CCS Smart Equipment Control Board for Single Packaged Unit (SPU) Controller Installation Instructions

6

Operation

The controllers are supplied in a pre-configured format. 
You do not need to configure the controller. Refer to the 

Commercial Comfort System (CCS) Operation 
Overview Technical Bulletin (LIT-12011617) 

or the 

Smart Equipment Controls (SEC) Quick Start Guide 
(LIT-12011938)

 for information on operating modes and 

functionality.

Troubleshooting

Use the following information to troubleshoot the 
System Manger and Zone Coordinator.

Power Status LED

The display backlight and green Power LED remain lit 
as long as power is applied to the C and 24V terminals.

The red Fault LED lights, goes off briefly, and then 
flashes throughout the startup sequence.

The green SA Bus LED lights briefly.

During the startup sequence, the joystick, the Enter 
button, and the Cancel button are 

not

 functional.

The LCD shows a countdown on the top line. 

After approximately 15 seconds, the green SA Bus 
LED does one of the following:

Lights to indicate the UCB has not established 
communication and is awaiting communication 
from SA Bus devices

Flashes to indicate the UCB established 
communication with SA Bus devices

After the startup sequence finishes, the display shows 

XxXx

 on both lines if no alarm is active. The red Fault 

LED stops flashing and turns off. The joystick, Enter, 
and Cancel buttons are operational.

Communication Bus Problems

Several factors may influence the behavior of the 
communication bus. In addition, certain problems can 
affect the bus in multiple ways and have multiple 
symptoms, which makes the exact diagnosis difficult. 
For example, duplicate addresses on the bus can 
degrade performance, make the device go offline, or 
stop communication completely.

Incomplete Address

With the SEC controller for VAV, COBP must have the 
address switch set to 4 on the zone communication 
bus. Other settings prevent the SPU from 
communicating on the System Communication bus.

Duplicate Addresses

Two or more devices on a communication bus cannot 
have the same address. For example, two SPUs on the 
System communication bus cannot both have the 
address 4. If two devices on the same bus have the 
same address, performance can degrade or serious 
communication problems may occur. These problems 
include the devices not coming online or all 
communication stopping completely. 

Check for duplicate addresses in the following ways 
depending on the severity of the situation:

If the bus performance is degraded, check the 
address switch settings at the devices with 
unreliable communications.

If a specific device is not communicating, remove 
the device with communication problems and 
check if the device address remains online at the 
System Manager or Zone Coordinator.

If the bus communication problems are severe, 
and no communication is present (or if you cannot 
determine where communication is unreliable), 
partition (disconnect and isolate a portion of the 
bus for testing purposes) and test the bus portion 
connected to the System Manager and Zone 
Coordinator controllers.

Figure 7:  Startup Countdown

Содержание SE-SPU101 Series

Страница 1: ... the UCB requires a communication bus connection Address selection is required for networking with a CCS Building Automation System BAS Power Wiring The SEC UCB controller is factory wired for 24 VAC power This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection ag...

Страница 2: ...r with the wire nuts Follow the stripping and connecting procedure in Step 1 through Step 8 Run the cable from the last unit to the location of the System Manager or Zone Coordinator Follow the connection instructions for the System Manger or Zone Coordinator Figure 4 displays an example communication riser 9 Make sure all the SPUs are powered and operating properly Note Be sure you observe polari...

Страница 3: ...ion cable terminations on the SPU controller board Figure 4 shows the VAV SPU controller communication riser Figure 3 VAV SPU Control Board Communication Terminations Communication Cable to Next VAV box Communication Cable to Next VAV box Zone Dampers and Bypass Damper Move the 4 position terminal block from the Thermostat inputs to the FC Bus connection of the communications card ...

Страница 4: ...W G 3 C O ND U CTO R TW ISTED SH IELD ED W IR E W ITH D RAIN System C om m unication B us Zone Communication Bus S 1 S 2 J 8 J 7 J 6 System Bus Zone Bus C O M C O M C O M 24 V O n O f f 2 4 V AC C O M C O M S B S B Z B Z B C O M E O L O N O f f E O L O N S 1 S 2 J 8 J 7 J 6 System Bus Zone Bus C O M C O M C O M 24 V O n O f f 2 4 V AC C O M C O M S B S B Z B Z B C O M E O L O N O f f E O L O N Ter...

Страница 5: ...3 COM AI 4 Monitored Contact To Temperature RH CO2 Sensor Building Pressure Light Sensor Refrigerant Sensor Common Flow To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Scheduled Item 3 To Scheduled Item 4 Non CCS HVAC System Universal CV Unit Controller 24V COM Zone Sensor COM AI 1 COM AI 2 1 2 3 4 BO 1 BO 2 BO 3 BO 4 BO 5 C R G Y1 Y2 W1 W2 COM AI 6 CO...

Страница 6: ...ay influence the behavior of the communication bus In addition certain problems can affect the bus in multiple ways and have multiple symptoms which makes the exact diagnosis difficult For example duplicate addresses on the bus can degrade performance make the device go offline or stop communication completely Incomplete Address With the SEC controller for VAV COBP must have the address switch set...

Страница 7: ...d of the zone bus trunk Verify that only the EOL switch at the end of the system bus is set to ON and all other system bus EOL switches are set to OFF Check connections polarity and lengths Verify that communications loops are less than approximately 304 m 1 000 ft total in length If you are using one transformer to power multiple devices verify that the device 24 VAC power connection follows the ...

Страница 8: ...perating 4 to 158 F 20 to 70 C 10 to 90 RH noncondensing Storage 40 to 194 F 40 to 85 C 5 to 95 RH noncondensing Processor RX631 Renesas microcontroller Memory 2 MB internal program flash 32 KB internal E2Data flash 4 MB external serial flash memory Input and Output Capabilities SE SPU1011 1 9 AIs 7 10k RTD 1 0 to 10 VDC 1 24 VAC Voltage Monitor 13 BIs 24 VAC input with contact cleaning circuits 5...

Отзывы: