5407934-UIM-C-1119
Johnson Controls Ducted Systems
39
Smart
Recovery
Yes
Yes or No
Enables or disables smart recovery.
Smart recovery is used in Programma-
ble mode. The controller initiates equip-
ment operation, if required before the
start time of the program schedule day
part. This is done to reach the desired
temperature setpoint of the program
schedule event at the time the event
occurs, rather than after.
Fan On
with W
No
Yes or No
Enables or disables Fan On with W.
When enabled, this supplies a fan out-
put demand as soon as a W1 or W2
output demand is active
Indoor
Temp
Offset
0°
-5°, -4°, -3°, -2°,
-1°, 0°,1°, 2°, 3°,
4°, 5°
Allows you to adjust the displayed tem-
perature to offset it from the measured
temperature in the thermostat
Indoor Hum
Offset
0%
-5%, -4%, -3%,
-2%, -1%, 0%, 1%,
2%, 3%, 4%, 5%
Allows you to adjust the displayed
humidity to offset it from the measured
humidity in the thermostat
Auto
Change-
over
30 MIN
5 MIN, 10 MIN,
15 MIN, 20 MIN,
25 MIN, 30 MIN
Sets the minimum time that must elapse
between switches from heat-to-cool to
cool-to-heat demands when operating
in Auto mode
Remote
Sensor
None
None, Indoor, Out-
door, Average
If you opt to use the remote sensor, you
can set it to sense the indoor room tem-
perature or the outdoor temperature. If
you select the Average option, the
onboard temperature sensor and the
connected sensor are averaged to
determine the room temperature on the
thermostat.
Cool
Lockout
OFF
OFF, 55°F, 60°F,
65°F, 70°F, 75°F,
80°F
When enabled, this setting prevents
cooling operation when the outdoor
temperature drops below the selected
temperature.
Time
Between
Fuel Types
15 MIN
10 MIN, 15 MIN,
20 MIN, 25 MIN
Sets the minimum time limit between
the switch from one fuel type to another
TABLE 7:
General System Settings (Continued)
Name
Default
Setting
Available
Settings
Explanation