Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
137/346
Compressor control and surveillance
3.5
Compressor control - user functions
3.5.1
External starting permission - immediate stop
The input must be connected for the compressor to run in
Manual
,
Auto
or
Remote
. If this input is
opened during operation the compressor stops immediately.
When the input is open
Stopped
appears in the bottom line of the display.
3.5.2
External starting permission - normal stop
This input and
External starting permission - immediate stop
must be connected before the compressor
is going to start in
Auto
or
Remote
but it can be started in
Manual
mode.
If the input has not been connected, the display will show
Stopped
in the bottom line. If the input is
opened during operation, the compressor capacity will be decreased to minimum and the compressor
will stop on its
Delay before stop
timer.
In case the input
Capacity down blocked
is connected, the compressor will not reduce capacity once the
input
External starting permission - normal stop
is opened.
3.5.3
Capacity down blocked
This function is enabled in
Setup/configuration/Plant/Cap down blocked.
When the compressor is in maximum capacity in
Auto
or
Remote
it can be locked in this state by closing
a digital input. See wiring diagrams. The input overrules
External starting permission - normal stop
.
If the compressor runs in limited operation (a limiting function is active), it will however reduce its ca-
pacity. When the state of operation is back to normal, the compressor will return to full load. See also
.
If the input is connected while the compressor is ready to start in
Auto
or
Remote
, the compressor will
be started by force irrespective of actual regulator settings.
In case the chiller and flow condenser function have both been configured, it will not be possible to use
the capacity blocked function. See section
3.6 Compressor control - chiller functions
3.5.4
Power management system (PMS)
This function works in
Manual
,
Auto
or
Remote
operation. It is a kind of "an agreement to start" system,
consisting of one digital output
PMS Request
, which is set when the compressor should start, and a digi-
tal input
PMS feedback
. This input must be set before the timer
PMS feedback
expires in order for the
compressor to start.
The shutdown
PMS error
is activated if the input
PMS feedback
has not been set before the timer
PMS
feedback
expires.
If the
PMS feedback fixed
is configured to No the feedback signal can be removed during operation with-
out stopping the compressor.
If the
PMS feedback fixed
is configured to Yes the feedback signal cannot be removed during operation
without stopping the compressor, having a PMS error shutdown.
3.5.5
Cold store function
This function is connected to the regulators for capacity regulation of the compressor. Usually, the com-
pressor is going to start in
Auto
or
Remote/Multisab
if the measured value is outside the neutral zone
and a capacity requirement exists.
If the
Cold store
function has been selected in the menu
Compr. Control
, the compressor will not start
until the measured value is outside the P Band. After this it will regulate normally in accordance with the
set point.
Example of cold store function:
UniSAB III is set for suction pressure regulation with
Set point (Sp) = -40
°