background image

Figure  8: 24 VAC supply power wiring

Note: 

Power supply wire colors may be different on transformers not manufactured by

Johnson Controls. Follow the transformer manufacturer’s instructions and the project

installation drawings.

6.  Connect the 24 VAC supply power wires from the transformer to the converter. No additional

external power adapter is required. Connect the hot and common wires as desired. The NAE

does not require an earth ground connection.

Note: 

The 24 VAC power should be connected to all network devices so transformer

phasing is uniform across the devices. Powering network devices with uniform 24 VAC

supply power phasing reduces noise, interference, and ground loop problems.

Wiring the NAE for M-Bus protocol

1.  Connect the Ethernet cable to the RJ-45, 8-pin Ethernet port shown in Figure 1.
2.  Connect from the RS232C A or RS232C B serial port on the NAE to the RS-232 connector of the

level converter. Wire to terminals 

GND

RxD

, and 

TxD

 as shown in Figure 9.

3.  Wire from the 

M-

 and 

M+

 terminals on the level converter (Figure 9) to the meters using a free

(star, tree, or line) topology. Specific cabling can vary depending on the topology and site. See

Wiring rules and guidelines for network integrations

.

Note: 

If the number of M-Bus unit loads or distances exceeds the specifications of a level

converter, an M-Bus repeater can be wired to the converter to increase the number of unit

loads and distances. The converter shown in Figure 9 is capable of handling up to 6 units

loads, while other models can handle up to 100. See 

Ordering information

 for a list of M-

Bus devices.

4.  Connect the 24 VAC supply power wires from the transformer to the removable power terminal

block plug on the NAE (Figure 8).

Note: 

Power supply wire colors may be different on transformers not manufactured by

Johnson Controls. Follow the transformer manufacturer’s instructions and the project

installation drawings.

5.  Connect the 24 VAC supply power wires from the transformer to the 

-/~

 and 

+/~

 terminals as

shown in Figure 9.

11

NAE35/NAE45 Installation Guide

Содержание NAE35

Страница 1: ...ating system If you receive from the factory a network engine with Release 9 0 that has an internal modem you can field upgrade the engine to Release 9 0 7 to acquire new release enhancements but its modem and pager functionality is lost If you need modem and pager functionality do not upgrade the NAE35 or NAE45 engine to Release 9 0 7 In addition support for the LonWorks network is no longer avai...

Страница 2: ...ounting space around engine Table 1 NAE45 physical features Callout Description 1 Mounting clip 2 Data protection battery compartment 3 24 VAC power terminal 4 6 pin modular field controller service port 5 FC Bus N2 Bus or FC Bus terminal 6 End of line switch 7 Mounting clip 8 USB port 9 RJ 45 8 pin Ethernet port 10 Mounting clip 11 RS 232 serial port 12 Modem terminal functional at Release 9 0 no...

Страница 3: ...prone to vibration or in areas where electromagnetic emissions can interfere with network engine communication Do not obstruct the network engine housing ventilation holes Do not mount power transformers below the network engine On applications where the network engine is mounted inside a panel or enclosure follow these additional guidelines Do not install the network engine in airtight enclosures...

Страница 4: ...tening the screws may damage the mounting clips or the network engine housing DIN rail mount applications To mount the network engine on a DIN rail 1 Securely mount a 20 cm 8 in or longer section of DIN rail horizontally and centered in the space 2 Ensure that the bottom two mounting clips are pulled outward and snapped firmly into the extended position Figure 3 Figure 3 DIN Rail and Mounting Clip...

Страница 5: ...C Bus connection on an NAE35 and NAE45 is a 4 pin removable keyed terminal block labeled FC BUS The FC bus connection is an optically isolated RS 485 port with a keyed 4 position terminal block that communicates at 9 6k 19 2k 38 4k or 76 8k baud Use an FC Bus port to integrate an N2 network BACnet MS TP FC Bus trunk or third party network into the Metasys system Note N2 BACnet MS TP Modbus RTU and...

Страница 6: ...m to the RS232C B port Refer to the NAE Commissioning Guide LIT 1201519 for information on external modems For a network engine at Release 9 0 7 the two RS232C serial ports do not support external modems Also the RS232C A port is inactive USB port For a network engine at Release 9 0 you can connect an external modem to the USB port labeled USB Refer to the NAE Commissioning Guide LIT 1201519 for m...

Страница 7: ...ur couper entièrement l alimentation de l équipement Tout contact avec des composants conducteurs de tensions dangereuses risque d entraîner une décharge électrique et de provoquer des blessures graves voire mortelles Important Do not apply 24 VAC power to the network engine before completing and checking connections Short circuits or improperly connected wires may result in permanent damage to th...

Страница 8: ...slots in the sides of the network engine housing Provide slack in the wires and cables Keep cables routed neatly around the network engine to promote good ventilation LED visibility and ease of service Ensure that the building automation network wiring meets the specifications rules and guidelines as outlined in the Power supply network and bus connections section The network engine does not requi...

Страница 9: ...rminal to the device s or B terminal c If the device has a Signal Ground or Reference terminal connect this to the converter s CG2 terminal Figure 5 Connection between converter and device 4 To add additional vendor devices wire from one device to the next as shown in Figure 6 No more than two wires may be connected to each terminal to ensure the daisy chain configuration See Wiring rules and guid...

Страница 10: ...mpleted wiring should look similar to Figure 7 Figure 7 Modbus wiring detail overview 5 Connect the 24 VAC supply power wires from the transformer to the removable power terminal block plug on the NAE Figure 8 NAE35 NAE45 Installation Guide 10 ...

Страница 11: ...Wire to terminals GND RxD and TxD as shown in Figure 9 3 Wire from the M and M terminals on the level converter Figure 9 to the meters using a free star tree or line topology Specific cabling can vary depending on the topology and site See Wiring rules and guidelines for network integrations Note If the number of M Bus unit loads or distances exceeds the specifications of a level converter an M Bu...

Страница 12: ...e to the port on the front of the KNX gateway Figure 10 Note Depending on the size of your network you can use either a KNX Interface or Router as a gateway The Interface connects the NAE to a single KNX line while the Router acts as both an Interface and a Line Coupler over Ethernet to connect the NAE to the network not to a single device NAE35 NAE45 Installation Guide 12 ...

Страница 13: ...iple KNX lines wire from the red and black terminals on each gateway to the devices on the same KNX line Note Specific cabling can vary depending on the topology and site See Wiring rules and guidelines for network integrations 4 Wire each KNX gateway to its own dedicated power supply on the KNX line 13 NAE35 NAE45 Installation Guide ...

Страница 14: ...hown below The LonWorks network trunk is available on the MS NAE3520 2 and MS NAE4520 3 models at Release 9 0 only Figure 11 LonWorks network terminal block and wiring connections 2 To add additional vendor devices wire from one device to the next in a daisy chained fashion Do not connect more than two wires to each terminal NAE35 NAE45 Installation Guide 14 ...

Страница 15: ...le isolate and insulate unused conductor Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for more information Terminations Two FC Bus devices with EOL switches in the ON position one at each end of each FC Bus segment 1 If the TEC Thermostat Controllers or third party MS TP devices are connected to the FC Bus the maximum total number of MS TP controllers on an FC Bus is 64 fo...

Страница 16: ...ype Maximum Segment Length with FTT10 Devices Only 1 Maximum Segment Length with FTT10 and or LPT10 Devices 1 Belden 85102 Cable 2 700 m 8 850 ft 2 200 m 7 200 ft Belden 8471 Cable 2 700 m 8 850 ft 2 200 m 7 200 ft Level IV 0 6 mm 22 AWG 1 400 m 4 600 ft 1 150 m 3 770 ft JY St Y 2 x 2 x 0 8 900 m 2 950 ft 750 m 2 460 ft 1 For the bus topology the maximum length stub cable is 3 m 10 ft and the stub...

