Johnson Controls M9106-AG 2N0 Series Скачать руководство пользователя страница 1

 

 

   

 

Installation Instructions  M9106AGx-2N0x 

 

Issue Date  June 3, 2014 

 

M9106-AGx-2N0x Series Electric 

Non-Spring Return Actuators 

Installation 

IMPORTANT:

  Use this M9106-AGx-2N0x Series 

Actuator only to control equipment 
under normal operating conditions. 
Where failure or malfunction of the 
actuators could lead to personal 
injury or property damage to the 
controlled equipment or other 
property, additional precautions must 
be designed into the control system. 
Incorporate and maintain other 
devices, such as supervisory or alarm 
systems or safety or limit controls, 
intended to warn of or protect against 
failure or malfunction of the 
actuators. 

IMPORTANT :

 Utiliser ce M9106-AGx-2N0x Series 

Actuator uniquement pour 
commander des équipements dans 
des conditions normales de 
fonctionnement. Lorsqu'une 
défaillance ou un dysfonctionnement 
du actuators risque de provoquer des 
blessures ou d'endommager 
l'équipement contrôlé ou un autre 
équipement, la conception du 
système de contrôle doit intégrer des 
dispositifs de protection 
supplémentaires. Veiller dans ce cas 
à intégrer de façon permanente 
d'autres dispositifs, tels que des 
systèmes de supervision ou d'alarme, 
ou des dispositifs de sécurité ou de 
limitation, ayant une fonction 
d'avertissement ou de protection en 
cas de défaillance ou de 
dysfonctionnement du actuators. 

The actuator may be mounted in any convenient 
orientation. When installing the DPT-2015 Differential 
Pressure Transmitter on the actuator, mount it so the 
tubing connecting the flow pick-up device to the 
DPT-2015 creates a moisture trap. This will prevent 
condensation from entering the sensor. 

No extra mounting brackets, linkage, or couplers are 
required for standard mounting, but wiring terminals 
must be accessible and protected from moisture and 
corrosive fumes. 

Parts Included 

 

M9106-AGx-2N0x Actuator 

 

CBL-2000-1 Wiring Harness and DPT-2015-0 
Differential Pressure Transmitter (included with the 
M9106-AGS-2N02) 

 

No. 10 self-drilling sheet metal screw 

Special Tools Needed 

 

5/16 in. (8 mm) square socket 

 

3/8 in. (10 mm) 12-point socket 

 

drill with a 5/16 in. hex nut driver 

 

digital voltmeter (for troubleshooting the 
transmitter) 

Mounting 

To mount the actuator to a damper: 

1.  Position the actuator on the damper shaft so the 

damper shaft protrudes through the actuator 
coupler as shown in Figure 1. 

Damper

Damper

Shaft

 

Figure 1: Mounting on the Damper Shaft  

2.  Make sure the actuator is in the desired mounting 

position, parallel to the mounting surface as shown 
in Figure 2. 

©  2014 Johnson Controls, Inc.

 

1

 

  Part No. 34-636-1077, Rev. B 

www.johnsoncontrols.com 

Содержание M9106-AG 2N0 Series

Страница 1: ...e sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du actuators The actuator may be mounted in any convenient orientation When installing the DPT 2015 Differential Pressure Transmitter on the actuator mount it so the tubing connecting the flow pick up device to the DPT 2015 creates a moisture trap This will prevent condensa...

Страница 2: ...aft as shown in Figure 4 Figure 4 Damper Position Icons To set the actuator stroke proceed as follows 1 Grasp the damper shaft firmly with pliers and rotate the damper fully closed See Figure 5 Damper Shaft CCW to Close CW to Close Damper Blade Damper Figure 5 Damper Rotation 2 Press and hold the gear release lever shown in Figure 2 and rotate the actuator coupler to the fully closed position 3 Ma...

Страница 3: ...upler to the minimum rotation position for the minimum ventilation flow required 2 Release the gear release lever 3 Use a Phillips screwdriver to loosen the end stop set screw that is closest to the stop gear Move the end stop set screw in its slot until it is tight against the stop gear See Figure 6 IMPORTANT Do not remove the end stop set screws as this could interfere with the actuator s operat...

Страница 4: ...the end of rotation stall The 20 in 0 5 m CBL 2000 1 Wiring Harness accepted by Underwriters Laboratories Inc UL for plenum use is pre wired with the M9106 AGS 2N02 or may be ordered separately The plenum rated 20 in 0 5 m CBL 2000 2 and 72 in 1 8 m CBL 2000 3 Wiring Harnesses are also available See Table 1 Setup and Adjustments Air Pressure M9106 AGS 2N02 The flow pickup device provided with the ...

Страница 5: ...power is applied Verify that the damper fully opens and closes using the gear release lever on the actuator Check that the actuator stroke is set for the desired application DPT 2015 The DPT 2015 must be auto zeroed by a Johnson Controls VAV controller If the DPT 2015 is not operating properly Verify that the air lines on the DPT 2015 are connected to their respective high and low ports with no ki...

Страница 6: ...itions M9106 AGA 2N0x 32 to 125 F 0 to 52 C 90 RH maximum non condensing M9106 AGS 2N02 32 to 125 F 0 to 52 C 90 RH maximum non condensing 60 to 100 F 16 to 38 C 90 RH maximum non condensing For DPT rated accuracy see DPT 2015 Differential Pressure Transmitter for VAV Box Applications Installation Instructions Part No 24 7547 18 Ambient Storage Conditions 20 to 150 F 29 to 66 C 90 RH maximum non c...

Отзывы: