Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
145/346
Compressor control and surveillance
3.6
Compressor control - chiller functions
Please note that when using the chiller functions described in this section there are certain limitations in
the use of some of the other UniSAB III functions, e.g. oil cooling functions.
•
When the chiller function
Level control LP/HP
or
Expansion control DX
is used it is not possible
to use the
By-pass
function - and vice versa.
•
When the chiller function
Level control LP/HP
or
Expansion control DX
or the
By-pass
function
is used it is only possible to use the following two oil cooling functions:
–
Water cooling
for reciprocating compressors
–
Intermediate liquid injection
for two step reciprocating compressors
All other
Oil cooling
functions are blocked and cannot be used.
•
When the chiller function
Flow condenser
is used it is not possible to use the
Cap down blocked
function - and vice versa.
•
When the new
Thermo pump - internal
function is used it is only possible to use the chiller func-
tions
Oil return from oil separator
and
Flow condenser
.
Chiller function
configured
Used I/O
Other functions using these I/O
Process out temp.
AI6
Process in temp.
AI5
Oil return from oil separator
DO19
Oil return from evaporator
DI13
DO18
Thermo pump - internal (recip.)
Oil return (recip.)
Oil rectifier (screw)
By-pass function
(or level control LP/HP)
(or expansion control DX)
DO16
Oil cooling - normal (screw/recip.)
Thermo pump - external (recip.)
Thermo pump - internal (recip.)
Dual 4-20 mA HLI valve (screw)
HLI - AKV stop valve (screw)
Motor valve (screw)
Flow evaporator
DI12
Thermo pump - internal (recip.)
Flow condenser
DI11
Cap down blocked
Liquid level limiter
DI5
Filter diff. pressure
Level control LP/HP
Expansion control DX
DO016
AI3
AO2
See
By-pass function
Table 32
3.6.1
Process out temp.
Display and monitor the analogue input
Process out temperature
in the picture
Control values/Process
temp/Process out temp/Values
.
Alarm and shutdown supervision settings are made in the picture
Control values/Process temp/Process
out temp/Limits
.
The PID regulator settings for compressor capacity regulation are made in the picture
Control values/
Process temp/Process out temp/Control
. This function is enabled in
Set-up/Configuration/Plant/Proces
out temp
. Monitoring is always active and the PID regulator is active when the compressor is running.
3.6.2
Process in temp.
Display and monitor the analogue input
Process in temperature
in the picture
Control values/Process
temp/Process in temp/Values
.