FAULTS AND SYSTEM EVENTS
TABLE 11:
Float Switch Settings (AHV, AVC, MVC, AVV,
and 2-Stage Variable Speed ECM Furnace)
Name
Default
Setting
Available
Settings
Explanation
Float Switch
Disabled
Enabled (Open),
Enabled (Closed),
Disabled
Allows you to activate an optional
condensate float switch (S1-ACS2).
If a normally closed (NC) switch is
used, choose Enabled (Open). If a
normally open (NO) switch is used,
choose Enabled (Closed).
TABLE 12:
Auxiliary Settings (2-Stage Variable Speed ECM Furnace)
Name
Default
Setting
Available
Settings
Explanation
AUX Switch
Disabled
Enabled (Open),
Enabled (Closed),
Disabled
Allows you to activate the optional
dry relay contact that is supplied by
the utility company
AUX
Switch: Heat
Stage
Down
Stage Down or
Shut Off Comp
Allows you to determine the equip-
ment functionality when the AUX
switch is activated
AUX
Switch: Cool
Stage
Down
Stage Down or
Shut Off Comp
Allows you to determine the equip-
ment functionality when the AUX
switch is activated
FIGURE 32:
Fault Display Settings
A1232-001
SYSTEM SETTINGS
EFFICIENCY FAULTS
DISABLED
WARNING FAULTS
DISABLED
STATUS FAULTS
DISABLED