RJ SERIES INSTALLATION MANUAL

Object Type

Type Enumeration

Instance

Name

Enumeration

Analog Value

2

1

Present_Value

85

WFI##########.Occupied Cool.Present_Value

Occupied Cooling Setpoint Input (Read/Write)
Standby Cooling Setpoint Input (Read/Write)

Analog Value

2

2

Present_Value

85

WFI##########.Unoccupied Cool.Present_Value

Unoccupied Cooling Setpoint Input (Read/Write)

Analog Value

2

3

Present_Value

85

WFI##########.Occupied Heat.Present_Value

Occupied Heating Setpoint Input (Read/Write)
Standby Heating Setpoint Input (Read/Write)

Analog Value

2

4

Present_Value

85

WFI##########.Unoccupied Heat.Present_Value

Unoccupied Heating Setpoint Input (Read/Write)
Minimum Cooling Setpoint Input (Read/Write)
Maximum Heating Setpoint Input (Read/Write)

Analog Input

0

1

Present_Value

85

WFI##########.Space Temp.Present_Value

Space or Zone Temperature Value (Read Only)

Analog Input

0

2

Present_Value

85

WFI##########.Discharge Air Temp.Present_Value

Discharge Air Temp

 Field Supplied Only

 (Read Only)

Analog Input

0

3

Present_Value

85

WFI##########.Effective Clg Setpt.Present_Value

Effective Cooling Setpoint Value (Read Only)

Analog Output

1

4

Present_Value

85

WFI##########.Space temp Ovrd.Present_Value

Space or Zone Temperature Value Override(Write)

Analog Input

0

4

Present_Value

85

WFI##########.Effective Htg Setpt.Present_Value

Effective Heating Setpoint Value (Read Only)

Analog Value

2

9

Present_Value

85

WFI##########.Dehumidify Setpt.Present_Value

Dehumidification Setpoint (Read/Write)

Analog Value

2

10

Present_Value

85

WFI##########.Low Temp Limit Adj.Present_Value

Heating Freeze Protection Temperature Setpoint Value (Read/Write)
Heating Freeze Protection Temperature Setpoint Value (Read/Write)
1st Stage Compressor Heating Output (Read Only)
1st Stage Compressor Cooling Output (Read Only)
Fan Output (Read Only)

Multistate Input

13

2

Present_Value

85

WFI##########.Mode.Present_Value

Unit Mode of Operation (Read Only)
Unit Alarm mode (Read Only)
Heating/Cooling Prop Band Input (Read/Write)

Analog Value

2

6

Present_Value

85

WFI##########.Remote Setpt Span.Present_Value

Warm/Cool Adjust Span (Read/Write)

Analog Value

2

7

Present_Value

85

WFI##########.Remote Setpt Bias.Present_Value

Warm/Cool Adjust Offset Value (Read/Write)

Analog Value

2

8

Present_Value

85

WFI##########.Space Temp Offset.Present_Value

Space or Zone Temperature Sensor Calibration Input (Read/Write)

Analog Output

1

1

Present_Value

85

WFI##########.Space Setpoint.Present_Value

General Setpoint Input (Read/Write)

Analog Input

0

6

Present_Value

85

WFI##########.Water Coil Temp.Present_Value

Heating Freeze Protection Temperature Value (Read Only)

Analog Input

0

7

Present_Value

85

WFI##########.Low Temp Limit.Present_Value

Heating Freeze Protection Temperature Setpoint Value (Read Only)

Analog Input

0

9

Present_Value

85

WFI##########.Alarms Enumerated.Present_Value

Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge 
Pressure alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze protection 
alarm, 8=Faulty Freeze Sensor alarm,
9=Loss of Charge]
 (Read Only)

Analog Input

0

8

Present_Value

85

WFI##########.ECM Cmd Output.Present_Value

ECM PWM Control signal value (Read Only)

Analog Output

1

2

Present_Value

85

WFI##########.ECM Fan Ovrd.Present_Value

ECM PWM Control signal Override (Read/Write)

Analog Input

0

5

Present_Value

85

WFI##########.Space Humidity.Present_Value

Space Humidity value (Read Only)

Analog Output

1

3

Present_Value

85

WFI##########.AO2 Override.Present_Value

Spare PWM Output AO2 Command (Write)

Analog Input

0

10

Present_Value

85

WFI##########.AO2 Value.Present_Value

Spare PWM Output AO2 Value (Read Only)

Analog Value

2

5

Present_Value

85

WFI##########.Temporary Occ Time.Present_Value

Temporary Occupancy Time Period Input (Read/Write)

Multistate Input

13

1

Present_Value

85

WFI##########.Effective Occupancy.Present_Value

Effective Occupancy State (Read Only)

Multistate Output

14

1

Present_Value

85

WFI##########.Occupancy Command.Present_Value

Occupancy Override Command Input (Read/Write)

Multistate Output

14

6

Present_Value

85

WFI##########.Emergency Override.Present_Value

Emergency Override Input (Read/Write)

Binary Input

3

1

Present_Value

85

WFI##########.Fan Cmd Status.Present_Value

Fan Output Status (Read Only)

Binary Input

3

6

Present_Value

85

WFI##########.Accessory 2 Output.Present_Value

Accessory 2 Output Status (Read Only)

Binary Input

3

5

Present_Value

85

WFI##########.Accessory 1 Output.Present_Value

Accessory 1 Output Status (Read Only)

Binary Input

3

8

Present_Value

85

WFI##########.Alarm Status.Present_Value

Alarm Output Status (Read Only)

Multistate Output

14

7

Present_Value

85

WFI##########.Alarm Reset.Present_Value

Alarm Reset Input (Read/Write)

Multistate Output

14

2

Present_Value

85

WFI##########.Fan Command (G).Present_Value

Network equivelant of a thermostatic 'G' call. (Write)

Multistate Output

14

3

Present_Value

85

WFI##########.Compressor Cmd (Y1).Present_Value

Network equivelant of a thermostatic 'Y1' call. (Write)

Multistate Output

14

3

Present_Value

85

WFI##########.Compressor Cmd (Y2).Present_Value

Network equivelant of a thermostatic 'Y2' call. (Write)

Binary Input

3

4

Present_Value

85

WFI##########.Reversing Valve.Present_Value

Reversing Valve Output Status (Read Only)
Occupancy Supervisory Scheduler Command Input (Read/Write)
Compressor/Fan Proving Switch Status (Read Only)

Binary Input

3

7

Present_Value

85

WFI##########.Dirty Filter (BI-12).Present_Value

Dirty Filter Switch Status (Read Only)

Binary Input

3

3

Present_Value

85

WFI##########.Comp Hi Capacity Cmd.Present_Value

Compressor Hi Capacity Command Status (Read Only)

Multistate Output

14

8

Present_Value

85

WFI##########.Emergency Heat BO5.Present_Value

Command for output BO5 used for Emg Heat-Interlocked with Fan DP9Read/Write)

Multistate Output

14

9

Present_Value

85

WFI##########.BO9.Present_Value

Command for output BO9(Read/Write)

Binary Input

3

9

Present_Value

85

WFI##########.BO5 Output.Present_Value

Value output for BO5 used for Emg Heat (Read Only)

Binary Input

3

10

Present_Value

85

WFI##########.BO9 Output.Present_Value

Value output for BO9 (Read Only)

Multistate Output

14

10

Present_Value

85

WFI##########.Dehum Cmd.Present_Value

Dehumidification command-like a Humidistat (Read/Write)

Point Description

Object Identifier

Property

BACnet

Full Reference

Some Cool Heading - BACNet

Optional Controls - FX10 cont.

Содержание RJ H Series

Страница 1: ...V Models stallation Information ater Piping Connections ot Water Generator Connections ectrical artup Procedures oubleshooting eventive Maintenance RJ Series Installation Manual RJ Series Geothermal W...

Страница 2: ......

Страница 3: ...nerator Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance 146 00 NOM2 03 10 RJ Series Installation Manual RJ Series Geothermal Water Source Heat Pump R 410A Refrigerant...

Страница 4: ......

Страница 5: ...g 14 Open Loop Ground Water Systems 15 Electrical Connections 16 17 Electronic Thermostat Installation 17 Auxiliary Heat Ratings 17 Electrical Data 18 19 Setting Fan Speed 20 Fan Performance Table 20...

Страница 6: ...022 030 036 042 048 Only NOTES 1 Not available with Hot Water Generator HWG 2 Not available with Hot Gas Reheat 3 Not available on dual capacity models 4 Not available in model sizes 009 018 5 Field...

Страница 7: ...or to setting the unit in place remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket Vertical units are available in left or right air retu...

Страница 8: ...k Width Supply Width Supply Depth Return Depth Return Height 009 012 in 22 2 22 5 34 5 5 3 11 9 14 9 8 6 1 2 1 2 3 8 9 7 11 7 2 2 2 2 10 0 10 0 6 1 8 8 11 8 2 4 18 1 14 2 1 7 cm 56 4 57 2 87 6 5 9 13...

Страница 9: ...8 5 1 0 0 8 8 4 6 m c 23 1 12 2 34 0 34 5 3 8 4 1 71 4 86 4 14 2 Condensate is 3 4 in PVC female glue socket and is switchable from side to front Rev 03 11 10 Vertical bottomflow unit shipped with de...

Страница 10: ...26 0 2 0 cm 56 6 67 3 122 9 5 8 18 5 34 0 41 7 26 4 19 05 mm 12 7 mm 13 0 27 4 32 5 5 5 24 1 26 4 21 6 16 5 5 3 55 9 66 0 5 1 036 072 in 25 5 31 2 58 4 2 3 7 3 15 9 18 9 11 6 1 1 2 5 6 11 4 13 4 2 2...

Страница 11: ...012 in 22 5 44 0 17 3 2 3 5 3 11 9 14 9 0 8 1 2 in N A 3 8 9 7 11 7 5 9 7 4 7 3 9 7 5 8 7 3 17 9 14 6 0 5 0 4 44 8 25 1 21 0 21 4 cm 57 2 111 8 43 9 5 8 13 5 30 2 37 8 2 1 12 7mm 9 7 24 6 29 7 15 0 18...

Страница 12: ...ld damage internal parts Some applications require the installation of horizontal units on an attic floor In this case the unit should be set in a full size secondary drain pan on top of a vibration a...

Страница 13: ...the unit blower the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet On systems employing a sheet metal duct system can...

Страница 14: ...rotten egg smell appears at 0 5 PPM 10 50 ppm Less than 1 ppm Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm Chlorine Less than 5 ppm Less than 5 ppm Less than 5 ppm Chlorides Less th...

Страница 15: ...e On vertical units the internal condensate drain assembly consists of a drain tube which is connected to the drain pan a 3 4 inch PVC fe male adapter and a flexible connecting hose The female adapter...

Страница 16: ...ct the system from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchanger may...

Страница 17: ...rtments to assure compliance in your area Note For open loop groundwater systems or systems that do not contain an antifreeze solution set SW2 Switch 2 to the WELL position Refer to the Dip Switch Fie...

Страница 18: ...s water solenoid valves on open loop installations electronic air cleaners humidifiers etc This relay contact should be used only with 24 volt signals and not line voltage power The relay has both nor...

Страница 19: ...FF position for the control to operate with FaultFlash or ComforTalk thermostats SW2 8 in the ON position configures the control to operate with typical thermostats continuous lockout signal There mus...

Страница 20: ...0 n a 6 9 12 7 14 1 15 048 208 230 60 1 197 253 31 0 19 8 109 0 38 0 4 0 23 8 28 8 45 208 230 60 3 187 253 21 2 13 6 83 1 n a 4 0 17 6 21 0 30 460 60 3 414 506 9 5 6 1 41 0 n a 4 1 10 2 11 7 15 048 20...

Страница 21: ...4 5 6 6 7 10 036 208 230 60 1 197 253 22 0 14 1 73 0 26 0 3 5 17 6 21 1 35 265 60 1 NOT AVAILABLE 208 230 60 3 187 253 13 9 8 896 58 0 n a 3 5 12 396 14 6 20 460 60 3 414 506 6 5 4 2 28 0 n a 1 8 6 0...

Страница 22: ...038 800 1000 1100 1300 1500 1600 1800 w 1hp L M H 650 800 900 1050 1150 1250 1350 1450 1550 L M H 049 800 900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400 w 1hp L M H 800 950 1100 1300 1500 1750...

Страница 23: ...175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260 L 2075 2050 2020 1995 1965 1940 1915 1885 1850 1820 1785 1720 1610 1505 1335 1175 RJS070 H 11 x 10 1 2430 2400 2365 2330 2290 2255 2215...

Страница 24: ...ssor Hi RV FAN Loop Pump 1 Loop Pump 2 Outputs 6 Off 7 Off Blower Lo Blower Med Blower Hi Aux Heat 1 Aux Heat 2 AuxHeat 3 Aux Heat 4 Outputs2 Diagnostic Modes Green LED not flashing T1 T3 T2 1 3 2 Red...

Страница 25: ...low Switch High pressure Switch Low pressure Switch Hot Water On Off Polarized connector Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optio...

Страница 26: ...Black F3 Black F4 Black F5 Black F6 Black F7 Black F8 Black F9 Black F10 Black F11 Black F12 Black F13 Black F14 Black F15 Black F16 Black F17 Black F18 Black F19 Black F20 Black R Black C Black L Bla...

Страница 27: ...Yellow 18 Red 33 Black 34 Black 54 Blue 55 Red 56 CC Orange 7 1 2 3 4 5 7 8 9 10 6 11 12 13 16 15 14 17 20 19 18 Yellow J2 Black F1 Blue 10 Black F2 Black F3 Black F4 Black F5 Black F6 Black F7 Black...

Страница 28: ...ockout FP thermistor loop 15 F well 30 F Lockout High Pressure Low Pressure Comfort Alert ECM2 RPM 100 rpm Lockout Microprocessor malfunction HWL thermistor 130 F DHW pump switch off Drain Water Flow...

Страница 29: ...sition when using the 17P501 A01 electric heat board and should be ON when using the 17P514 A01 electric heat board 9 SW2 8 must be in the OFF position for pulsed L lockout signal and in the ON positi...

Страница 30: ...op Pump2 Outputs 6 Off 7 Off Blower Lo Blower Med Blower Hi Aux Heat 1 Aux Heat 2 AuxHeat 3 Aux Heat 4 Outputs2 Diagnostic Modes Status LED not flashing RCP CS Blue Blue NOTE 3 NOTE6 Not Used Notes 2...

Страница 31: ...ch High pressure Switch Low pressure Switch Hot Water On Off Polarized connector Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional bloc...

Страница 32: ...for a high pressure switch for safety a low pressure switch to prevent loss of charge damage and a low suction temperature thermistor for freeze sensing Upon a continuous 30 second measurement of the...

Страница 33: ...ECM Motor ECM2 Airflow Selection DIP Switches SW1 A 12 position DIP switch package on the control allows the airflow levels to be set for low medium and high speed Refer to the ECM Blower tables Only...

Страница 34: ...TCHES SW3 DIP SWITCH NUMBER DESCRIPTION OFF POSITION ON POSITION SW 2 1 Service Test Mode On the control allows field selection of NORMAL or TEST operational modes Test mode accelerates most timing fu...

Страница 35: ...On On On Aux Heater Off Off Staged Staged Off Off Secondary 1 Out On On On Off On On Emerg LED Off Off Off On Off Off Off T Stat Signal Y1 Y1 Y2 Y1 Y2 W W Y1 O Y1 Y2 O G DUAL CAPACITY UNITS Compressor...

Страница 36: ...d superheat and subcooling numbers calculated If superheat and subcooling are outside recommended ranges an adjustment to the refrigerant charge may be necessary Note Refrigerant tests must be made wi...

Страница 37: ...ed Low Water Coil Temperature Limit Field selectable for 15 or 30 F 9 or 1 C Installation Options Standalone controlled by standard room thermostat Standalone with a Zone Temperature Sensor must have...

Страница 38: ...protocol boards that can be added to the FX10 are Johnson Control N2 BACnet LonWorks Control and Safety Feature Details Emergency Shutdown The emergency shutdown mode can be activated by a command fr...

