Johnson Controls M9106-AG 2N0 Series Скачать руководство пользователя страница 2

Approximately

an 1/8 in.

(3.2 mm) Gap

Gear

Release

Lever

Mounting

Surface

DPT-2015

 

Figure 2: Actuator Position 

3.  Verify that the shoulder washer is centered 

between the plastic ribs of the actuator housing to 
allow actuator movement during rotation. 
(See Figure 3.) 

Shoulder
 Washer

Plastic Ribs

Self-drilling
Sheet Metal
   Screw

CCW

COM

CW

O

U

T

G

N

D

  I

N

(-

)L

O

D

P

T-

20

15

 

Figure 3: Shoulder Washer Position 

4.  Hold the actuator in place on the damper shaft, 

and insert the self-drilling sheet metal screw 
through the shoulder washer. (See Figure 3.) 

5.  Place a 5/16 in. (8 mm) socket on the screw and 

using a drill and extension, drill the screw into the 
mounting surface until tight against the washer. 

IMPORTANT: 

Do not overtighten the mounting 

screw to avoid stripping the threads. 

Rotation Range 

Make sure that the damper blade is visually accessible 
or its position is permanently marked on the end of the 
damper shaft as shown in Figure 4. 

 

Figure 4: Damper Position Icons

 

To set the actuator stroke, proceed as follows: 

1.  Grasp the damper shaft firmly with pliers and 

rotate the damper fully closed. (See Figure 5.) 

Damper

Shaft

CCW to

Close

CW to

Close

Damper

Blade

Damper

 

Figure 5: Damper Rotation  

2.  Press and hold the gear release lever shown in 

Figure 2, and rotate the actuator coupler to the 
fully closed position. 

3.  Make a note of the rotation travel and direction, 

either Clockwise (CW) or Counterclockwise 
(CCW), required to close the damper. 

If rotation is less than 90°, proceed to 

Less Than 

90 Degrees

 section. 

IMPORTANT: 

Do not remove the sheet metal 

screw and force the damper blade closed by rotating 
the actuator. This puts additional stress on the gear 
train and could reduce the life of the actuator. 

90 Degrees 

1.  Release the gear release lever. 

2.  Secure the coupler to the shaft using a crescent 

wrench or one of the tools from the Special Tools 
Needed section to tighten the coupler set screw 
against the damper shaft. (See Figure 6.) 

2    

M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions 

Содержание M9106-AG 2N0 Series

Страница 1: ...e sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du actuators The actuator may be mounted in any convenient orientation When installing the DPT 2015 Differential Pressure Transmitter on the actuator mount it so the tubing connecting the flow pick up device to the DPT 2015 creates a moisture trap This will prevent condensa...

Страница 2: ...aft as shown in Figure 4 Figure 4 Damper Position Icons To set the actuator stroke proceed as follows 1 Grasp the damper shaft firmly with pliers and rotate the damper fully closed See Figure 5 Damper Shaft CCW to Close CW to Close Damper Blade Damper Figure 5 Damper Rotation 2 Press and hold the gear release lever shown in Figure 2 and rotate the actuator coupler to the fully closed position 3 Ma...

Страница 3: ...upler to the minimum rotation position for the minimum ventilation flow required 2 Release the gear release lever 3 Use a Phillips screwdriver to loosen the end stop set screw that is closest to the stop gear Move the end stop set screw in its slot until it is tight against the stop gear See Figure 6 IMPORTANT Do not remove the end stop set screws as this could interfere with the actuator s operat...

Страница 4: ...the end of rotation stall The 20 in 0 5 m CBL 2000 1 Wiring Harness accepted by Underwriters Laboratories Inc UL for plenum use is pre wired with the M9106 AGS 2N02 or may be ordered separately The plenum rated 20 in 0 5 m CBL 2000 2 and 72 in 1 8 m CBL 2000 3 Wiring Harnesses are also available See Table 1 Setup and Adjustments Air Pressure M9106 AGS 2N02 The flow pickup device provided with the ...

Страница 5: ...power is applied Verify that the damper fully opens and closes using the gear release lever on the actuator Check that the actuator stroke is set for the desired application DPT 2015 The DPT 2015 must be auto zeroed by a Johnson Controls VAV controller If the DPT 2015 is not operating properly Verify that the air lines on the DPT 2015 are connected to their respective high and low ports with no ki...

Страница 6: ...itions M9106 AGA 2N0x 32 to 125 F 0 to 52 C 90 RH maximum non condensing M9106 AGS 2N02 32 to 125 F 0 to 52 C 90 RH maximum non condensing 60 to 100 F 16 to 38 C 90 RH maximum non condensing For DPT rated accuracy see DPT 2015 Differential Pressure Transmitter for VAV Box Applications Installation Instructions Part No 24 7547 18 Ambient Storage Conditions 20 to 150 F 29 to 66 C 90 RH maximum non c...

Отзывы: