Страница 1: ...Owner s Manual and Installation Instructions High Resolution Touch Screen Code No LIT 12012449 Issued October 3 2017 model T9180 Commercial Digital Thermostat...

Страница 2: ...tation inscription signifie simplement que le produit est conforme aux sp cifications techniques d Industry Canada This color touch screen has the ability to receive updates to its firmware Periodical...

Страница 3: ...hat the space should drop to before heating is turned on without regard to deadband Icon The word or symbol that appears on the thermostat display Mode The current operating condition of the thermosta...

Страница 4: ...ing the Override Button 7 Setting the Time Date 8 Setting the Time 9 Setting the Date 10 Daylight Savings Setup 10 Connecting to Wi Fi 11 WiFi Set up Create a Skyport Account 12 MAIN MENU BUTTONS SCHE...

Страница 5: ...aintenance 25 PREFERENCES 26 User Interface Themes 27 Custom Wallpaper 27 Heat Cool Indicator 27 Sound Options 27 HOLIDAYS 28 Holiday Schedule On Off 29 Edit Holidays 29 Preset Holidays 31 SECURITY 32...

Страница 6: ...s 56 Heat Pump Settings 58 Heat Pump Lockout Enabled Disabled 58 Heat Pump Lockout Outdoor Temp 58 Aux Heat Lockout Enabled Disabled 58 Aux Heat Lockout Temp 58 Aux Output Settings 59 Fan Off Delay 60...

Страница 7: ...INSTALLATION INSTRUCTIONS 72 Remove Replace the Old Thermostat 72 Wire Connections 73 Determining Your Existing Wiring and Equipment 74 Making 4 Wires Work When 5 Wires Are Required 76 Making 5 Wires...

Страница 8: ...me Fan Button Override Button OutdoorTemperature Cooler Button Warmer Button SD Card Slot Menu Button Mode Buttons If optional accessory is used or connected to Skyport Connectivity Symbol Drop Down S...

Страница 9: ...Connected to local access point w IP address without Skyport enabled Connected to local access point w IP address but not yet connected to Skyport Connected to Skyport Connectivity Symbol Table Dropd...

Страница 10: ...forecast for the following 3 days Weather Display Skyport connection required for weather This page displays sensor information Select Onboard to view room temperature sensors that are built into the...

Страница 11: ...4 Get To Know Your Thermostat Thermostat Info Equipment Configuration Thermostat Outputs These 3 screens are for informational purposes only Settings may not be changed from these screens...

Страница 12: ...uch screen Only use your finger tip to press the screen buttons Use a soft damp cloth to clean the screen CAUTION DO NOT USE ABRASIVE CLEANERS OR CLEANERSTHAT CONTAIN SOLVENTS DO NOT SPRAY ANYTHING DI...

Страница 13: ...O CHANGEOVER MODE Pressing theWARMER or COOLER buttons in Auto mode will adjust both the heat and cool setpoints simultaneously To adjust heat and cool setpoints individually choose HEAT mode to adjus...

Страница 14: ...OVERRIDE button will force the thermostat into an unoccupied period for the rest of the day During this forced unoccupied period the OVERRIDE button will operate as described above Holiday Operation...

Страница 15: ...OFF Start Schedule Starts On Day Month Stop Schedule Ends On Day Month 2nd Sun March 1st Sun November NOTE When the thermostat is connected to a Skyport account theTime Date are automatically synchro...

Страница 16: ...rrent Time 12 00 AM hr hr min min Press and to set the current time Press when finished Press then to scroll down Press Use AM PM ON Use AM PM OFF For 12 hour AM PM clock For 24 hour clock Choose Pres...

Страница 17: ...5 14 13 12 11 18 19 20 21 22 23 24 31 30 29 28 27 26 25 1 2 3 4 5 6 7 Press Press Daylight Savings Time OFF Daylight Savings Time ON Start Schedule Starts On Day Month Stop Schedule 2nd Sun March Ends...

Страница 18: ...t the access point you wish to connect to from the list Enter the password for the Wi Fi Access Point and press NEXT Select automatic setup and press NEXT When finished a dialog box will appear confir...

