M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Guide
10
Audible Noise
Rating
Power On
(Running)
-AGx-2 Models
<28 dBA at 27 lb·in. (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Power On
(Running)
-AGx-2Z Models
<37 dBA at 27 lb·in. (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Power On
(Holding)
<20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off
(Spring
Returning)
<56 dBA at 27 lb·in. (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Electrical
Connections
-AGA-2(Z) Models
120 in. (3.05 m) UL 444 Type CMP Plenum Rated Cable with 19 AWG
(0.75 mm²) Conductors and 0.25 in. (6 mm) Ferrule Ends
Auxiliary Switch
(-xxB Models)
48 in. (1.2 m) UL 758 Type AWM Halogen Free Cable with 18 AWG (0.85 mm²)
Conductors and 0.25 in. (6 mm) Ferrule Ends
Conduit Connections
Integral 1/2 in. (13 mm) Threaded Conduit Connector(s)
Mechanical
Connections
Round Shafts
Range of Sizes: 1/4 to 1/2 in. (6 to 12 mm)
Square Shafts
Range of Sizes: 1/4 to 5/16 in. (6 to 8 mm)
Enclosure Rating
NEMA 2 (IP54) for all Mounting Orientations
Ambient
Conditions
Standard
Operating
-22 to 140°F (-30 to 60°C); 90% RH Maximum, Noncondensing
Storage
-40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
Dimensions
6.38 x 3.23 x 2.26 in. (162 x 82 x 57.5 mm)
Compliance
United States
UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1,
Automatic Electrical Controls for Household and Similar Use;
and UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for Electric
Actuators. (Models: All)
Plenum Rated (UL 2043). Suitable for use in other environmental air space
(plenums) in accordance with Section 300.22 (C) of the National Electric Code
Canada
UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002,
3rd Ed., Automatic Electrical Controls for Household and Similar Use;
and CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment
(Models: All)
Europe
CE Mark – Johnson Controls, Inc. declares that this product is in compliance with
the essential requirements and other relevant provisions of the EMC Directive
and Low Voltage Directive.
Australia and
New Zealand
RCM Mark, Australia/NZ Emissions Compliant (Models: All)
Shipping Weight
-AGA Models: 2.0 lb (0.9 kg)
-AGB Models: 2.4 lb (1.1 kg)
M9203-AGx-2(Z) Series On/Off and Floating Point Control Electric Spring Return Actuator
(Part 2 of 2 )