Страница 17: ...n of individual LPT10 devices may limit a segment to fewer devices The MS NAE352x x an MS NAE452x x models that support a LonWorks Network trunk do not have an internal network terminator Table 7 Ethernet network rules Category Rules Maximums Allowed 1 General Point to point star topology with network hubs switches Number of Devices Maximum of 100 supervisory devices may be connected to one site i...

Страница 18: ...mplete the start up sequence and the RUN LED to go On steady before initiating any other action on the network engine Disconnecting power from the Network Engine When 24 VAC supply power to a network engine is disconnected or lost the network engine is nonoperational but the POWER LED remains On and the data protection battery continues to power the network engine for approximately 1 to 5 minutes ...

Страница 19: ...Figure 12 FC Bus EOL switch in the factory default ON up position Figure 13 EOL switch setting N2 or MS TP 19 NAE35 NAE45 Installation Guide ...

Страница 20: ...ence occurs 1 The POWER BAT FAULT 10 LINK FAULT RUN and PEER COM LEDs turn On indicating that the OS is booting up After 2 seconds the LEDs may change states depending on site specific network activity 2 The BAT FAULT PEER COM and FAULT LEDs shut Off The RUN LED flashes to indicate that the network engine software is loading 3 The LEDs display the status of the network engine When the RUN LED goes...

Страница 21: ... FC Bus is transmitting and receiving data Flickers are generally in sync with data transmission but should not be used to indicate specific transmission times Off Steady No field controllers are defined to FC Bus in the network engine PEER COM Green Varies see next column Flicker Data traffic between network engines For a network engine that is not a Site Director this LED indicates regular heart...

Страница 22: ...n a site with a new network engine for any reason or add a new network engine to a site you must update the site registration to ensure that the new network engine is recognized and able to communicate in the site Refer to the Replacing an NAE section of the NAE Commissioning Guide LIT 1201519 for information on removing a network engine from service and configuring a replacement network engine to...

Страница 23: ...ces on the N2 or BACnet MS TP trunk MS NAE3511 2 9 0 7 1 Supports one N2 or BACnet MS TP RS 485 trunk includes an internal modem supports a maximum of 50 devices on the N2 or BACnet MS TP trunk Note Modem and pager functions are no longer available if this engine is updated with Metasys Release 9 0 7 or later MS NAE3514 2 9 0 7 Supports one N2 or BACnet MS TP RS 485 trunk features Basic Access sup...

Страница 24: ...ports a maximum of 127 devices on the LonWorks trunk MS NAE4521 2 9 0 Supports one LonWorks trunk includes an internal modem supports a maximum of 127 devices on the LonWorks trunk MS NAE451L 2 9 0 7 Supports one BACnet MS TP RS 485 trunk supports a maximum of 100 BACnet MS TP devices on the trunk N2 Bus field trunk is not supported This model is currently available only in select regions For deta...

Страница 25: ... to an older Metasys release that uses a Windows Embedded OS Network and Serial Interfaces One Ethernet port 10 100 Mbps 8 pin RJ 45 connector One optically isolated RS 485 port 9600 19 2k 38 4k or 76 8k baud depending on protocol with a pluggable and keyed 4 position terminal block FC Bus available on NAE351x 1 and NAE451x 1 models only One LonWORKS port FTT10 78 Kbps pluggable keyed 3 position t...

Страница 26: ...liant ICES 003 Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive Australia and New Zealand RCM Mark Australia NZ Emissions Compliant Compliance BACnet International BTL 135 2004 Listed B BC The performance specifications are nominal and conform to acceptable industry standard For applic...

Страница 27: ...gy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in which case the users will be required to correct the interference at their own expense Canada This Class A digital apparatus meets all the requirements of the Canadian Interference Causi...

Страница 28: ... 2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com ...

Отзывы: