Johnson Controls IOM2721 Скачать руководство пользователя страница 13

Figure 11: End-of-Line switch positions

To set the EOL switch on an expansion module, complete

the following steps:

1. Determine the physical location of the

expansion module on the SA or FC bus.

2. Determine if the expansion module must be

set as a terminating device on the bus.

Note: 

The EOL termination rules for SA

buses and FC buses are different. Refer to

the 

MS/TP Communications Bus Technical

Bulletin (LIT-12011034)

 for detailed information

regarding EOL termination rules and EOL

switch settings on SA and FC buses.

3. If the expansion module is a terminating

device on the FC bus, set the EOL switch

to ON. If the expansion module is not a

terminating device on the bus, set the EOL

switch to OFF.

When an expansion module is connected to

power with its EOL switch set to ON, the amber

EOL LED on the expansion module cover is lit.

UI current loop jumpers

The UI current loop fail-safe jumpers are on the circuit

board under the expansion module cover near the UI

terminals. When a UI is defined (in the system software)

as a 4 to 20 mA Analog Input and the UI’s current loop

jumper is in the Disabled (default) position (Figure 12), the

4 to 20 mA current loop circuit opens whenever power to

the expansion module is interrupted or off.

Figure 12: Current loop jumper positions

Setting the current loop jumper to the Enabled position

(Figure 12) connects an internal 100 ohm resistor across

the UI terminals, which maintains the 4 to 20 mA current

loop circuit even when power to the expansion module is

interrupted or off.

Important: 

Current Loop jumpers must be in the

Disabled (default) position for all UIs that are not set

up to operate as 4 to 20 mA analog inputs.

Table 7: UI Inputs and Jumper Labels

Universal Input Label

Jumper Label on Circuit Board

Label

IN1

J20

IN2

J21

IN3

J22

IN4

J24

IN5

J25

IN6

J26

IN7

J27

IN8

J28

Commissioning

You commission expansion modules with Controller

Configuration Tool (CCT) software, using a Bluetooth

Wireless Commissioning Converter (BTCVT), through

Mobile Access Portal (MAP) Gateway at version 4.2 or

above, or in BACnet router mode when connected to a

Supervisory Controller. Refer to the 

Controller Tool Help

(LIT-12011147)

 for detailed information on commissioning

expansion modules.

Note: 

The MAP Gateway serves as a replacement for

the BTCVT, which is no longer available for purchase,

but continues to be supported.

Troubleshooting

Observe the Status LEDs on the front of the expansion

module. Table 8 provides LED status indicator information

for troubleshooting the expansion module.

IOM2721 Input/Output Module Installation Guide

13

Содержание IOM2721

Страница 1: ...equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operatio...

Страница 2: ...applications Use shims or washers to mount the expansion module securely and evenly on the mounting surface Mount the expansion module in an area free of corrosive vapors and observe the Ambient Cond...

Страница 3: ...or surface in a proper mount position and mark the hole locations through the mounting clips 3 Drill holes in the wall or surface at the marked locations and insert appropriate wall anchors in the ho...

Страница 4: ...terminal blocks are mounted on the top of the expansion module SA FC bus terminal block An IOM can be connected to a Sensor Actuator SA bus or a Field Controller FC bus but not to both buses simultan...

Страница 5: ...us port RJ 12 modular jack on the front of the expansion module 2 Ensure that the expansion module s device address DIP switches are set to the correct device address See 3 Set DIP switch 128 to ON wh...

Страница 6: ...inum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 10k JCI Type II 2 252k Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1...

Страница 7: ...re See Figure 8 to determine cable length Use twisted wire cable N A Maximum cable length versus load current Use the following figure to estimate the maximum cable length relative to the wire size an...

Страница 8: ...upply 15 VDC The SA bus supervisor supplies 15 VDC to devices on the SA bus requiring power FC Bus 0 6 mm 22 AWG stranded 3 wire twisted shielded cable required SA Bus 0 6 mm 22 AWG stranded 4 wire 2...

Страница 9: ...applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Interna...

Страница 10: ...grams Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI 0 10 VDC Output to Actuator External Source AO 0 10 VDC Out...

Страница 11: ...pansion module on the bus You set an expansion module s device address by setting the positions of the switches on the DIP switch block at the top of the expansion module Device addresses 4 through 12...

Страница 12: ...e on Descriptions 0 Switch 128 Off Reserved for FC Bus Supervisory Controller not for use on controllers or expansion modules 1 3 Switch 128 Off Reserved for peripheral devices not for use on controll...

Страница 13: ...er to the expansion module is interrupted or off Figure 12 Current loop jumper positions Setting the current loop jumper to the Enabled position Figure 12 connects an internal 100 ohm resistor across...

Страница 14: ...tartup in progress not ready for normal operation SA FC BUS Green Blink 2 Hz Blink 2 Hz Data Transmission normal communication Off Steady No Data Transmission N A auto baud not supported On Steady Com...

Страница 15: ...k of 10 Note These terminal blocks can be used as replacement parts if keeping consistent terminal block colors is important AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of...

Страница 16: ...w Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module Housing Enclosure material ABS and...

Страница 17: ...C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 5...

Страница 18: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Отзывы: