Operating Limitations
TABLE 4 -
OPERATING LIMITATIONS — LSWU025-LSWU105
MINIMUM
MAXIMUM
Entering Air DX Coil-Dry Bulb
75.0°F
85.0°F
Entering Air DX Coil-Wet Bulb
62.0°F
72.0°F
Condenser Water Flow
2.5 GPM/Ton
3.0 GPM/Ton
Entering Cond. Water Temp with Economizer
40.0°F
90.0°F
Entering Cond. Water Temp with Condenser
Water Control Valve
40.0°F
90.0°F
Entering Cond. Water Temp w/o Condenser
Water Control Valve
60.0°F
90.0°F
Steam Heat-Steam Pressure
5 psig
15 psig
Hot Water Heat Entering Water Temp
140.0°F
160.0°F