VFD68 Variable Frequency Drives (575 VAC) 

12

Prevent VFD-generated EMI from causing functional problems.

-

Do not run the low-voltage signal cables and the high-voltage power cables in parallel with each other, 
and do not bundle them together.

-

Run low-voltage signal cables as far away as possible from high-voltage power cables.

-

Use shielded cables for the low-voltage signal cables. Connect the sensor cable shield at only one 
point and that one point is the same terminal as the sensor's common wire.

-

Install a ferrite core on the signal cable (for example, ZCAT3035-1330 TDK).

Terminal Screw Torque Specifications

Tighten the terminal screw to the specified torque. Over-tightening the terminal screws may damage the 
terminal blocks and screw threads. Loose terminal screw connections can result in a short circuit or 
malfunction.  

 

Branch Circuit Protection

Integral solid-state short circuit protection does not provide branch circuit protection. The installer must provide 
branch circuit protection in accordance with the National Electrical Code for the U.S. or the Canadian Electrical 
Code for Canada and any additional codes. 

As specified, UL Class T fuses or any faster acting fuse with the appropriate rating or Listed UL 489 Molded 
Case Circuit Breaker (MCCB) must be employed in accordance with Table 7.  

Short Circuit Ratings

The VFD68 Drives meet the requirements for their respective rating categories (Table 8).

Table 6: Torque Specifications for VFD68Dxx Drives

Rated Capacity, kW (HP)

Terminal Screw Size

1

1.

The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/-, P1 and a screw for 
earthing (grounding). 

Tightening Torque, N•m (lb•in.)

0.75

7.5 (1

10)

M4

1 (8.85)

Table 7: VFD68Dxx Drives Electrical Ratings

VFD68 575 VAC

kW (HP)

0.75 (1)

1.5 (2)

2.2 (3)

3.7 (5)

5.5 (7.5)

7.5 (10)

Rated fuse voltage (V)

575 V or more

Fuse Maximum allowable rating (A) 
(without power factor improving reactor)

1

1.

Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.

6 A

10 A

15 A

20 A

30 A

40 A

Molded case circuit breaker (MCCB) 
Maximum allowable rating (A)

1

5 A

10 A

15 A

20 A

30 A

30 A

Table 8: VFD68 Drives Short Circuit Ratings

Rating Category

Suitable for use in a circuit capable of delivering not more than

VFD68Dxx Drives (575 VAC Class)

100 kA rms symmetrical amperes, 600 V maximum

Содержание PENN VFD68

Страница 1: ...5 Dimensions 7 Mounting 8 Wiring 10 Precautions 11 Terminal Screw Torque Specifications 12 Branch Circuit Protection 12 Short Circuit Ratings 12 High Voltage Wire Size and Maximum Wire Length 13 Selec...

Страница 2: ...Adjusting the Default Parameters 26 Enter the Parameter Adjustment Mode 26 Select and Change Most Parameters 26 Select and Change P 90x Parameters 26 Exit the Parameter Adjustment Mode 27 Manual Moto...

Страница 3: ...equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls inte...

Страница 4: ...Voltage kW Horsepower Dimensions H x W x D mm in D 575 VAC 50 60 Hz F 0 75 1 G 1 5 2 H 2 2 3 J 3 7 5 K 5 5 7 1 2 L 7 5 10 M 150 x 140 x 136 5 15 16 x 5 1 2 x 5 5 16 N 150 x 220 x 148 5 15 16 x 8 11 16...

Страница 5: ...uency or electromagnetic emissions may cause interference IMPORTANT When selecting the motor do not exceed the maximum output current rating of the VFD68 Drive IMPORTANT Do not control both single pha...

Страница 6: ...an enclosure Ambient air temperature is a temperature outside an enclosure The VFD68 is designed to operate above 50 C by following the maximum output current derating limits show in Table 3 and Figur...

Страница 7: ...Drives mm in VFD Model H H1 W W1 D VFD68DFM 150 5 15 16 138 5 7 16 140 5 1 2 128 5 1 16 136 5 3 8 VFD68DGM VFD68DHM VFD68DJN 220 8 11 16 208 8 3 16 148 5 13 16 VFD68DKN VFD68DLN Figure 2 VFD68Dxx Maxi...

Страница 8: ...ove the high voltage wiring cover at the bottom of the VFD68 Drive by pulling in the direction of Arrow A Figure 5 Mount the VFD vertically in an acceptable NEMA rated enclosure on a non flammable sur...

Страница 9: ...W 5 HP or Less 5 5 to 7 5 kW 7 1 2 to 10 HP A 100 mm 4 in or more 100 mm 4 in or more B 10 mm 7 16 in or more 50 mm 2 in or more C Figure 6 Required Clearance for Mounting Inside an Enclosure 5 5 to 7...

