RJ SERIES INSTALLATION MANUAL
Setting Fan Speed
ECM2 fan motors have a 12-speed selector dip switch on the logic board (SW1) and are factory set for optimum performance. To change
speeds, select the appropriate speeds on dip switch SW1. Consult the ECM2 fan performance table below for specific airflow and switch
information.
CAUTION: Disconnect all power before performing this operation.
1
2
3
4
5
6
7
8
9
10
11
12
SW1
On
Off
A 12-position DIP switch package on the control allows the airflow levels to be set for low, medium, and high speed when
using the ECM2 blower motor. Only three of the DIP switches can be in the “on” position.
The first “on” switch (the lowest position number) determines the low speed fan setting.
•
The second “on” switch determines the medium speed fan setting.
•
The third “on” switch determines the high speed fan setting.
•
The example to the right shows SW1 on the control board configured for the following 042 airflow settings.
Low Speed Fan: 900 CFM
Medium Speed Fan: 1150 CFM
High Speed Fan: 1450 CFM
Fan Performance Data
Single Speed
Dual Capacity
MAX
AIR FLOW DIP SWITCH SETTINGS
ESP
1
2
3
4
5
6
7
8
9
10
11
12
400
500
600
700
800
900
1000
1100
1200
L
M
H
650
750
850
1000
1100
1200
1300
1400
1500
L
M
H
038
800
1000
1100
1300
1500
1600
1800
w/1hp*
L
M
H
650
800
900
1050
1150
1250
1350
1450
1550
L
M
H
049
800
900
1000
1200
1400
1600
1700
1850
2000
2200
2300
2400
w/1hp*
L
M
H
800
950
1100
1300
1500
1750
1950
2100
2300
L
M
H
800
950
1100
1300
1500
1750
1950
2100
2300
L
M
H
5/30/06
Factory settings are at recommended L-M-H DIP switch locations
CFM is controlled within ±5% up to the maximum ESP
M-H settings MUST be located within boldface CFM range
Max ESP includes allowance for wet coil and standard filter
Lowest and Highest DIP switch settings are assumed to be L and H respectively
026
0.50
MODEL
049
0.50
0.75
038
0.50
0.75
072
0.75
064
0.75
MAX
AIR FLOW DIP SWITCH SETTINGS
ESP
1
2
3
4
5
6
7
8
9
10
11
12
300
400
500
600
700
L
M
H
300
400
500
600
700
800
L
M
H
400
500
600
700
800
900
1000
1100
1200
L
M
H
400
500
600
700
800
900
1000
1100
1200
L
M
H
650
750
850
1000
1100
1200
1300
1400
1500
L
M
H
036
800
1000
1100
1300
1500
1600
1800
w/1hp*
L
M
H
650
800
900
1050
1150
1250
1350
1450
1550
L
M
H
042
800
900
1000
1200
1400
1600
1700
1850
2000
2200
2300
2400
w/1hp*
L
M
H
650
800
900
1050
1150
1250
1350
1450
1550
L
M
H
048
800
900
1000
1200
1400
1600
1700
1850
2000
2200
2300
2400
w/1hp*
L
M
H
800
950
1100
1300
1500
1750
1950
2100
2300
L
M
H
800
950
1100
1300
1500
1750
1950
2100
2300
L
M
H
5/25/07
060
0.75
070
0.75
0.75
048
0.50
0.75
036
0.50
0.75
042
0.50
MODEL
022
0.50
030
0.50
018
0.50
015
0.50
ECM Motor