Figure 4: SA bus terminal block wiring
Modular port
The modular (TSTAT) port on the face of the PCV (Figure 2) is an RJ-45, 8-position modular jack used
to easily connect one TE-730 series analog (non-communicating) sensor to the PCV. The modular
TSTAT port provides 15 VDC, SA Bus communications, and analog signals for zone temperature,
zone setpoint, and temporary zone occupancy override.
Note:
On the TE-730 Series sensors, you can activate the occupancy override functionality by
using a pushbutton to momentarily short the zone temperature AI.
The TSTAT pin assignment is shown in Figure 5.
Note:
Do not use the modular SA Bus port and the terminal block SA Bus simultaneously. Only
use one of these connections at a time.
Figure 5: Pin number assignments for the
modular port on PCV1617 and PCV1632 Controllers
Supply power terminal block
The 24 VAC supply power terminal block is a gray, removable, 2-terminal plug that fits into a board-
mounted jack on the upper left of the PCV controller.
PCV1617 and PCV1632 VAV Box Controllers Installation instructions