background image

 

The display now shows the frost protection setup 
prompt. See the 

Enabling Frost Protection (Frost pr)

 

section for setup instructions. 

Enabling Frost Protection (Frost pr) 

Frost protection establishes a minimum heating 
setpoint of 42

°

F (5.5

°

C) to prevent freezing in the zone 

controlled by the thermostat. If enabled, frost 
protection is activated even if the thermostat is set to 
the Off System Mode. If frost protection is active, it is 
displayed as an alarm (

Frost on

 with the backlight lit) 

on the Status Display Menu. 

To enable frost protection while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the frost protection 

setup prompt appears in the display. Press YES to 
enter the frost protection menu. 

2.  Use the UP/DOWN arrow keys to select 

off

 or 

on

Press YES to store the selection. 

The display now shows the maximum heating setpoint 
prompt. See the 

Setting the Maximum Heating 

Setpoint (Heat max)

 section for instructions. 

Setting the Maximum Heating Setpoint (Heat max) 

The maximum heating setpoint establishes the 
maximum temperature in the heating setpoint range 
that can be adjusted from the Main User Menu for both 
occupied and unoccupied periods. The parameter is 
adjustable from 40 to 90

°

F (4.5 to 32

°

C). 

Note: 

When adjusting the temperature, holding the 

keys down changes the temperature by 5 F/C

°

 

increments. 

To set the maximum heating setpoint while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the maximum 

heating setpoint prompt appears in the display. 
Press YES to enter the maximum heating setpoint 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum heating setpoint temperature. Press 
YES to store the value. 

The display now shows the minimum cooling setpoint 
prompt. See the 

Setting the Minimum Cooling Setpoint 

(Cool min)

 section for instructions. 

Setting the Minimum Cooling Setpoint (Cool min) 

The minimum cooling setpoint establishes the 
minimum temperature in the cooling setpoint range 
that can be adjusted from the Main User Menu for both 
occupied and unoccupied periods. The parameter is 
adjustable from 54 to 100

°

F (12 to 37.5

°

C). 

Note: 

When adjusting the temperature, holding the 

keys down changes the temperature by 5 F/C

°

 

increments. 

To set the minimum cooling setpoint while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the minimum 

cooling setpoint prompt appears in the display. 
Press YES to enter the minimum cooling setpoint 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

minimum cooling setpoint temperature. Press YES 
to store the value. 

The display now shows the anti-short cycle timer 
prompt. See the 

Setting the Anti-Short Cycle Timer 

(Anticycl)

 section for instructions. 

Setting the Anti-Short Cycle Timer (Anticycl) 

The anti-short cycle timer establishes the minimum 
on/off times for the cooling and heating stages. The 
timer is adjustable from 0 to 5 minutes in 1-minute 
increments. Set the anti-short cycle to 0 for equipment 
that possesses its own anti-short cycle timer. 

!

  CAUTION:  Risk of Property Damage. 

Do not set the T600HPP-2 anti-short cycling timer to 
0 minutes, if the controlled equipment is not 
protected by its own internal anti-short cycling timer. 
Setting the anti-short cycling timer to 0 minutes may 
result in damage to the controller. 

To set the anti-short cycle time while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the anti-short cycle 

timer prompt appears in the display. Press YES to 
enter the anti-short cycle timer menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

minimum on/off times for the heating and cooling 
stages. Press YES to store the value. 

The display now shows the heating cycles per hour 
setup prompt. See the 

Setting the Maximum Heating 

Cycles per Hour (Heat cph)

 section for instructions. 

8    

T600HPP-2 Programmable Thermostat Installation Instructions 

Содержание T600HPP-2

Страница 1: ...r in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills stairwells or outside doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the thermostat cover using a Phillips head screwdriver Open the th...

Страница 2: ...ks and reinsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram Figure 5 2 Gently push excess wire back into wall plug the wall hole with fireproof material to prevent drafts from affecting ambient temperature readings and install screw terminal blocks back onto the PCB 3 Reattach the thermosta...

Страница 3: ...st stage compressor on a call for heating or cooling Energizes second stage compressor on a call for heating or cooling Energizes fan in accordance with the selected fan mode 24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for auxiliary heat Energizes auxiliary heat Energizes reversing valve configurable to energize valve on a call for heat or call for cooling Con...

Страница 4: ...esumes scrolling NO key when you do not desire a parameter change and to advance to the next menu item MENU key to access the Main User Menu or exit the menu UP DOWN arrow keys to adjust values activate a Temporary Setpoint Configuration Key T600_TEC_Config_Key Figure 7 Configuration Key Location Backlit Liquid Crystal Display LCD The T600HPP 2 uses a two line eight character backlit display Low l...

Страница 5: ...changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Status Display Menu Table 1 Installer Configuration Menu Remove the cover and press the CONFIG key from the Status Display Menu to enter the Installer Configuration Menu Configures Digital Input 1 Default No Function None See the Configuring the Digital Input...

Страница 6: ...t 40 F 40 C See the Setting the Cooling Lockout C lock section Sets the Number of Events in 24 Hour Period Default Two Events 2 0 See the Selecting the Number of Events 2 4event section Sets the Auxiliary Contact as Normally Open or Normally Closed Default Normally Open N O See the Configuring the Auxiliary Contact Aux cont section Enable Disable Progressive Recovery Default Off See the Enable Dis...

Страница 7: ...keys to locate the desired function for the Digital Input 2 Press YES to select the desired function The display now shows the keypad lockout setup prompt See the Enabling Keypad Lockout Lockout section for instructions Enabling Keypad Lockout Lockout The T600HPP 2 has three levels of keypad lockout The levels and degree of lockout are shown in Table 2 To set the keypad lockout level while in the ...

Страница 8: ...ns Setting the Minimum Cooling Setpoint Cool min The minimum cooling setpoint establishes the minimum temperature in the cooling setpoint range that can be adjusted from the Main User Menu for both occupied and unoccupied periods The parameter is adjustable from 54 to 100 F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the...

Страница 9: ...ing the Heating Cooling Deadband Deadband The heating cooling deadband setting establishes the minimum difference between the heating and cooling setpoints The range is adjustable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint prompt appears in the displ...

Страница 10: ...ments of 1 F 0 5 C To change the outdoor air sensor calibration offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the outdoor sensor calibration prompt appears in the display Press YES to enter the outdoor sensor calibration menu 2 Use the UP DOWN arrow keys to adjust the correction that should be applied to the sensor reading Press YES to store the offset The displ...

Страница 11: ...ux cont The auxiliary contact is an output that can be used to energize peripheral devices for example lighting equipment exhaust fans and economizers The contact can be configured as normally open or normally closed and toggles with the internal occupied unoccupied schedule or the remote NSB contact on one of the digital inputs if used Table 3 Operation of Auxiliary Contact Configuration Setup Co...

Страница 12: ...ature selects how the auxiliary heat is used on heat pump models The selections are Comfort or Economy mode Comfort Mode in heating mode If the heat pump is not able to satisfy the heating setpoint the auxiliary heat is energized to satisfy the same heating setpoint Economy Mode in heating mode If the heat pump is not able to satisfy the heating setpoint the auxiliary heat is energized to satisfy ...

Страница 13: ...r Menu by pressing the MENU key during normal thermostat operation The Main User Menu contains the basic operating features of the T600HPP 2 The Main User Menu uses Auto Help Auto Help is displayed automatically in the Main User Menu when there is a pause in programming activity To exit Auto Help continue with the programming selection When the thermostat is in the Main User Menu and is left unatt...

Страница 14: ...pt 2 Press YES to resume the programmed schedule The T600HPP 2 thermostat returns to the Status Display Menu Entering Permanent Temperature Setpoints The first prompt appearing in the Main User Menu of the T600HPP 2 thermostat is to set the permanent temperature setpoints Permanent setpoints are stored in the programmed schedule To enter the permanent heating and cooling setpoints for the occupied...

Страница 15: ... the default setting Unocc HT set Y N Cooling Mode cool Cooling operation only Heating Mode heat Heating operation only Unocc HT 62 0 F Off Mode off The T600HPP 2 is off However when frost protection is on see the Enabling Frost Protection Frost pr section the thermostat still calls for heat if required F C set Y N Emergency Heat Mode emergenc Forced auxiliary heat operation mode only To set the s...

Страница 16: ... Press MENU from the Status Display Menu to enter the Main User Menu Answer NO to all prompts until the schedule set prompt appears in the display Press YES to enter the scheduling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday Use the UP DOWN arrow keys to set the occupied start time Press Y...

Страница 17: ...pt appears in the display Press YES to enter the scheduling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday Use the UP DOWN arrow keys to set the first occupied start time Press YES to enter the time Use the UP DOWN arrow keys to set the first unoccupied start time Press YES to enter the time ...

Страница 18: ...e day 6 Press YES to choose the time format or NO to access the Main User Menu exit prompt 7 Use the UP DOWN arrow keys to select the desired time format Press YES to enter format 8 Press YES to return to the Status Display Menu or NO to return to the time set menu When the thermostat scrolls through the day and time the new day and time should be displayed and no alarm backlit should be present I...

Страница 19: ...Table 9 Optional Accessories Includes Mounting Hardware Description Product Code Number Remote Indoor Temperature Sensor SEN 600 1 Outdoor Air Temperature Sensor SEN 600 2 Duct Mount Temperature Sensor SEN 600 3 Remote Indoor Temperature Sensor with Occupancy Override and LED SEN 600 4 T600HPP 2 Programmable Thermostat Installation Instructions 19 ...

Страница 20: ...pment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accord...

Отзывы: