IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
135
Type Codes for Input Devices
Type Codes
G.3.3 Type Codes for Monitor Modules
Following is a list of monitor module Type Codes, which can be used to change the function of a
monitor module point.
Table G.2 Type Codes for Monitor Modules
NOTE:
Do not assign Releasing Type Codes to Panel Circuit module points
.
Point Characteristics
Type Code
Point Type
Latching
(Y=yes
N=no)
Activates
CBE
Device Function
MONITOR
fire alarm
Y
Y
Alarm-monitoring device
NC MONITOR
fire alarm
Y
Y
Alarm monitoring device, where an open circuit=active. SLC only.
PULL STATION
fire alarm
Y
Y
Manual fire-alarm-activating device
SMOKE CONVEN
fire alarm
Y
Y
Indicates activation of a conventional smoke detector. An
M302MJ must be used
for alarm verification of a two-wire conventional detector.
SMOKE DETECT
fire alarm
Y
Y
Indicates activation of a conventional smoke detector. An
M302MJ must be used
for alarm verification of a two-wire conventional detector
WATERFLOW
fire alarm
Y
Y
Monitor for waterflow alarm switch
WATERFLOW S
supervisory
Y
Y
Indicates supervisory condition for activated waterflow switch
ACCESS MONTR
non-alarm security
N
Y
Used for monitoring building access
AREA MONITOR
security
Y
Y
Monitors building access
AUDIO SYSTEM
trouble
N
N
Used for monitoring audio equipment (use trouble zones for activations)
EQUIP MONITR
non-alarm security
N
Y
Used for monitoring equipment
SECURITY L
security
Y
Y
Indicates activation of security alarm
LATCH SUPERV
supervisory
Y
Y
Indicates latching supervisory condition
NC SUP L
supervisory
Y
Y
Indicates latching supervisory conditon, where an open circuit=active. SLC only.
TRACK SUPERV
supervisory
N
Y
Monitors for waterflow tamper switches for alarm points
NC SUP T
supervisory
N
Y
Indicates tracking supervisory conditon, where an open circuit=active. SLC only.
SPRINKLR SYS
supervisory
Y
Y
Monitors a waterflow device
SYS MONITOR
security
Y
Y
Monitors equipment security
TAMPER
supervisory
Y
Y
Indicates activation of tamper switch
ACK SWITCH
non-alarm
N
N
Emulates panel Acknowledge switch
ALLCALL PAGE
non-alarm
N
Y
Emulates AMG-1 All-call switch and telephone page
DRILL SWITCH
non-alarm
*
N
N
Emulates panel Drill switch, activates silenceable fire outputs
EVACUATE SWITCH
non-alarm*
N
N
Emulates panel Drill Switch, activates silenceable fire outputs
FIRE CONTROL
non-alarm
N
Y
Monitors non-fire activations
NON FIRE
non-alarm
N
Y
Monitors non-fire activations
NC NON FIRE
non-alarm
N
Y
Monitors non-fire activations, where an open circuit=active. SLC only.
PAS INHIBIT
non-alarm
N
N
Inhibits Positive Alarm Sequence
POWER MONITR
trouble
†
N
N
Monitors main and auxiliary power supplies (use trouble zones for activations)
RESET SWITCH
non-alarm
N
N
Emulates keypad Reset switch
SIL SWITCH
non alarm
N
N
Emulates keypad Signal Silence switch
TELE PAGE
non-alarm
N
Y
Emulates Page Button on FFT-7. Allows remote paging to a fire area
TROUBLE MON
trouble
N
N
Monitors trouble inputs (use trouble zones for activations)
Blank
fire alarm
Y
Y
Monitors for a device with no description
HEAT DETECT
fire alarm
Y
Y
Monitors for conventional heat detector
RF MON MODUL
fire alarm
Y
Y
Wireless alarm-monitoring device
RF PULL STA
fire alarm
Y
Y
Wireless manual fire-alarm-activating device
RF SUPERVSRY
supervisory
N
Y
Wireless supervisory-monitoring device
ABORT SWITCH
non-alarm
N
Y
Provides an abort function through a monitor module (connected to a UL-listed
abort station) for a releasing zone.
MAN RELEASE
fire alarm
‡
Y
Y
Provides a manual release through a monitor module (connected to a UL-listed
pull station) for a releasing zone
MAN REL DELAY
fire alarm†
Y
Y
Provides a manual release with a 10-second delay through a monitor module
(connected to a UL-listed pull station) for a releasing zone
SECOND SHOT
fire alarm†
Y
Y
Provides a second manual release through a monitor module (connected to a UL-
listed pull station) for a releasing zone
*
Local Mode treats this point as a fire alarm point.
† Does not participate in Local Mode
‡ Local Mode activation of NACs only. No releasing.
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...