Страница 19: ...tic setup and press NEXT When finished a dialog box will appear confirming the successful connection to the local Wi Fi Access Point Select OK then the Wi Fi status page will appear Upon closing of th...

Страница 20: ...cal Wi Fi Access Point but not yet joined to a Skyport account you may join the thermostat to an account by doing the following Select MENU from the thermostat s home screen Scroll down Select Skyport...

Страница 21: ...14 Main Menu Buttons Schedule Schedule Unoccupied Settings View My Schedule Edit My Schedule Mode Off Auto Heat Auto Cool Heat Setpoint 55 Cool Setpoint 85...

Страница 22: ...ettings This may be repeated for each day View My Schedule Press and select day s to program Then press NEXT Edit My Schedule Continued Select individual day s or Select groups of day s Press and sele...

Страница 23: ...o desired settings TheTime Period May also be Enabled or Disabled Un check the enabled box forTime Periods you don t want to use Press DONE when finished Save Edit Mode Done Enable Disable Time Period...

Страница 24: ...17 Main Menu Buttons Fan Settings Who To Call For Service View Runtime Graphs Fan Auto Fan Purge OFF Fan Settings Occupied Fan State On Auto Auto Preoccupancy Purge Time 15 mins...

Страница 25: ...to run continuously or Auto for fan to run only with heating or cooling Press to turn on Preoccupancy Fan Purge This feature allows the fan to run for a preset amount of time before Occupied 1 begins...

Страница 26: ...raphs Screensaver OFF Screensaver Setup Screensaver Turn On Delay Change Image After Show Clock OFF Screensaver Type Screensaver Home Screen Info OFF View Runtime Graphs Screensaver Preview Slideshow...

Страница 27: ...ore returning to the Home Screen After the preview press anywhere on the screen to return to the sub menu Screensaver Screensaver Setup The Screensaver allows you to create custom slideshows Screensav...

Страница 28: ...er Reminder OFF Set Max Filter Runtime Reset Air Filter Alert Reset UV Lamp Alert Alerts Set Edit Reminders Service Information UV Lamp Reminder OFF Max UV Lamp Runtime 300 hrs Set Max Filter Days 0 d...

Страница 29: ...rrent service alerts Set service alert runtimes and turn reminders on or off View and reset current service alerts here Alerts will appear on the bottom bar of the Home Screen Press to view and reset...

Страница 30: ...23 Main Menu Buttons Display Screen Cleaning Touch Calibration Active Brightness Night Dimmer Display Maintenance Auto Night Dimmer OFF Set Idle Brightness Set Dimmer Schedule Idle Brightness...

Страница 31: ...splay is active for 3 minutes after last touch it then goes Idle You may dim the brightness of the screen at night The screen can be set to dim automatically at night Dimming the display can prolong t...

Страница 32: ...een Cleaning Mode disables the touch feature for 15 seconds so the screen may be cleaned without altering any settings Under normal circumstances the touch screen should not need to be calibrated When...

Страница 33: ...tons Preferences User Interface Themes Custom Wallpaper Heat Cool Indicator OFF Taskbar red white OFF Room Temp red blue OFF Mode Status red blue OFF Preferences Heat Cool Indicator Sound Options Beep...

Страница 34: ...ound will change to an evening scene At 7am it will return to a daytime scene You may choose your own background image by selecting a photo that you have uploaded from an SD memory card Sound Options...

Страница 35: ...28 Main Menu Buttons Holidays Holiday Schedule OFF Edit Holidays Preset Holidays Holidays...

Страница 36: ...nued You may continue to select more holidays or you can press the Repeat button for recurring holidays Choose to repeat the holiday every week month or year Or press CANCEL to go back If you choose t...

Страница 37: ...n holiday If you choose to edit repeating holidays that affect this day press NEXT and the next screen will appear Press BACK to save your changes and return to the Holiday menu Deselecting Holidays M...

Страница 38: ...o observe When the preset holidays are set to ON they will be observed every year on that date Editing Repeating Holidays continued Overriding Holiday Mode You may override Holiday Mode by pressing th...

Страница 39: ...Screenlock Setpoint Limits Security Auto Screenlock OFF Set Passcode Lock After Setpoint Limits OFF Minimum Cool Setpoint Maximum Heat Setpoint Allow fan mode changes NO Allow setpoint changes NO Allo...

Страница 40: ...ttings Set the time the screen will automatically lock after the last button press When the thermostat is locked the bottom bar of the display will show Allow fan mode changes NO Allow setpoint change...

Страница 41: ...34 Main Menu Buttons Information View Runtime Graphs Information Last 7 Days Cooling Last 7 Days Heating Who To Call For Service Delete Runtime Data Last 7 Days Override...

Страница 42: ...ooling Last 7 Days Heating Track your system s runtime energy usage Press the information icon to learn more about each graph Press anywhere on the screen to return to the submenu Delete Runtime Data...

Страница 43: ...ly Cool Only Fahrenheit Celsius Heat Cool Stages Compressor Stages Aux Heat Stages English Spanish Espanol French Francais Heat Cool Stages Continued next page Import Settings from SD Card Export Sett...

Страница 44: ...eadband 2nd Stage Deadband 2nd Stage Timer 2nd Stage Turnoff Point 3rd Stage Deadband Deadband Setpoint 3rd Stage Deadband 3rd Stage Timer 3rd Stage Turnoff Point 4th Stage Deadband Deadband Setpoint...

Страница 45: ...AUX Output Usage AUX Output Polarity Continued next page Sensor Settings AUX Output Settings Control Source Thermostat Sensor Only Wired Sensor Only Average All Wireless Sensors Average Wired Thermost...

Страница 46: ...Settings Dealer Information Dealer Name Contact Name Dealer Phone Dealer Email Dealer Website Factory Defaults Restart Thermostat Installation Settings Settings Test Outputs Upgrade Firmware Delete Cu...

Страница 47: ...are found in this menu Name appears here General Setup Units F Fahrenheit F Celsius C SD Card Import and export files to and from the thermostat See the ColorDisplay Desktop app instructions for furt...

Страница 48: ...art Recovery is active Language en Installation Settings Heat Cool Stages 1h1c Heat Cool Stages 1h1c Up to 2 Stages Cooling and 4 stages Heating Compressor Stages 1h1c Up to 2 compressors Aux Heat Sta...

Страница 49: ...n order to reduce energy usage on demand This is known as Automated Demand Response or ADR for short You must register to participate in a utility sponsored program if offered by your local utility to...

Страница 50: ...e thermostat is configured to respond to the energy provider s signals It also sets operational parameters for the thermostat The left column of the ADR configuration page allows or prevents access by...

Страница 51: ...r ADR events are adjusted here The Static Settings are applied when the utility sends a signal to allow the occupant to enforce their own discrete temperature settings during an ADR event The Offset S...

Страница 52: ...45 Selecting the Overview tab of the ADR page will cause a summary of ADR events to be displayed Office Configuration Main Menu Buttons Settings...

Страница 53: ...at the Skyport Cloud Services account From the thermostat Home Screen press the Menu button then select Settings From the above screen the Automated Demand Response button is pressed By selecting ADR...

Страница 54: ...action is taken when the price rises above the set threshold In the above example if the price threshold is exceeded the thermostat will invoke the Offset Setpoints configured for an ADR event until...

Страница 55: ...48 Main Menu Buttons Settings The user may limit the maximum Cooling Setpoint...

Страница 56: ...49 Main Menu Buttons Settings The user may limit the minimum Heating Setpoint...

Страница 57: ...50 Main Menu Buttons Settings 2 The user may adjust the ADR Cooling static Setpoint...

Страница 58: ...51 2 Main Menu Buttons Settings The user may adjust the ADR Heating static Setpoint...

Страница 59: ...52 The user may adjust the ADR Cool offset During an ADR event the cooling setpoint will be adjusted by the amount of degrees configured in this step Main Menu Buttons Settings 2...

Страница 60: ...53 2 Main Menu Buttons Settings The user may adjust the ADR Heat offset During an ADR event the heating setpoint will be adjusted by the amount of degrees configured in this step...

Страница 61: ...ending and hasn t started yet there will be a yellow leaf on the top bar This will be accompanied by associated text as shown below During an ADR event there will be a green leaf on the top bar This w...

Страница 62: ...ssed during an active ADR event then the user is presented with this opt out screen If a pricing triggered ADR event is enabled there will be a green leaf on the top bar along with the actual cost of...

Страница 63: ...ressor Min OFF Time 5m None 3 minutes or 5 minutes At 6 cycles per hour the HVAC unit will only be allowed to energize once every 10 minutes The Cycles Per Hour limit may be overridden and reset by pr...

Страница 64: ...set to 2 degrees the room temperature will need to drop to 66 degrees before the heat turns on 3rd Stage Deadband 4th Stage Deadband 1st Stage Deadband 2 1 6 deg F 2nd Stage Deadband 2nd Stage Deadba...

Страница 65: ...Turns on Aux Heat Lockout Aux Heat Lockout Temp 65 Aux Heat will not run above this temp 0 75 deg F GAS EL or HP dip switch must be set for HP and GAS or ELEC dip switch must be set for ELEC Heat Pum...

Страница 66: ...59 Installation Settings AUX Output Settings Main Menu Buttons Settings...

Страница 67: ...ch sensor source is used to measure room temperature Wired Sensor Use remote The wired sensor may be used as follows Use as an Outdoor sensor Use as a Remote Sensor Use as a Supply Sensor Use as a Ret...

Страница 68: ...calibrated 7 to 7 degrees F Thermostat Wired Sensor The installer or service technician can use this feature to test the functions without any time delays of the thermostat Test Outputs With a 1st sta...

Страница 69: ...play Desktop APP that firmware is up to date or simply try reinserting the SD card Dealer s Logo here Delete Custom Images Press to delete the custom photos you uploaded to the thermostat Dealer Name...

Страница 70: ...63 Wi Fi Setup Choose Network Password Entry Local API OFF API Protocol Wi Fi Status Wi Fi Enabled Local API Option HTTP HTTPS Main Menu Buttons Wi Fi...

Страница 71: ...lows the wifi radio to be turned off or on Wi Fi Setup Choose your network from the list and enter the network password If your network does not appear in the list hit the refresh button Network Name...

Страница 72: ...equired then select API Protocol This is the default with the local API OFF Upon pressing API Protocol the following screen will appear Then select HTTPS and press BACK Local API OFF Local API OFF API...

Страница 73: ...asic Auth User API Protocol http API Protocol http API Protocol https Basic Auth Password Main Menu Buttons Wi Fi Q W E R T Y U I O 64 remaining A S D F G H J K L Shift BACK DONE Basic Auth User 123 S...

Страница 74: ...elow and press DONE to save Q W E R T Y U I O 64 remaining A S D F G H J K L Shift BACK DONE Basic Auth Password 123 SPACE Z X C V B N M Del P X Basic Auth Password The last step is to turn the Local...

Страница 75: ...ort Account Skyport Skyport Services ON Weather Updates ON Pressing this button will let you know if you are paired with a Skyport account If not then you may follow prompt and instructions to create...

Страница 76: ...cy Heat operation the thermostat will turn on the fan and auxiliary stages of heat when there is a demand for heat The 1st stage of heating and all stages of cooling will be unavailable To exit Emerge...

Страница 77: ...bsite in the background and updates the software and firmware the operating system for touch screen at no cost The ColorDisplay Desktop App allows you to use your computer to ColorDisplay Desktop App...

Страница 78: ...der on your computer Save to SD SD Card Slot At the thermostat Press then Settings SD Card Insert the SD card into the SD Card Slot Next press Press Then press Select the items to import into your the...

Страница 79: ...ions Turn off the power to the Heating Air Conditioning system at the main fuse panel Most systems have a separate breaker for disconnecting power to the furnace Remove the cover of the old thermostat...

Страница 80: ...agrams that follow Wire from the Install on the old thermostat Function new thermostat terminal marked connector marked G or F Fan G Y1 Y Cooling Y1 W1 W Heating W1 0 B Rh R M Vr A Power R C Common C...

Страница 81: ...f there are only 4 wires present that are connected to the existing thermostat there are at least 2 options available to connect the JCI thermostat 1 Use the 4 wires as instructed in the Making 4 Wire...

Страница 82: ...m the HVAC equipment to the thermostat so that there are at least 5 wires available E If you have a heat pump with aux heat the JCI model will require 6 wires R 24Vac C 24Vac W1 O B Reversing Value Y...

Страница 83: ...erminals that the wires are attached to 4 Remove the G wire from the terminal marked G 5 Place the G wire on terminal C 6 Place one end of the 3 long jumper on terminal G 7 Place the other end of the...

Страница 84: ...locate the terminals that the wires are attached to 4 Remove the G wire from the terminal marked G 5 Place the G wire on terminal C 6 Place one end of the 3 long jumper on terminal G 7 Place the other...

Страница 85: ...equires both R 24 VAC Return and C 24 VAC Common be connected to the backplate terminals To remove the thermostat backplate Using the Finger Pull Areas pull the front housing away from the backplate L...

Страница 86: ...cooling If B is chosen the W1 O B terminal will energize in heating 1 When GAS EL or HP is set for GAS EL This switch GAS or ELEC controls how the thermostat will control the Fan G terminal in heating...

Страница 87: ...Heat 5 Wire 1 Stage Cooling 1 Stage Heat 24VAC Power 24VAC Common 1st Stage Heat 1st Stage Cool Fan Residential Commercial 2 Stage Cooling with 3 stage Gas Heat 8 Wire 2 Stage Cooling 3 Stage Heat 24V...

Страница 88: ...r Heat Y2 2nd Stage Compressor Cool or Heat G Fan Residential Commercial Heat Pump with O ReversingValve 6 Wire 1 Stage Cooling 2 Stage Heat R 24VAC Power C 24VAC Common W1 O B Reversing Valve Y1 1st...

Страница 89: ...O B W2 W3 AUX 10K Thermistor Outdoor Sensor Use 18 22 gauge thermostat wire C R G Y1 Y2 W1 O B W2 W3 AUX 10K Thermistor Remote Sensor Use 18 22 gauge thermostat wire SENSOR SENSOR ACC RSEN Indoor Remo...

Страница 90: ...t point limit See Setpoint Limits page 32 SYMPTOM The heating does not attempt to turn on CAUSE The heating setpoint is set too low REMEDY Raise the heating setpoint or raise the heating set point lim...

Страница 91: ...s 40 Choose Network 64 Cleaning 5 25 Clock Display 1 Setting 9 ColorDisplay Desktop App 70 Compressor Lockout 54 Cool 1st stage deadband see Deadband 2nd stage deadband see Deadband Minutes of runtime...

Страница 92: ...runtime 35 2nd stage deadband see Deadband electric strip heat see Aux Heat minutes of runtime 35 3rd stage deadband see Deadband 4th stage deadband see Deadband timer 57 turnoff point 58 electric he...

Страница 93: ...erences 27 Program daily schedule 16 Reset alert messages 22 thermostat settings see Factory Defaults runtime fan filter 22 UV light 22 Reversing Valve 78 Runtime resetting see Reset service filter 22...

Страница 94: ...cycles per hour 56 1st stage to 2nd stage 57 2nd stage to 3rd stage 57 3rd stage to 4th stage 57 Time schedule see Schedule Touch Calibration 25 Upgrade Firmware 62 User InterfaceThemes 27 UV Light r...

Страница 95: ...N WHATSOEVER ALL WORK UNDERTHETERMS OFTHIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS ALL REPLACEMENT PARTS WHETHER NEW OR REMANUFACTURED ASSUME ASTHEIR WARRANTY PERIOD ONLYTHE REMAININGT...

Страница 96: ...Adjustment Range Accuracy Wire Size Deadband Operating Storage Ambient Conditions Compliance Dimensions Shipping Weight This equipment has been tested and found to comply with the limits for a Class...

Страница 97: ...Printed on recycled paper LIT 12012449 Rev 1 10 17...