background image

CCS Smart Equipment Control Board for Single Packaged Unit (SPU) Controller Installation Instructions

2

In certain cases, you may need to share a 24 V 
transformer with multiple CCS devices. Be sure that 
you maintain cons, -, and common wiring 
terminations on the shared CCS devices.

Setup and Adjustments

To quickly set up your CCS network:

1.

On each end of the 3-conductor cable, strip the 
outside insulation back approximately 2 in. 
(51 mm).

2.

Tear off excess foil shield, leaving the bare drain 
wire and the three insulated conductors. 

3.

On each end of the three insulated conductors in 
the cable, strip the insulation back approximately 
1/8 to 1/4 in. (4 to 7 mm).

4.

Choose a color pattern to follow and insert each of 
the three conductors into one each of the three 
terminals on the CCS board communication 
connector. 

5.

Tighten each terminal until the wire is secure. 

6.

Ground the drain wire at one end only of the 
communication trunk. Do this on the last unit in 
line. 

Use an existing hole or drill a hole and insert a 
sheet metal screw in the back plate below the 
communication connector. 

Wrap the bare drain wire around the screw and 
tighten the screw. This is the only location where 
the shield is grounded.

7.

Daisy chain the three-conductor wire between the 
remaining SPUs. Connect the drain wires together 
with the wire nuts. Follow the stripping and 
connecting procedure in Step 1 through Step .

8.

Run the cable from the last unit to the location of 
the System Manager or Zone Coordinator. Follow 
the connection instructions for the System Manger 
or Zone Coordinator. Figure 4 displays an example 
communication riser.

9.

Make sure all the SPUs are powered and operating 
properly.

Note:

Be sure you observe polarity of each of the 

conductors in the communication cable.

Communication Bus

The UCB default address is set to 4. The available 
values range from 0 to 127. To view the UCB Network 
Address, use the joystick and the two push buttons 
below the LCD, to navigate through the menus to the 
Commissioning menu (Figure 1). 

Up and down movements of the joystick move the > 
cursor and scroll through the selections in the active 
section of the menu (Figure 2). 

Each menu selection represents either a submenu or a 
property. Press Enter to display the items in the 
submenu or the values of the selected property.

Once you navigate to the Commissioning menu, use 
the cursor to scroll to the Network submenu. From the 
Address submenu, press Enter to display the current 
network address. Move up or down with the joystick to 
display the values of other properties.

IMPORTANT:

Do not inter, -, and 

common 24 V terminations when sharing a 
transformer with multiple CCS devices. 
Interchanging these terminations can cause damage 
to the controller.

Figure 1: Joystick and Push Buttons on UCB

ENTER

CANCEL

JOY

Figure 2: UCB Top Level Menu

Содержание SE-SPU101 Series

Страница 1: ... the UCB requires a communication bus connection Address selection is required for networking with a CCS Building Automation System BAS Power Wiring The SEC UCB controller is factory wired for 24 VAC power This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection ag...

Страница 2: ...r with the wire nuts Follow the stripping and connecting procedure in Step 1 through Step 8 Run the cable from the last unit to the location of the System Manager or Zone Coordinator Follow the connection instructions for the System Manger or Zone Coordinator Figure 4 displays an example communication riser 9 Make sure all the SPUs are powered and operating properly Note Be sure you observe polari...

Страница 3: ...ion cable terminations on the SPU controller board Figure 4 shows the VAV SPU controller communication riser Figure 3 VAV SPU Control Board Communication Terminations Communication Cable to Next VAV box Communication Cable to Next VAV box Zone Dampers and Bypass Damper Move the 4 position terminal block from the Thermostat inputs to the FC Bus connection of the communications card ...

Страница 4: ...W G 3 C O ND U CTO R TW ISTED SH IELD ED W IR E W ITH D RAIN System C om m unication B us Zone Communication Bus S 1 S 2 J 8 J 7 J 6 System Bus Zone Bus C O M C O M C O M 24 V O n O f f 2 4 V AC C O M C O M S B S B Z B Z B C O M E O L O N O f f E O L O N S 1 S 2 J 8 J 7 J 6 System Bus Zone Bus C O M C O M C O M 24 V O n O f f 2 4 V AC C O M C O M S B S B Z B Z B C O M E O L O N O f f E O L O N Ter...

Страница 5: ...3 COM AI 4 Monitored Contact To Temperature RH CO2 Sensor Building Pressure Light Sensor Refrigerant Sensor Common Flow To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Scheduled Item 3 To Scheduled Item 4 Non CCS HVAC System Universal CV Unit Controller 24V COM Zone Sensor COM AI 1 COM AI 2 1 2 3 4 BO 1 BO 2 BO 3 BO 4 BO 5 C R G Y1 Y2 W1 W2 COM AI 6 CO...

Страница 6: ...ay influence the behavior of the communication bus In addition certain problems can affect the bus in multiple ways and have multiple symptoms which makes the exact diagnosis difficult For example duplicate addresses on the bus can degrade performance make the device go offline or stop communication completely Incomplete Address With the SEC controller for VAV COBP must have the address switch set...

Страница 7: ...d of the zone bus trunk Verify that only the EOL switch at the end of the system bus is set to ON and all other system bus EOL switches are set to OFF Check connections polarity and lengths Verify that communications loops are less than approximately 304 m 1 000 ft total in length If you are using one transformer to power multiple devices verify that the device 24 VAC power connection follows the ...

Страница 8: ...perating 4 to 158 F 20 to 70 C 10 to 90 RH noncondensing Storage 40 to 194 F 40 to 85 C 5 to 95 RH noncondensing Processor RX631 Renesas microcontroller Memory 2 MB internal program flash 32 KB internal E2Data flash 4 MB external serial flash memory Input and Output Capabilities SE SPU1011 1 9 AIs 7 10k RTD 1 0 to 10 VDC 1 24 VAC Voltage Monitor 13 BIs 24 VAC input with contact cleaning circuits 5...

Отзывы: