—MR4 Refrigeration Temperature/Defrost Control Installation Bulletin 

A

larm and Fault Codes 

Table 4: Error Codes and Status 

Error Code (Codes will flash on the display.) 

System Status 

F1

 

Open or shorted temperature sensor

 

Alarm output On. Compressor runs according to 

SF

. Cycle power 

to reset. 

F2

 

Open or shorted evaporator sensor

 

Alarm output On. Defrost cycle controlled by 

di

 

and 

dd

. Correct 

problem to reset. 

A1

 

Binary input open for longer than 

id

 and 

iF

 = 1

 

Compressor output Off. Alarm output On. Correct problem to 
reset. 

A2

 

Binary input open for longer than 

id

 and 

iF

 = 2

 

Alarm output On. Correct problem to reset. 

A3

 

Binary input open for longer than 

id

 and 

iF

 = 3

 

Fan output Off. Alarm output On. 

AH

 and 

AL

 disabled. Correct 

problem to reset. 

HI

 

Temperature has reached or exceeded  
(se 

AH

)

 

Alarm output On. Correct problem to reset. 

LO

 

Temperature has reached or  fallen below 
 (setpoint 

– 

AL

)

 

Alarm output On. Correct problem to reset. 

EE

 

Program failure

 

Alarm output On. Other outputs Off. Replace control. 

O

rdering Information 

Table 5: Specifications 

Power Requirements 

3.7 VA @ 24 VAC 50/60 Hz, Class 2 (20-30 VAC) 

Ambient Conditions 

Operating 

14 to 140

o

F (-10 to 60

o

C); 0 to 95% RH (non-condensing) 

Storage   

-22 to 176

o

F (-30 to 80

o

C); 0 to 95% RH (non-condensing) 

Accuracy 

+1.8 F

 (+ 1C

Agency Listings 

UL Recognized: File E194024, CCN XAPX2 
Canadian UL Recognized: File E194024, CCN XAPX8 
FCC Compliant per Class A Digital Device, Part 15 
Canadian DOC Compliant per Class A, Radio Interference Regulations 

Table 6: Ordering Information 

Product Code Number 

Description 

MR4PM24-12C 

MR4 Panel Mount Control; 2 A99BB-200C sensors included 

MR4DR24-12C 

MR4 DIN Rail Mount Control; 2 A99BB-200C sensors included 

A99BB-200C 

Replacement Sensor, lead length: 6-1/2 ft (2 m) 

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult Johnson Controls/Penn Refrigeration Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be 