Страница 39: ...pressor Fixed On Delay Time The Compressor Fixed On Delay Time will ensure that the compressor output B02 is not enabled for 90 seconds after the control receives a call to start the compressor This d...

Страница 40: ...l be speed 10 and the minimum high speed setting will be speed 3 In addition there is a low limit setting in the software to prevent the ECM2 fan speed from being set below acceptable limits for each...

Страница 41: ...eries Water to Air Welcome Info Status Temps Outputs Settings Maint Alarms Alm History PROFXENV XX 3 8 07 Info Run Mode Auto Eff Occup y Occ Y1 Input OFF Y2 Input OFF G Input OFF O Input OFF Occ Input...

Страница 42: ...Bad Sensor 0 Alm History NOTE This FX10 application implements an alarm history which is reset only by cycling power This history shows on the Alm History page Any alarm showing 4 events has occurred...

Страница 43: ...tion Temperature Value Read Only ADF 40 nvoHtgFrzSetpt Heating Freeze Protection Temperature Setpoint Value Read Only ADF 41 nvoAlarms Alarms Enumerated 0 no alarms 1 condensate alarm 2 Compressor Hi...

Страница 44: ...ow Suction Pressure alarm 4 Freeze protection alarm 8 Faulty Freeze Sensor alarm 9 Loss of Charge Read Only nvoPWMOut SNVT_volt 44 ECM PWM Control signal value Read Only nvoECMOvrd SNVT_volt 44 ECM PW...

Страница 45: ...f Charge Read Only Analog Input 0 8 Present_Value 85 WFI ECM Cmd Output Present_Value ECM PWM Control signal value Read Only Analog Output 1 2 Present_Value 85 WFI ECM Fan Ovrd Present_Value ECM PWM C...

Страница 46: ...controller volatile these will supersede any temperature sensor connected to the space temperature Analog Input Analog Value Type 2 2 1 Occupied Cool Write Cooling setpoint in Occupied mode 2 2 Unocc...

Страница 47: ...ressor Cmd Y1 Write allows a network command equivalent of a thermostatic Y1 call 14 4 Compressor Cmd Y2 Write allows a network command equivalent of a thermostatic Y2 call 14 5 Reversing Vlv Cmd O Wr...

Страница 48: ...water control valve or loop pump s are activated 5 Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P T plugs and comparing to unit capac...

Страница 49: ...rheat 009 040 Subcooling 048 Subcooling 060 070 Subcooling Water Temp Drop F Air Temp Rise F DB 1 5 73 79 279 304 7 13 2 6 11 15 4 8 7 10 18 24 3 0 79 85 285 310 8 14 2 6 11 15 4 8 3 6 20 26 1 5 103 1...

Страница 50: ...p F Water Flow GPM Ton Heating No Hot Water Generator 30 50 70 Note Cooling performance based on entering air temperatures of 80 F DB 67 F WB Heating performance based on entering air temperature of 7...

Страница 51: ...30 70 1 1 Max Entering Water 120 48 9 90 32 2 Notes Cooling Heating Minimum maximum limits are only for start up conditions and are meant for bringing the space up to occupancy temperature Units are n...

Страница 52: ...or water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE COAX LOAD HEATING CYCLE ANALYSIS EX...

Страница 53: ...2 8 2 6 2 4 2 2 15 4 4 4 0 3 8 3 5 3 3 18 6 0 5 5 5 1 4 8 4 4 24 9 7 9 1 8 5 7 9 7 3 5 25 07 Model GPM Pressure Drop psi 30 F 50 F 70 F 90 F 110 F 026 full load 4 1 4 1 3 1 2 1 1 1 0 6 2 8 2 6 2 4 2 3...

Страница 54: ...erated without a filter Condensate Drain In areas where airborne bacteria produce a slime in the drain pan it may be necessary to treat chemically to minimize the problem The condensate drain can pick...

Страница 55: ...53 RJ SERIES INSTALLATION MANUAL Notes...

Страница 56: ...2010 Johnson Controls Inc P O Box 423 Milwaukee WI 53203 www johnsoncontrols com Printed in USA 146 00 NOM2 310 New Release...

Отзывы: