0.94 0.90 0.95