Reporting
[307] Zone Reporting
Zone alarms, tampers and faults are transmitted to the central station using automatic contact ID
or SIA formats. Reporting can be toggled on or off by zone using toggle options 1-6 in subsections
001-128.
.
[308] Event Reporting
System events are transmitted to the central station using automatic contact ID or SIA formats.
Reporting can be disabled by toggle options, programmable in the following sub-sections.
for event code descriptions.
[001] Miscellaneous Alarm 1
The reporting codes in this section are sent to the Alarm & Restore call direction group.
1 - Duress Alarm
Sent when a duress code is used to perform any function on the system.
2 - Opening After Alarm
Sent during disarming if an alarm occurred during the previous armed period.
3 - Recent Closing Alarm
Sent if an alarm occurs within 2 minutes of the exit time expiration (for the first alarm only). Zone
alarm transmission delays do not affect this reporting code.
4/5 – Zone Expander Supervisory Alarm/ Restore
Sent when the system loses communication with the following modules:
• Zone Expander Module
• Keypad with an on-board I/O configured as a zone
This reporting code is independent of the general system supervisory code sent to the Alarms and
Restores call direction group.
6 - Burglary Verified
When using Cross Zoning, this reporting code is sent when two crossed zones go into alarm during
the cross zone timer.
When using Police Code, this reporting code is sent when any two zones that have the burglary
verification attribute enabled go into alarm. Arming the system resets the zone alarm count for
police code.
7 - Burglary Not Verified
When using Cross Zoning, this reporting code is sent if the cross zone timer is initiated by the first
cross zone alarm, but is not verified by a second alarm before the timer expires.
8 - Alarm Cancel
Sent when a valid access code is entered during the communications cancel window. The central
station acknowledges cancellation by providing a keypad ringback.
[002] Miscellaneous Alarm 2
1 - Holdup Verified
Sent when the configured Holdup verified conditions have been met.
131
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference