Technical Specificaions

Electrical:

Operating Voltage: 

24 V (via P-UIM)

Quiescent Current: 

25 mA

Alarm Current: 

 

80 mA (max)

Beam Length: 

 

2 to 30 metres

Mechanical:

Dimensions:  

 

W165  x  H125  x  D165 mm

Weight:   

 

0.96 kg

Material:  

 

Noryll GTX Grade 810

Environmental:

Operating Temperature: 

-10 to +55°C

Housing Protection: 

IP65  

BASEEFA 9 Cert:   

BAS 02 ATEX 2313X  

   

 

 

EEx ib IIB T5

SIRA Cert 

 

IECEx SIR 14.0009X 

 

 

   

 

 

II2 G Ex ib IIB T5 Gb

Accesories

Flying Lead: 

 

01-33-14

Reflector Type 1:   

01-33-05

Reflector Type 2:   

01-33-10

Reflector Type 3:   

01-33-11

P-UIM:   

 

01-33-22

0-20 mA Adapter:  

01-33-22A

Heavy Duty M/B:  

01-33-24

U-Bracket: 

 

01-33-12

IR Alignment Tool:  

01-33-21

IR Test Film:  

 

01-33-26

Detector Monitoring Characteristics

Detector Life Compensation Characteristics

Detector Life Compensation Characteristics

PSF330JC_Time_Saver_Mount.indd   4

27/08/2019   17:23:14

Содержание IR6003/7

Страница 1: ...or beam The detector has been developed for use in enclosed oil rig well head areas generator rooms and turbine enclosures The detector automatically compensates for contamination of the detector lenses and signals when a point is reached where further deterioration cannot be tolerated and the lense requires cleaning Two levels of alarm status are provided A low level alarm and a high level alarm ...

Страница 2: ... Block If the level of obscuration increases suddenly to a high level of loss a beam blocked status will be latched and if the level is maintained for 60 seconds Beam Blocked will be reported LED flashes ON for 2 seconds If the beam blocked level of obscuration clears for more than a few seconds during the 60 second period monitoring period the detector will return to its normal operating state Du...

Страница 3: ...dicator is lit steady Now remove the obstruction from the detectors path 5 Initiate a short reset and check that the P UIM returns to the status detailed in step 1 6 Initiate a long reset with the beam path blocked and check that the detector indicates a Life Fault LED is lit steady The P UIM Life indicator is lit steady Now remove the obstruction for the detectors path 7 Initiate a long reset and...

Страница 4: ...tection IP65 BASEEFA 9 Cert BAS 02 ATEX 2313X EEx ib IIB T5 SIRA Cert IECEx SIR 14 0009X II2 G Ex ib IIB T5 Gb Accesories Flying Lead 01 33 14 Reflector Type 1 01 33 05 Reflector Type 2 01 33 10 Reflector Type 3 01 33 11 P UIM 01 33 22 0 20 mA Adapter 01 33 22A Heavy Duty M B 01 33 24 U Bracket 01 33 12 IR Alignment Tool 01 33 21 IR Test Film 01 33 26 Detector Monitoring Characteristics Detector L...

Страница 5: ...ted to mechanical and thermal stress or where it may be attacked by existing or foreseeable aggressive substances Number Name General Count Number Name General Count 1 Shell 150 19 Technip Mar 5 2 BP 250 20 Det tronics 30 3 How 50 21 HESS 4 4 Total 20 22 Debyl Ltd 6 5 BNFL 8 23 North Sea 50 6 Micropack 10 24 STAT Oil 15 7 Maersk 10 25 Dutch Navy 16 8 Silvertech 30 26 Prudhoe Bay 10 9 ICS 60 27 FPS...

Страница 6: ...ut notice PSF303JC Issue 1 08 19 www johnsoncontrols co uk There are many other companies who integrate our oil mist detection equipment into there safety systems These can range from Heavy Industrial Areas e g Engine Rooms Hazardous Areas Warehouses Marine Applications Oil Rigs FSPO s e g Shell BONGA Turbines Hyraulic Power Units Plus many more PSF330JC_Time_Saver_Mount indd 6 27 08 2019 17 23 14...