background image

Table 4: Communication Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and
Cables

Recommended Cable Type

1

Function, Electrical Ratings/Requirements

Terminal Labels

Terminal
Block/Port Label

24 AWG 3-pair CAT 3 Cable

<30.5 m (100 ft)

RJ-12 6-Position Modular Connector provides:

SA Bus Communications

SA Bus Signal Reference and 15 VDC Common

15 VDC Power for devices on the SA Bus

SENSOR

SENSOR

2

(SA Bus Port)

0.8 mm to 1.0 mm

(20 to 18 AWG) 2-wire

24 VAC Power Supply - Hot

Supplies 20–30 VAC (Nominal 24 VAC)

HOT

24~

24 VAC Power Supply Common

(Isolated from

all other Common terminals on controller)

COM

1

See

Table 2

to determine wire size and cable lengths for cables other than the recommended cables.

2

The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38.4k baud. For more
information, refer to the

MS/TP Communications Bus Technical Bulletin (LIT-12011034)

.

Setup and Adjustments

Important:

Electrostatic discharge can damage
controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.

Setting the Device Address

Metasys

field controllers are master devices on BACnet

MS/TP (SA or FC) buses. Before operating controllers
on a bus, you

must

set a valid and unique device address

for each controller on the bus.

You set a controller's device address by setting the
positions of the switches on the Device Address DIP
switch block at the top of the controller (

Figure 2

). Valid

addresses for these controllers are device addresses 4
through 127.

The DIP switch block (

Figure 8

) has eight switches

numbered 128, 64, 32, 16, 8, 4, 2, and 1. Switches 64
through 1 are device address switches. Switch 128 is a
mode switch that enables a field controller to operate on
a ZFR1800 Series Wireless Field Bus. Switch 128 must
be set to off for all hard-wired SA and FC Bus
applications.

Figure 8: Device Address Switches Set to 21

Note: Metasys

field controllers ship with switch 128 ON

and the remaining address switches off. This
renders the controllers wired slave devices, which
do not operate on MS/TP buses, but do not
interfere with bus operation. Set a valid and
unique device address on the controller before
applying power to the controller on the bus.

To set the device addresses on a VMA controller:

1. Set all of the switches on the controller’s device

address DIP switch block (128 through 1) to off.

2. Set one or more of the seven address switches (64

through 1) to ON, so that the sum of the switch
numbers set to ON equals the intended device
address. See

Table 5

for valid controller addresses.

Set the highest number switch that is less than or
equal to the intended device address to ON. Then
continue setting lower numbered switches until the
total equals the intended address. For example, if the
intended device address is 21, set switch 16 to ON
first, then set switch 4 ON, followed by switch 1
(16+4+1= 21). See

Figure 8

.

Note:

Do not connect a field controller with switch
128 set to

ON

to an active (hard-wired) SA or

FC Bus. When a controller with switch 128 set
to

ON

and a device address from 4 to 127 is

connected to a wired field bus, the entire field
bus is rendered inoperable until the controller
is disconnected or switch 128 is set to

OFF

.

3. Set a unique and sequential device address for each

of the controllers connected on the SA or FC Bus
starting with device address 4.

14

VMA1610 and VMA1620 Variable Air Volume Controllers Installation Instructions

Содержание Metasys VMA1610

Страница 1: ...ol Equipment is voided if 1 you do not use the required software tools at the required versions or 2 you do not meet the requirements or do not follow the procedures as documented in the Metasys System UL 864 UUKL Tenth Edition Smoke Control System Technical Bulletin LIT 12012487 North American Emissions Compliance United States This equipment has been tested and found to comply with the limits fo...

Страница 2: ...wiring connections are easily accessible Make sure the controller base is parallel to the VAV box perpendicular to the damper shaft If needed use a spacer to offset tipping of the VMA controller caused by the shaft bushings 2 Secure the self drilling No 10 screw through the VMA controller mounting slot with a power screwdriver and 100 mm 4 in extension socket Otherwise use a punch to mark the posi...

Страница 3: ...y rotating the damper to the fully open position Risk of Property Damage Rotate the damper to the full open position before starting the air handler Failure to rotate the damper to the full open position may result in damage to the VAV box or ductwork when the air handler is started Mise En Garde Risque de dégâts matériels Faire pivoter le registre pour le placer en position d ouverture complète a...

Страница 4: ...Figure 2 VMA16 Controller Physical Features and Wiring Terminations 4 VMA1610 and VMA1620 Variable Air Volume Controllers Installation Instructions ...

Страница 5: ...1034 VMA Terminals and Bus Ports See Figure 2 for input and output terminal and bus port locations on the VMA controller Observe the following guidelines when wiring a VMA controller Input and Output Terminals The input spade terminals are located on the side of the VMA near the device address switch The output spade terminals are located on the opposite side of the controller near the power suppl...

Страница 6: ...al block is not used See Table 4 for more information The supply power wire colors may be different on transformers from other manufacturers Refer to the transformer manufacturer s instructions and the project installation drawings for wiring details Important Connect 24 VAC supply power to the VMA and all other network devices so that transformer phasing is uniform across the network devices Powe...

Страница 7: ... input output software setup Table 1 I O Terminal Blocks Functions Ratings Requirements and Cables To Determine Wire Size and Maximum Cable Length Function Ratings and Requirements Terminal Labels Terminal Block Label Same as Universal INn Note Use 3 wire cable for devices that source power from the 15 V terminal 15 VDC Power Source for active 3 wire input devices connected to the Universal INn te...

Страница 8: ...OUTn CONFIGURABLE Outputs See Guideline C in Table 2 Binary Output 24 VAC Triac Connects OUT to OCOM when activated External Power Source 30 VAC maximum voltage to load 0 5 A maximum output current 1 3 A at 25 duty cycle Maximum 6 cycles hour with M9220 BGx 3 40 mA minimum load current Same as Configurable OUTn Analog Output Signal Common All Configurable Outputs defined as Analog Outputs share a ...

Страница 9: ...fine an offset in the setup software for the input or output point 229 m 750 ft twisted wire 1 0 mm 18 AWG stranded copper B 137 m 450 ft twisted wire 0 8 mm 20 AWG stranded copper 91 m 300 ft twisted wire 0 6 mm 22 AWG stranded copper 61 m 200 ft twisted wire 0 5 mm 24 AWG stranded copper N A See Figure 7 to determine cable length Use twisted wire cable See Figure 7 to select wire size gauge Use ...

Страница 10: ...put Self Powered UI Dry Contact CO or AO 0 10 VDC Output to Actuator External Source CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO Analog Output Voltage CO or AO 24 VAC Triac Output Switch Low External Source 10 VMA1610 and VMA1620 Variable Air Volume Controllers Installation Instructions ...

Страница 11: ...emental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output Switch Low Internal Source BO Incremental Control to Actuator Switch Low Internal Source SA Bus Network Stat with Phone Jack Fixed Address 199 11 VMA1610 and VMA1620 Variable Air Volume Controllers Installation Instructions ...

Страница 12: ...als Addressable SA Bus Network Stat with Terminals Fixed Address 199 Maximum Cable Length versus Load Current Use Figure 7 to estimate the maximum cable length relative to the wire size and the load current in mA when wiring inputs and outputs 12 VMA1610 and VMA1620 Variable Air Volume Controllers Installation Instructions ...

Страница 13: ... Bulletin LIT 12011034 for detailed information regarding wire size and cable length requirements for the FC and SA buses Table 4 Communication Bus and Supply Power Terminal Blocks Functions Ratings Requirements and Cables Recommended Cable Type 1 Function Electrical Ratings Requirements Terminal Labels Terminal Block Port Label 0 6 mm 22 AWG stranded 3 wire twisted shielded cable recommended FC B...

Страница 14: ...8 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address switches Switch 128 is a mode switch that enables a field controller to operate on a ZFR1800 Series Wireless Field Bus Switch 128 must be set to off for all hard wired SA and FC Bus applications Figure 8 Device Address Switches Set to 21 Note Metasys field controllers ship with switch 128 ON and the remaining address switches off This...

Страница 15: ...VMA controller on the SA or FC Bus 2 Determine if the controller must be set as a terminating device on the bus Note The EOL termination rules for SA Buses and FC Buses are different Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for detailed information regarding EOL termination rules and EOL switch settings on SA and FC Buses 3 If the controller is a terminating device on ...

Страница 16: ...able 7 VMA Accessories Order Separately Description Product Code Number Transformer 96 VA Class 2 120 24 VAC power supply compliant for UL 864 UUKL UUKLC Tenth Edition Smoke Control System PAN PWRSP U 2 position Screw Terminal that Plugs onto VMA Output Point Spade Lugs AP TBK1002 0 3 position Screw Terminal that Plugs onto VMA Output Point Spade Lugs AP TBK1003 0 Replacement MS TP SA Bus Terminal...

Страница 17: ... F Storage 40 to 70 C 40 to 158 F Ambient Conditions Inputs Outputs 6 3 mm 1 4 in spade lugs FC Bus SA Bus and Supply Power 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Sensor Port RJ 12 6 Pin Modular Jacks Terminations DIP switch set valid controller device addresses 4 127 Device addresses 0 3 and 128 255 are reserved and not valid controller addresses Controller Addressing BACnet MS TP RS 4...

Страница 18: ...dels only FCC Compliant to CFR47 Part 15 Subpart B Class A Compliance Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment UL Listed File S4977 UUKLC ULC ORD C100 13 Smoke Control System Equipment MS VMA1610 0U MS VMA1610 1U MS VMA1620 0U and MS VMA1620 1U models only Industry Canada Compliant ICES 003 Europe CE Mark Johnson Controls declares that this product is in compli...

Страница 19: ...ys and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2017 Johnson Controls www johnsoncontrols com Published in U S A 19 VMA1610 and VMA1620 Variable Air Volume Controllers Installation Instructions ...

Отзывы: