Technical Data
Product
M9106-AGx-2N0x Series Electric Non-Spring Return Actuators
Power Requirements
M9106-AGA-2N01:
20 to 30 VAC at 50/60 Hz, 2.5 VA supply, Class 2
M9106-AGx-2N02:
20 to 30 VAC at 50/60 Hz, 2.1 VA supply, Class 2
DPT-2015:
15 VDC (14.5 to 17 VDC) unregulated; 15 mA maximum
Input Signal
M9106-AGx-2N0x:
24 VAC (20 to 30 VAC) at 50 or 60 Hz
Motor Input Impedance
M9106-AGA-2N01:
200 ohms, nominal
M9106-AGx-2N02:
250 ohms, nominal
DPT-2015-0
Pressure Range:
0 to 1.5 in. W.C. (0 to 374 Pa)
Over Pressure Limit: 15 in. W.C. (3.74 kPa)
Output Voltage:
0.5 to 4.5 VDC with 25,000 ohm minimum load impedance
Mechanical Output
Running Torque:
53 lb∙in (6 N∙m)
Cycles
100,000 full cycles; 2,500,000 repositions rated at 53 lb∙in (6 N∙m)
Audible Noise Rating
35 dBA maximum at 1 m
Rotation Range
Adjustable from 30 to 90°, CW or CCW
Rotation Time
M9106-AGx-2N01:
Nominal 60 seconds at 60 Hz and 72 seconds at 50 Hz for 90°
M9106-AGS-2N02:
Nominal 120 seconds at 60 Hz and 144 seconds at 50 Hz for 90°
Electrical Connection
No. 6-32 screw terminals on the M9106 actuator; 1/4 in. spade terminals on the DPT-2015
Pressure Connection
6 in. (152 mm) length of silicone tubing with barbed fittings for 1/4 in. (6.35 mm)
O.D. tubing
Enclosure
NEMA1, IP30
Ambient Operating
Conditions
M9106-AGA-2N0x:
32 to 125°F (0 to 52°C); 90% RH maximum, non-condensing
M9106-AGS-2N02:
32 to 125°F (0 to 52°C); 90% RH maximum, non-condensing
60 to 100°F (16 to 38°C); 90% RH maximum, non-condensing
For DPT rated accuracy, see
DPT-2015 Differential Pressure Transmitter for VAV Box
Applications Installation Instructions (Part No. 24-7547-18).
Ambient Storage
Conditions
-20 to 150°F (-29 to 66°C); 90% RH maximum, non-condensing
Dimensions (H x W x D)
M9106-AGA-2N01:
5.95 x 4.2 x 2.15 in. (151.2 x 107.3 x 54.6 mm)
M9106-AGx-2N02: 5.95 x 4.2 x 2.32 in. (151.2 x 107.3 x 58.9 mm) with the DPT-2015
Shipping Weight
M9106-AGA-2N0x:
2.0 lb (0.91 kg)
M9106-AGS-2N02:
2.2 lb (0.99 kg) with the DPT-2015
Agency Compliance
(M9106 Actuator)
UL 873 Listed, File E27734, CCN XAPX
CSA C22.2 No. 139 Certified, File LR85083, Class 3221 02
CE Mark, EMC Directive 89/336/EEC
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.
6
M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions