LX Series Unit Ventilator Controller User's Guide
91
nviOutdoorTemp
This network variable input receives the outdoor air temperature.
Type: SNVT_temp_p (105)
nviReturnTemp
Transmits return temperature from a network device to the UV. Network values
have priority over local sensor values.
nviSetPoint
Use this network variable input to change the temperature setpoints for the
occupied and standby modes via the network. The individual heating and cooling
setpoints for the occupied and standby modes are calculated from nviSetPoint. See
the
The Effect of nviSetPoint on the Active Setpoints
Type: SNVT_temp_p (105)
nviSetPointOffset
Use this network variable input to shift the temperature setpoint by adding the
value of nviSetpointOffset to the current setpoint. This network variable operates
only on occupied and standby setpoints and does not affect the unoccupied
setpoint. See the
The Effect of nviSetPoint on the Active Setpoints
section.
Type: SNVT_temp_p (105)
nviShedding
Use this network variable input to reduce the Unit Ventilator Controller power
consumption. For example, if nviShedding is set to 25%, then heating and cooling
do not exceed 75%.
Type: SNVT_lev_percent (81)
nviSlave
Use this network variable input to force the Unit Ventilator Controller to follow the
demands of another unit ventilation controller. It is normally bound to the
nvoUnitStatus of the other Unit Ventilator Controller.
Type: SNVT_hvac_status (112)
nviSpaceEnth
Transmits space enthalpy from a network device to the UV. Network values have
priority over local sensor values.
Type: SNVT_enthalpy (153)