Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
237/346
6.5.10
Timer values - screw compressors
No.
Value
Factory
Low
High
Unit
Adjust-
able
1
Start-start delay 1/2
1200
600/60
3600
Sec.
Yes
2
Stop-start delay
300
60
3600
Sec.
Yes
3
Start delay
300
0
3600
Sec.
Yes
4
Stop delay
300
60
3600
Sec.
Yes
5
Suction ramp
0
0
1200
Sec.
Yes
6
Slide max.
300
60
3600
Sec.
Yes
7
Prelub. 1/2/3/4/5/6
10/60/0/6/50/0
0
120
Sec.
Yes
8
Oil flow 1/2/3/4/5/6
600/90/60/120/600/0
-
-
Sec.
No
9
Oil flow delay 1/2/3/4/5/6
50/0/20/10/0/50
-
-
Sec.
No
10 No oil/flow 1/2/3/4/5/6
10/2/6/120/30/30
-
-
Sec.
No
11 Lubrication time/flow 1/2
60/300
-
-
Sec.
No
12 Differential pressure OK
60
-
-
Sec.
No
13 Oil pressure low 1/2/3/4
45/300/45/15
-
-
Sec.
No
14 Filter diff. pressure high 1/2
300/600
60
1200
Sec.
Yes
15 Oil temperature low
300
-
-
Sec.
No
16 Oil temperature high
300/300
5
300
Sec.
No
17 Superheating low
300
-
-
Sec.
No
18 Superheating high
300
-
-
Sec.
No
19 Discharge pressure overload
300
-
-
Sec.
No
20 Current overload
300
-
-
Sec.
No
21 Motor start
45
5
120
Sec.
Yes
22 PMS feedback
60
10
3600
Sec.
Yes
23 F.F. Pump start
10
5
30
Sec.
Yes
24 Oil pump start
10
5
30
Sec.
Yes
25 Oil rectifier start
900
0
3600
Sec.
Yes
26 Oil rectifier delay
300
0
3600
Sec.
Yes
27 Oil rectifier disable
3600
0
7200
Sec.
Yes
28 Start high pressure
30
0
120
Sec.
Yes
29 Not used
-
-
-
-
-
30 Capacity negative
5000
60
20000
Sec.
Yes
31 Start unload 1/2/3
15
0
60
Sec.
Yes
32 Low suction pressure
0
0
60
Sec.
Yes
33 Lubricating pressure 1/2
120/180
-
-
Sec.
No
34 Vi-pause 1/2
60/7
-
-
Sec.
No
35 Oil log shutdown
30
0
300
Sec.
Yes
36 Low oil flow 1/2
180/180
-
-
Sec.
No
37 Oil circuit alarm
600
-
-
Sec.
No
38 Oil circuit shutdown
900
-
-
Sec.
No
39 SSSTV stop delay
40
20
60
Sec.
Yes
40 Max. start-up time
600
60
24000
Sec.
Yes
41 Oil return open
30
5
600
Sec.
Yes
42 Oil return close
900
0
32400
Sec.
Yes
43 By-pass start
600
0
1200
Sec.
Yes
44 Flow evaporator
5
2
15
Sec.
Yes
45 Flow condenser
5
2
15
Sec.
Yes
46 Oil return evaporator
5
2
60
Sec.
Yes
47 Oil return delay
600
0
1200
Sec.
Yes
48 Pump down
10
0
600
Sec.
Yes
49 PMS delay
0
0
900
Sec.
Yes
50 Critical low oil circuit
25
-
-
Sec.
No
51 Start rpm limiter
300
60
3600
Sec.
Yes
52 High internal pressure
25
-
-
Sec.
No