S321-IP Network Controller

 Hardware Installation

24-10239-480 Rev. F

 

19

See the diagram below for the 

Network

 menu navigation map:

T

ECHNICAL

 S

PECIFICATIONS

The terminal is expected to operate at moderate temperature variation, non-
condensing humidity variation, moderate vibration, and possible dust 
contamination.

Item

Specification

Input Power

+12 to +24 VDC or 16 to 24 VAC at 24W

Reader Interface

• 2-wire Wiegand (up to 256 bits)
• 12 VDC, 250 mA (typical), 500 mA (peak)
• Red indicator
• Green indicator

General Purpose Inputs Resistive load

Relay Outputs

1 A max. 0-24 VDC/VAC, 25 VA max

Red LED/Green LED 
Outputs

50 mA max. 0-24 VDC.
These open collector outputs can be damaged by alternating 
current (AC) potentials as low as 1 VAC. Connect the LED 
outputs only to direct current (DC) loads up to 24VDC.

Communications

10/100 Base-T Ethernet using TCP/IP protocol

Certifications

• FCC, Class B
• CE Mark
• C-Tick

SNMP Agent 
Enable

System 
Information

Community

Traps 
Configuration

FTP Enable

Certificate

Private Key
Self-Signed 
Certificate

IP

SNMP

FTP

SSL

HTTP

Main

Database

Network

Username 
and Password

Timeout

Maximum Bytes 
Allowed

Admin Account

User Account

DHCP Enable

IP Address

Network Mask

Gateway

MAC Address

P2000 Host 
Name

User Name 
or IP
Name

P2000 Host 
IP Address

Содержание S321-IP

Страница 1: ...24 10239 480 Revision F December 2017 hardware installation S321 IP Network Controller ...

Страница 2: ...t of other manufacturers When unpacking your equipment keep all original manufacturer documentation for future reference Technical Support For factory technical support Johnson Controls authorized field technicians or authorized dealer representatives can contact Global Security Solutions Technical Support by phone at 866 893 0423 or 414 524 1214 or by email at support globalsecuritysolutions jci ...

Страница 3: ... cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Canada CAN ICES 3 A NMB 3 A European Union This product complies with the requirements of the EMC Directive This equipment must not be modified for any reason and it must ...

Страница 4: ...ontrolled by a switch 5 The sole use of a class 2 transformer to power the S321 IP would not provide battery standby power 6 The RS485 reader interfaces were not investigated by Underwriters Laboratories 7 For a UL 294 Listed system the following Listed readers may be used 8 Model S321 IP must use a Class 2 direct plug in transformer rated 120 VAC input and 24 VAC 50 VA output from one of the foll...

Страница 5: ...asic Commissioning on page 10 The S321 IP User Interface on page 16 Technical Specifications on page 19 Maintenance on page 20 UNPACKING THE EQUIPMENT Inspect the S321 IP shipping containers as soon as you receive them with the delivery agent present If a container is damaged open it immediately inspect the contents and have the agent make note on the shipping document Check the purchase order aga...

Страница 6: ...r on a flat surface 1 Fully extend the white clips located on the top and bottom of the controller You may need to remove the connectors 2 Mount the controller to the surface with mounting screws 3 Replace the connectors if previously removed To mount an S321 IP controller on a DIN rail 1 Fully extend the white clips located on the bottom of the controller You may need to remove the connectors 2 H...

Страница 7: ...g is one cause of power line transients others can be internal or external to the building environment The general application of transient surge suppression is low cost insurance to ensure long life of the equipment being installed Lithium Battery The S321 IP contains a lithium battery that is used for realtime clock backup The lithium battery is shipped from the factory charged and operational I...

Страница 8: ...and gently move the battery out of the holder while keeping the battery pried up 5 Dispose of the old battery according to local requirements 6 Insert the new battery into holder IMPORTANT The lithium battery is polarized Ensure the side marked faces out that is towards you 7 Close the plastic enclosure and secure it with the screw 8 Re connect the power to the S321 IP CAUTION Risk of Explosion Re...

Страница 9: ... Rs485 DATA0 Rs485 COM POWER GREEN LED COM RED LED REX COM DOOR CONTACT 12 24 VAC VDC RDR n PANEL RDR n RDR n RDR n CAL POWER RDR Request to Exit Device RDR Red Light RDR Green Light RDR Door Reader Calibration Resistor To the power supply RDR Door Contact RDR 1 General Purpose Input 5 RDR 1 General Purpose Input 6 RDR General Purpose Input 3 RDR General Purpose Input 4 RDR Shunt RDR Strike READER...

Страница 10: ...s External Circuits 4 state operation requires two external resistors and switch circuit connected between an input point and COM 2 state operation requires an external switch connected between an input point and COM For wiring details see Wiring Input Devices on page 8 Output Points Description of Signals The following are open collector outputs with voltage range for these signals of 0 24 VDC li...

Страница 11: ... the S321 IP to the network The S321 IP communicates with the P2000 server via 10 100Base T Ethernet using the TCP IP protocol CABLE REQUIREMENTS This table describes the recommended cable to use when wiring the S321 IP Reader 1 Strike Reader 1 Shunt Reader 2 Strike Reader 2 Shunt Description Recommended Cable Type Maximum Segment Length S321 IP to Power Supply1 Listed 18 AWG hook up wire Wire sho...

Страница 12: ...itch Wiring The tamper switch connects to a general purpose input point To be operational the tamper switch must be wired to one of the unused input points on any S321 IP in the enclosure and programmed Request to Exit Belden 8442 1 twisted unshielded pair 22 AWG 500 feet 152 m Reader Power2 Belden 9740 1 twisted unshielded pair 18 AWG Refer to reader manufacturer s specification for power require...

Страница 13: ...e requirements as described under Cable Requirements on page 7 are not guaranteed when the resistor value is less than 500 ohms or when all the inputs on an S321 IP are not wired with the same resistor values To use the Calibrate with Resistor method install a resistor matching the resistors wired to a 4 state input across the CAL RESISTOR contacts and issue a Calibrate with Resistor command Use t...

Страница 14: ...ndows Server 2008 Windows 8 Windows 7 or Windows Vista 32 or 64 bit operating systems are supported Compatible web browser such as Windows Internet Explorer Version 6 0 or higher or Mozilla Firefox Version 1 0 or higher For proper operation cookies from the S321 IP must be allowed NOTE Functionality of the browser s Forward Back and Refresh buttons may differ depending on the type of browser and t...

Страница 15: ...ace using the default static IP address of 192 168 0 1 or the default controller name s321ip when DNS service is running Assign a static IP address network mask and gateway to the S321 IP In systems with the DNS server assign a unique name to the controller Configure the following network protocol settings as needed FTP SSL and HTTP Define the P2000 host IP configuration settings on the Configurat...

Страница 16: ...s or no readers all general purpose I Os Add cardholder badges to the database If you use FTP you can import badge data from a spreadsheet or from another panel If you use the badge enrollment feature add names to the cardholder records once the badges are enrolled in the system Power off the S321 IP Set DIP switches 6 and 8 to ON up Power on the S321 IP Turn DIP switch 6 to OFF down Mount wire an...

Страница 17: ...21 IP is connected to a DHCP network use the Lantronix DeviceInstaller software utility provided on the S321 IP Network Controller CD to determine the IP address the DHCP server assigned to the controller Before determining the IP address 1 Find out the controller s Media Access Control MAC address It is listed on the sticker on the left side as well as top of the S321 IP You need to match the MAC...

Страница 18: ...face 2 Install the DeviceInstaller utility 3 From the Windows taskbar select Start All Programs or Programs Lantronix DeviceInstaller DeviceInstaller to launch the DeviceInstaller software utility 4 When DeviceInstaller launches the utility automatically searches for all S321 IP controllers on the network and lists them in the right pane 5 Locate the S321 IP controller s MAC address under the Hard...

Страница 19: ...ic IP use as follows turn switch 6 down OFF 4 Log on to S321 IP see Logging On and Off 5 Assign a new static IP address to the controller using the S321 IP user interface Log in and go to Network IP On the IP page configure the IP address under the Static IP Configuration section Refer to the S321 IP Network Controller Configuration and Operation Manual for more information 6 The controller reboot...

Страница 20: ...lick OK The Main menu options appear To log off from the S321 IP controller s user interface 1 To log off from the S321 IP user interface click the Logout link at the upper right corner of any page or simply close the browser window In addition the S321 IP user interface automatically logs off the current user if the system does not detect any activity for 20 minutes THE S321 IP USER INTERFACE Thi...

Страница 21: ...menu navigation map Menu Bar Menu Options Logout Link Commands System Info Alarms and Events Main Database Network Reboot System Firmware Upgrade Database Operations Logger Operations Output Operations Input Operations Reader Keypad Operations Badge Count Logger Record Count ACM Firmware Version NIM Firmware Version Reader Info Output Info Schedule Info Input Info ...

Страница 22: ...Savings Time Date Configuration Report Status Input and Latch Enable Name Index Name Index Flash Period Duration Report Status Output Enable Name Index Schedule Enable Define Days Times Name Index Holiday Enable Type Month Day Year Storage Time Last First Name Badge Number Facility Code Assign Schedules Last First Name Security Level PIN Override Status Schedule Config Holiday Config Logger Config...

Страница 23: ...oad Relay Outputs 1 A max 0 24 VDC VAC 25 VA max Red LED Green LED Outputs 50 mA max 0 24 VDC These open collector outputs can be damaged by alternating current AC potentials as low as 1 VAC Connect the LED outputs only to direct current DC loads up to 24VDC Communications 10 100 Base T Ethernet using TCP IP protocol Certifications FCC Class B CE Mark C Tick SNMP Agent Enable System Information Co...

Страница 24: ...ive network communication to and from the controller LINK and ACT are located near the RJ45 connector Routine Maintenance Perform the following routine maintenance on the S321 IP 1 Periodically check the continuity of the grounding circuit 2 Perform operational testing monthly see Testing Procedure on page 21 3 Change the battery every five years Replace with Panasonic part number CR2025 or equiva...

Страница 25: ...invalid card to each reader connected to the S321 IP reader interface and then verify that access is denied red lamp lights Replacement Parts There are no serviceable components inside the S321 IP plastic enclosure Generic replacement terminal blocks can be ordered if lost For more information on the parts listed refer to the applicable catalog page Fuses The S321 IP has no replaceable fuses Condi...

Страница 26: ...S321 IP Network Controller Hardware Installation 24 10239 480 Rev F 22 ...

Страница 27: ...We welcome your comments at BE techpubs security jci com Security Solutions 805 522 5555 www johnsoncontrols com ...

Отзывы: