                                                                                                                                         Installation Instructions     M9216 
                                                                                                                                                             Issue Date    October 2017 

©  2017 Johnson Controls

 

1

 

  Part No. 34-636-461, Rev. J 

www.johnsoncontrols.com 

 

 

 

M9216 Series Electric Spring Return Actuators

 

Installation 

IMPORTANT: 

The M9216 Series actuator is 

intended to control equipment under normal 
operating conditions. Where failure or malfunction of 
an M9216 actuator could lead to an abnormal 
operating condition that could cause personal injury 
or damage to the equipment or other property, other 
devices (limit or safety controls) or systems (alarm or 
supervisory) intended to warn of, or protect against, 
failure or malfunction of an M9216 actuator must be 
incorporated into and maintained as part of the 
control system. 

Parts Included 

 

M9216 actuator 

 

M9000-100 NPT conduit adaptor and nut 
(two included for actuators with switches or a 
feedback potentiometer) 

 

M9000-160 anti-rotation bracket 

 

two No. 12-24 x 1/2 in. self-tapping hex 
washer-head screws 

 

5 mm manual crank 

For GGA models: 

 

one M9000-106 pluggable 4-terminal block 

For GGC models: 

 

two M9000-105 pluggable 3-terminal blocks 

 

one M9000-106 pluggable 4-terminal block 

Special Tools Needed 

 

Drill with a 3/16 in. (No. 15, 4.57 mm) drill bit 

 

Torque wrench with 10 mm socket 

 

7 mm and 5/16 in. (8 mm) nut driver 

 

Digital voltmeter 

Spring Return Direction 

The actuator is factory set to spring return in a 
Counterclockwise (CCW) direction. 

Clockwise (CW) 

To change the spring return direction to CW, refer to 
Figure 1 and proceed as follows: 

1.  Turn the actuator over. Use a flat-blade 

screwdriver to release the locking clip, and remove 
it from the coupler. 

2.  Remove the coupler and sleeve from the front of 

the actuator, and slide the sleeve off the coupler. 

Groove

for the

Locking Clip

Locking

Clip

Limit
Stop

Position
Indicator

Tab

Back of

the Actuator

Sleeve

 

Figure 1: Changing the Spring Return Direction 

*34636461G* 

34-636-461, Rev. J 

Содержание M9216 Series

Страница 1: ...otentiometer M9000 160 anti rotation bracket two No 12 24 x 1 2 in self tapping hex washer head screws 5 mm manual crank For GGA models one M9000 106 pluggable 4 terminal block For GGC models two M9000 105 pluggable 3 terminal blocks one M9000 106 pluggable 4 terminal block Special Tools Needed Drill with a 3 16 in No 15 4 57 mm drill bit Torque wrench with 10 mm socket 7 mm and 5 16 in 8 mm nut d...

Страница 2: ...he smooth half of the sleeve inserted first See Figure 2 Note Make sure the gap in the sleeve rim aligns with the two guide marks on the front of the actuator 4 Repeat Steps 4 5 and 6 of the previous section Mounting IMPORTANT Make sure the space between the back of the actuator and the mounting surface is at least 5 32 in 4 mm M9216 actuators may be mounted in any convenient orientation They may ...

Страница 3: ...0 Verify that the actuator rotates freely throughout the range This may be done by applying a full stroke control signal or reinserting the manual crank and turning it CW to rotate the coupler to the fully open position Rotation Range The actuator is factory set for 0 to 93 rotation The rotation range is changed by adjusting the rotation limiters This may be done by using an input signal or the ma...

Страница 4: ...Rotation Range 2 10V Feedback 0 10V Feedback Direct Acting 1000Ω 135Ω 113Ω 667Ω 90 Ω 45 Ω 167Ω Ω is ohms Ω Ω 0 0 833 Ω 68 Ω 23 Ω 0 135 ohms Feedback 0 1000 ohms Feedback Ω 500 333Ω Direct or Reverse Acting 2 10 V Feedback Reverse Acting 0 10V Feedback 0 0 V 1 7 V 3 3 V 5 0 V 6 7 V 8 3 V 10 0V 10 0V 8 7 V 7 3 V 6 0 V 4 7 V 3 3 V 2 0 V Rotation Limiter Adjustment Rotation Limiter Adjustment Note 0 1...

Страница 5: ... Note NC is normally closed NO is normally open and C is common C1 NC1 NO1 C2 NO2 NC2 0 10 V Proportional Control Models GGA and GGC 24 V COM Extra COM VAC VDC VDC mA FB Note COM is common and FB is feedback 0 10 V or 0 20 mA Resistive Input Control Models JGA and JGC 1 2 3 4 5 6 COM CCW CW 100 10 k ohms 0 10 V 24V Note Terminals 3 and 4 function as CCW and CW references when the Resistive models ...

Страница 6: ...b in 32 N m twice the torque of a single unit The actuators operate in exact synchronization ensuring the load is split evenly between each unit Use two actuators from the same model group BGx GGx or HGx for tandem operation BGx models must be wired in parallel for tandem operation GGx models employ Mode Switch 5 and HGx models employ Jumper W4 IMPORTANT When connecting two actuators back to back ...

Страница 7: ...ther HGx actuator to the slave position 2 Connect the control signal to the master actuator only and set the remaining jumpers on the master unit according to the action and signal range desired Refer to the Calibration section 3 Repeat Steps 3 through 4 from the GGx Models section If the actuators configured for tandem operation stall or do not drive Make sure both actuators are from the same mod...

Страница 8: ...tion of spring return rotation range or the linkage is changed respan by moving Mode Switch 1 to the fixed position for 5 seconds and then back to auto This reinitiates the auto mode The feedback output remains 0 to 10 VDC unless Mode Switch 3 is positioned for 2 to 10 VDC LED GGx Models The GGx models have a Light Emitting Diode LED indicator shown in Figure 13 When the actuator is driving to pos...

Страница 9: ...echnical Data section for auxiliary switch ratings The following procedures serve as examples to change the position of the auxiliary switch angles Switch S1 To change the angle of Switch S1 to 20 refer to Figure 14 and proceed as follows Position Indicator Plunger Manual Crank CCW 90 Nodule Guides 10 Increments Edge of Switch S1 Edge of Switch S2 0 CCW Figure 14 Switch Angle Settings 1 Insert the...

Страница 10: ... Throw rated at 24 VAC 1 5 A inductive 3 0 A resistive 35 VA maximum per switch Class 2 Spring Return Factory Setting CCW Direction is selectable with the coupler Mechanical Output Running Torque All Models 140 lb in 16 N m for one unit BGx GGx HGx 280 lb in 32 N m for two units in tandem Rotation Range Adjustable from 30 to 90 CW or CCW mechanically limited to 93 Rotation Time 70 to 130 seconds f...

Отзывы: