Technical Bulletin  A19K, A28K 

 

 

Issue Date  0119 

©  2019 Johnson Controls 

1

 

  Code No.  LIT-121078 

  Part No. 996-241, Rev. A 

A19K, A28K Series 

Industrial Controls 

 

Application 

These controls are for 

refrigeration, air conditioning 

and heating applications.  

Control ranges are available to 

cover working temperatures 

from -30 to 550

°

F (-35 to 

288

°

C).  Controls have NEMA 

3R rainproof enclosure for a 

broad range of industrial and 

general purpose applications. 
The A19 single-stage controls 

are available with open low, 

open high or SPDT contact 

action.  The A28 two-stage 

controls have SPDT contact 

action on both switches. 

All Series A19K and A28K 

controls are designed for use 

only 

as operating controls.  

Where an operating control 

failure would result in 

personal injury and/or loss of 

property, it is the 

responsibility of the installer 

to add devices (safety, limit 

controls) or systems (alarm, 

supervisory systems) that 

protect against, or warn of, 

control failure. 

Operation 

When the temperature increases 

to the control dial setting on the 

single-pole, double-throw model, 

the circuit between “R” and “Y” 

closes.  Simultaneously the 

circuit between “R” and “B” 

opens. 
Figure 3 illustrates the two-stage 

operation of the A28KA and 

A28KJ.  On a temperature 

increase to the dial setting, the 

circuit between “R” and “Y” of 

the low stage switch (RY

L

closes.  Simultaneously the 

circuit between “R” and “B” (RB

L

opens.  On a further increase in 

temperature the high stage 

switch operates and closes RY

H

 

while simultaneously opening 

RB

H

.  The reverse sequencing 

takes place on a temperature 

fall. 

Installation 

Mounting 

Mount the control with the 

conduit connector pointing 

down.  Mount to any flat surface 

with screws or bolts through the 

rubber bushing in the three 

mounting feet.  (See Fig. 1.) 

!

 CAUTION: Do not dent or 

deform the sensitive bulb 

(element) of this control.  A 

dent or deformation will 

change the calibration and 

cause the control to cycle 

at a temperature lower 

than the dial setting.  

When installing the bulb in a 

closed tank, turn off liquid 

supply, relieve pressure and 

lower liquid level below the 

opening before installing or 

removing the bulb or bulb well. 
For closed tank applications 

without well assembly Part  

No. FTG13A-600R packing nut 

assembly may be supplied.  This 

packing nut is for applications 

where the temperature does not 

fall below -35

°

F (-37

°

C) or 

250

°

F (121

°

C).  

Maximum liquid pressure limit is 

150 PSIG (1034 kPa).  See Fig. 

4 for sequence of installation.  

Put parts over support tube 

section of element, placing bulb 

into tank.  Tighten 1/2 in. NPT 

adapter.  Screw packing nut into 

adapter with the retaining 

washers and packing in place as 

shown. 

To install models supplied with 

bulb well, first install bulb well 

into tank.  Remove bushing from 

bulb well and slide bushing over 

capillary.  Push bulb into position 

in bottom of well.  Replace 

bushing into bulb well. 
Tighten set screw in end of 

adapter to hold bulb in position.  

See Fig. 5 for bulb well 

illustration. 

Wiring 

!

 

WARNING:

 

Disconnect 

power supply before 

wiring connections are 

made to avoid electrical 

shock or possible 

damage to equipment.

  

 

Fig. 1 -- Industrial control with 

remote bulb.

 

 