Technical Data 

Product 

M9106-AGx-2N0x Series Electric Non-Spring Return Actuators 

Power Requirements 

M9106-AGA-2N01: 

20 to 30 VAC at 50/60 Hz, 2.5 VA supply, Class 2 

M9106-AGx-2N02: 

20 to 30 VAC at 50/60 Hz, 2.1 VA supply, Class 2 

DPT-2015: 

15 VDC (14.5 to 17 VDC) unregulated; 15 mA maximum 

Input Signal 

M9106-AGx-2N0x: 

24 VAC (20 to 30 VAC) at 50 or 60 Hz 

Motor Input Impedance 

M9106-AGA-2N01: 

200 ohms, nominal 

M9106-AGx-2N02: 

250 ohms, nominal 

DPT-2015-0 

Pressure Range: 

0 to 1.5 in. W.C. (0 to 374 Pa) 

Over Pressure Limit:  15 in. W.C. (3.74 kPa) 
Output Voltage: 

0.5 to 4.5 VDC with 25,000 ohm minimum load impedance 

Mechanical Output 

Running Torque: 

53 lb∙in (6 N∙m) 

Cycles 

100,000 full cycles; 2,500,000 repositions rated at 53 lb∙in (6 N∙m) 

Audible Noise Rating 

35 dBA maximum at 1 m 

Rotation Range 

Adjustable from 30 to 90°, CW or CCW 

Rotation Time 

M9106-AGx-2N01: 

Nominal 60 seconds at 60 Hz and 72 seconds at 50 Hz for 90° 

M9106-AGS-2N02: 

Nominal 120 seconds at 60 Hz and 144 seconds at 50 Hz for 90° 

Electrical Connection 

No. 6-32 screw terminals on the M9106 actuator; 1/4 in. spade terminals on the DPT-2015 

Pressure Connection 

6 in. (152 mm) length of silicone tubing with barbed fittings for 1/4 in. (6.35 mm) 
O.D. tubing 

Enclosure 

NEMA1, IP30 

Ambient Operating 
Conditions 

M9106-AGA-2N0x: 

32 to 125°F (0 to 52°C); 90% RH maximum, non-condensing 

M9106-AGS-2N02: 

32 to 125°F (0 to 52°C); 90% RH maximum, non-condensing 

 

60 to 100°F (16 to 38°C); 90% RH maximum, non-condensing 

For DPT rated accuracy, see 

DPT-2015 Differential Pressure Transmitter for VAV Box 

Applications Installation Instructions (Part No. 24-7547-18).

 

Ambient Storage 
Conditions 

-20 to 150°F (-29 to 66°C); 90% RH maximum, non-condensing 

Dimensions (H x W x D) 

M9106-AGA-2N01: 

5.95 x 4.2 x 2.15 in. (151.2 x 107.3 x 54.6 mm) 

M9106-AGx-2N02: 5.95 x 4.2 x 2.32 in. (151.2 x 107.3 x 58.9 mm) with the DPT-2015 

Shipping Weight 

M9106-AGA-2N0x: 

2.0 lb (0.91 kg) 

M9106-AGS-2N02: 

2.2 lb (0.99 kg) with the DPT-2015 

Agency Compliance 
(M9106 Actuator) 

UL 873 Listed, File E27734, CCN XAPX 
CSA C22.2 No. 139 Certified, File LR85083, Class 3221 02 
CE Mark, EMC Directive 89/336/EEC 

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication 
or misuse of its products. 
 

Building Efficiency

 

507 E. Michigan Street, Milwaukee, WI  53202 

 

 

Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.  

All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.

 

6    

M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions 

Содержание M9106-AG 2N0 Series

Страница 1: ...e sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du actuators The actuator may be mounted in any convenient orientation When installing the DPT 2015 Differential Pressure Transmitter on the actuator mount it so the tubing connecting the flow pick up device to the DPT 2015 creates a moisture trap This will prevent condensa...

Страница 2: ...aft as shown in Figure 4 Figure 4 Damper Position Icons To set the actuator stroke proceed as follows 1 Grasp the damper shaft firmly with pliers and rotate the damper fully closed See Figure 5 Damper Shaft CCW to Close CW to Close Damper Blade Damper Figure 5 Damper Rotation 2 Press and hold the gear release lever shown in Figure 2 and rotate the actuator coupler to the fully closed position 3 Ma...

Страница 3: ...upler to the minimum rotation position for the minimum ventilation flow required 2 Release the gear release lever 3 Use a Phillips screwdriver to loosen the end stop set screw that is closest to the stop gear Move the end stop set screw in its slot until it is tight against the stop gear See Figure 6 IMPORTANT Do not remove the end stop set screws as this could interfere with the actuator s operat...

Страница 4: ...the end of rotation stall The 20 in 0 5 m CBL 2000 1 Wiring Harness accepted by Underwriters Laboratories Inc UL for plenum use is pre wired with the M9106 AGS 2N02 or may be ordered separately The plenum rated 20 in 0 5 m CBL 2000 2 and 72 in 1 8 m CBL 2000 3 Wiring Harnesses are also available See Table 1 Setup and Adjustments Air Pressure M9106 AGS 2N02 The flow pickup device provided with the ...

Страница 5: ...power is applied Verify that the damper fully opens and closes using the gear release lever on the actuator Check that the actuator stroke is set for the desired application DPT 2015 The DPT 2015 must be auto zeroed by a Johnson Controls VAV controller If the DPT 2015 is not operating properly Verify that the air lines on the DPT 2015 are connected to their respective high and low ports with no ki...

Страница 6: ...itions M9106 AGA 2N0x 32 to 125 F 0 to 52 C 90 RH maximum non condensing M9106 AGS 2N02 32 to 125 F 0 to 52 C 90 RH maximum non condensing 60 to 100 F 16 to 38 C 90 RH maximum non condensing For DPT rated accuracy see DPT 2015 Differential Pressure Transmitter for VAV Box Applications Installation Instructions Part No 24 7547 18 Ambient Storage Conditions 20 to 150 F 29 to 66 C 90 RH maximum non c...