Normally Open
(N.O.)
Normally Opened (N.O.) relay contacts are open when the relay is
not
energized/activated and closed when the relay is energized. On System
450 Relay Outputs, the LC
y
and LNO
y
terminals connect to the Normally
Opened contacts. See
on page 18 for more information.
OEP
x
In the Percent Output Signal Strength at End Point Selection (OEP
x
)
screen in the Analog Output Setup screens, select the value (0 to 100%) of
the total signal strength, to be generated by analog output
x
when the
controlled condition is at the selected End Point (EP) value. See
Reverse Control Actions for Analog Outputs
on page 50 for more information.
OFFS
x
In the Temperature Offset Selection (OFFS
x
) screen in the Sensor Setup
screens, select the value (in degrees) that you want the measured (and
displayed) temperature value to differ from the actual sensed temperature
value. System 450 allows you to select a offset for each temperature sensor
in your System 450 control system. You cannot select an offset for
pressure or humidity sensors. The
x
value is the ID number for the
temperature sensor you are setting up (Sn-1, Sn-2, or Sn-3). See
on page 45 for more information.
OFFT
x
In the Minimum Off-Time Selection (OFFT
x
) screen in the Relay Setup
screens, select the number of seconds (0 to 300) that output relay
x
remains Off after being driven Off by control loop conditions. The
minimum off-time feature is typically used to prevent short-cycling of
controlled equipment. See
information.
ONT
x
In the Minimum On-Time Selection (ONT
x
) screen in the Relay Setup
screens, select the number of seconds (0 and 300 seconds) that relay
output
x
remains On after being driven On by control loop conditions. The
minimum on-time feature is typically used to prevent short-cycling of
controlled equipment. See
information.
OSP
x
In the Percent Output Signal Strength at Setpoint Selection (OSP
x
) screen
in the Analog Output Setup screens, select the value (0 to 100%) of the
total signal strength, to be generated by analog output when the controlled
condition is at the selected Setpoint (SP) value. The
x
value is the ID
number for the output you are setting up. See
on page 50 for more information.
Term
Definition
79