background image

 

 
 

Installation Instructions  M9206-DNx 

 

Issue Date  August 29, 2014 

 

M9206-DNx Series Electric Spring Return 

Economizer Damper Actuators 

 

Installation 

IMPORTANT: 

Use this M9206-DNx Series 

actuator only to control equipment under normal 
operating conditions. Where failure or malfunction of 
the damper actuator could lead to personal injury or 
property damage to the controlled equipment or 
other property, additional precautions must be 
designed into the control system. Incorporate and 
maintain other devices, such as

 

supervisory or alarm 

systems or safety or limit controls, intended to warn 
of or protect against failure or malfunction of the 
damper actuator. 

IMPORTANT : 

Utiliser ce M9206-DNx Series 

actuator uniquement pour commander des 
équipements dans des conditions normales de 
fonctionnement. Lorsqu'une défaillance ou un 
dysfonctionnement du damper actuator risque de 
provoquer des blessures ou d'endommager 
l'équipement contrôlé ou un autre équipement, la 
conception du système de contrôle doit intégrer des 
dispositifs de protection supplémentaires. Veiller 
dans ce cas à intégrer de façon permanente d'autres 
dispositifs, tels que des systèmes de supervision ou 
d'alarme, ou des dispositifs de sécurité ou de 
limitation, ayant une fonction d'avertissement ou de 
protection en cas de défaillance ou de 
dysfonctionnement du damper actuator. 

The M9206-DNx actuator is designed for use with the 
Johnson Controls AD-DME100-0 Economizer 
Controller.  

Parts Included 

The M9206-DNx actuator is included. 

Special Tools Required 

 

5/16 in. (8 mm) square socket or 3/8 in. (10 mm) 
12-point socket 

 

5/16 in. (8 mm) hex socket or nut driver 

Setup and Adjustments 

Spring Return Direction - Counterclockwise (CCW) 
Operation 

For CCW spring return operation, mount the actuator 
to the damper shaft so the CCW face of the actuator 
(Figure 1) is away from the damper. The coupler is at 
the 0° position to drive Clockwise (CW) and spring 
return CCW. 

Arrow

Indicating

CCW

Spring Return

Direction

Auxiliary

Switch

Adjuster

Located

on the Left

0° Position

 

Figure 1: CCW Face of the Actuator 

Spring Return Direction - Clockwise (CW) 
Operation 

To change the spring return direction to CW, mount 
the actuator to the damper shaft so the CW face of the 
actuator (Figure 2) is away from the damper. The 
actuator now drives CCW from the 0° position. 

Arrow

Indicating

CW

Spring Return

Direction

Auxiliary

Switch

Adjuster

Located

on the Right

0° Position

 

Figure 2: CW Face of the Actuator 

©  2014 Johnson Controls, Inc.

 

1

 

  Part No. 34-1280-130, Rev. C 

www.johnsoncontrols.com

 

Содержание M9206-DN Series

Страница 1: ...supervision ou d alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du damper actuator The M9206 DNx actuator is designed for use with the Johnson Controls AD DME100 0 Economizer Controller Parts Included The M9206 DNx actuator is included Special Tools Required 5 16 in 8 mm square socket or 3 8 i...

Страница 2: ...omizer applications only Install the actuators on a 1 2 in 13 mm round damper shaft using the M9000 159 anti rotation bracket If the shaft extends less than 3 2 in 80 mm refer to the Removable Coupler section Note The anti rotation bracket is part of the economizer installation but not included with an M9206 DNx actuator If the bracket is missing order one using product code number M9000 159 You m...

Страница 3: ... screw is midway between the 40 and 50 nodule guides 90 45 45 Note The minimum rotation range is 34 5 3 Snap the locking clip securely into the coupler groove to retain the coupler in the actuator Wiring WARNING Risk of Electric Shock Disconnect or isolate all power supplies before making electrical connections More than one disconnection or isolation may be required to completely de energize equi...

Страница 4: ...built in auxiliary switch with a switch adjuster accessible on either face of the actuator See Figure 1 and Figure 2 The factory setting is 20 Refer to the Auxiliary Switch Rating in the Technical Specifications section The switch point is continuously adjustable from 0 to 90 For the most accurate position of the switch refer to Figure 9 and use the method in the following example To change the tr...

Страница 5: ...econds maximum Cycles 60 000 full stroke cycles rated at 53 lb in 6 N m Audible Noise Rating 55 dBA nominal at 1 m Electrical Connection Actuator 17 in 0 43 m cable with 5 pin connector Auxiliary Switch 48 in 1 2 m cable with 18 AWG wire leads Mechanical Connection 1 2 in 13 0 mm diameter round shaft or a 3 8 in 10 mm square shaft Enclosure IP20 Ambient Conditions Operating 25 to 140 F 32 to 60 C ...