Operating manual – DualPAC with reciprocating compressors
28/63
0012201 en 2021.04
3.2.6
Receiver
The outlet of the condenser is connected to a small receiver, see Fig. 14.
The receiver is equipped with two sight glasses, pos. 1, a purge valve, pos. 2, an electronic level
transmitter, pos. 3, and a drain valve, pos. 4.
The outlet pipe, pos. 5, comes either from the bottom of the receiver or from the condenser if it
has a built-in subcooler.
Fig. 14: DualPAC receiver
3.2.7
Air purge valve
If there is air or other non-condensable gases in the refrigeration/heat pump plant it tends to ac-
cumulate in the receiver or the condenser.
On DualPAC, the air purge valve is fitted at the top of the receiver, pos. 2 in Fig. 14.
During air purging the air purge valve should be connected to an open vessel containing water via
a refrigerant hose.
The air will leave the water as bubbles whereas the R717 gas will be absorbed by the water.
Note:
R717 containing water must be disposed of in a correct and proper way, see section
.