Страница 10: ...ause electric shock personal injury or death AVERTISSEMENT Risque de d charge lectrique Afin d viter tout risque de d charge lectrique attendre au moins 10 minutes apr s la d connexion de l alimentati...

Страница 11: ...t inadequacy an earth ground fault due to wiring inadequacy or reduced motor insulation resistance Check the ground to earth insulation and phase to phase insulation of the VFD output side before appl...

Страница 12: ...Canadian Electrical Code for Canada and any additional codes As specified UL Class T fuses or any faster acting fuse with the appropriate rating or Listed UL 489 Molded Case Circuit Breaker MCCB must...

Страница 13: ...dance with local national and regional regulations Table 9 Maximum Output Amperes and Wiring Sizes for VFD68Dxx Drives Part Number Rated Capacity kW HP Maximum Output Current Amperes Cable Wire Size A...

Страница 14: ...indicates that the VFD68DGM Drive has a voltage rating of 575 VAC and a maximum output rating of 7 amperes c Table 9 on page 13 gives the recommended wire size as 14 AWG d Table 10 on page 14 shows 1...

Страница 15: ...e 8 2 Remove the high voltage wiring cover at the bottom of the VFD68 Drive by pulling in the direction of Arrow A Figure 9 3 Connect a 575 VAC three phase power supply to high voltage terminals R L1...

Страница 16: ...and wiring the high voltage drive output U V W to the motor 5 Connect earth ground wiring to the earth ground terminals on the VFD68 Drive and on the motor 6 Replace the high voltage wiring cover Not...

Страница 17: ...generative brake circuits SD Common Common for contact inputs using Sink logic default setting and 24 VDC supply AM Analog Output 0 10 VDC analog output corresponding to output frequency PC 24V 24 VDC...

Страница 18: ...a forward direction STR Contact Input Reverse rotation not used SD Common Common for contact inputs when using Sink logic default setting 1 Gray cells indicate a terminal that is typically not used i...

Страница 19: ...107 Ratiometric Transducer Figure 12 For high pressure refrigerants other than R410a you must calculate and change the P 90x parameters For medium and low pressure refrigerants you must determine the...

Страница 20: ...and motor operation using controlled input signal values EXT Mode In the External EXT mode the drive and motor respond to a signal or signals from one or two external analog input signal devices such...

Страница 21: ...setting consecutively when in the setting mode Press the key to change the parameter setting Used to give a forward rotation command Used to give a reverse rotation command Used to stop operation Used...

Страница 22: ...d Current Set parameter to the rated FLA on motor rating plate 0 500 A Rated VFD68 Output P 19 VFD Output Voltage Defines the maximum output voltage relative to the drive supply voltage 2 9999 the max...

Страница 23: ...peed defined as frequency 0 60 Hz 12 5 Hz P 902b screen b Analog Input 1 of input voltage to start minimum speed ramp 0 100 38 1 90 V P 903 screen a Analog Input 1 Maximum speed defined as frequency 1...

Страница 24: ...otor Speed Frequency Hz is an expression of motor speed RPM on the VFD Figure 14 and Figure 15 show how the drive operating frequency is related to the speed RPM of the motor Figure 14 Frequency and M...

Страница 25: ...tor Noise and EMI Using the default setting P 72 1 frequency 1 kHz electromagnetic interference EMI radiation and leakage current from the wiring between the VFD68 Drive and the motor is low however t...

Страница 26: ...additional parameters press or Select and Change P 90x Parameters 12 To change parameter 902 screen a or 902 screen b press until Pr PU appears on the display 13 Press P 000 appears The underline ind...

Страница 27: ...on the display then press until PU PU appears on the display 2 Press or to start the VFD68 output to the motor The RUN icon appears on the display 3 Press until the motor runs at maximum speed 50 or...

Страница 28: ...message regarding operational or setting errors displays The VFD continues operating Warning The VFD continues operating Failure to take appropriate measures will lead to a fault Alarm The VFD continu...

Страница 29: ...thermal O L relay function E FIN Heatsink overheat E ILF Input phase loss not used E OLT Stall prevention stop E BE Brake transistor alarm detection E GF Output side earth ground fault over current a...

Страница 30: ...ve monitor displays PS PU Stop Warning and then performs a controlled shutdown of the motor WARNING Risk of Personal Injury Before you reset the VFD68 Drive verify that all persons are clear of the co...

Страница 31: ...e SD and STF terminals on the low voltage terminal blocks 2 Verify that the SINK SOURCE jumper to the left of the low voltage terminal blocks Figure 11 is set to SINK 3 Press until PU PU appears on th...

Страница 32: ...y Input Devices Johnson Controls PENN P499 Electronic Pressure Transducers PWM Carrier Frequency Adjustable 0 7 to 15 kHz Motor Requirements Three phase NEMA Design B motors required Inverter rated mo...

Отзывы: