Operating manual - ComPAC
011769 en 2020.03
41/56
5.3
Starting
5.3.1
Starting procedures
Starting and stopping can only be carried out from Unisab III. The operator must always make
sure that the appropriate external starting conditions exist before start-up.
Fig. 18: Unisab III front
5.3.2
Normal start-up procedure
1.
Confirm that the system conditions permit the chiller to start.
2.
Press the start button on Unisab III.
3.
Allow the compressor to start up and stabilise.
4.
Check the following on the chiller unit:
a.
Mechanical tightness of the external piping, bolts and valves.
b.
No oil and refrigerant leaks.
If not satisfactory, shut down the chiller and correct the problem.
Top bar
Content area
Info bar
F-key area
Содержание SABROE ComPAC
Страница 1: ...ComPAC Chiller unit with screw compressor Operating manual en...
Страница 2: ......
Страница 43: ...Operating manual ComPAC 011769 en 2020 03 43 56 Operating instructions Fig 19 P I diagram for ComPAC...
Страница 57: ......