Johnson Controls HE-6800 Series Скачать руководство пользователя страница 2

• away from steam or water pipes, warm air stacks,

unconditioned areas (no heating and no cooling), or

sources of electrical interference

Note: 

The HE-6800 Series Humidity Transmitter is

shock and vibration resistant; however, be careful

not to drop the unit or mount it where it could be

exposed to excessive vibration.
The following ambient operating conditions apply:

• Temperature: 32 to 131°F (0 to 55°C)

• Humidity: 10 to 95% RH, noncondensing; 86°F (30°C)

maximum dew point

To mount the transmitter to the wall:

1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson

Controls T-4000-119 Allen-Head Adjustment Tool to

loosen the security screw on the top of the unit.

2. Insert a blade screwdriver into the slot next to the

security screw location, and then carefully pry the

top edge of the transmitter assembly away from its

mounting base and remove.

Important: 

Do not remove the Printed Circuit

Board (PCB). Removing the PCB voids the

product warranty.

3. Pull out approximately 6 in. (152 mm) of cable from

the wall, and insert the cable through the hole in

the mounting base.

4. Align the mounting base on the wall, and use the

base as a template to mark the location of the two

mounting holes on the surface.

Note: 

Make sure the mounting base is

positioned correctly with the security screw

located on the top edge of the base.

5. Secure the mounting base to the wall using the

appropriate mounting hardware (field furnished).

6. Set DIP switches for the desired operation. See the

Internal Wiring Diagrams

 and 

Setup and Adjustments

sections for additional information.

7. Align the tabs on the bottom edge of the mounting

base with the slots on the bottom edge of the

transmitter assembly, and rotate the assembly onto

its mounting base.

Note: 

Make sure the terminal block pins align

with the holes in the terminal block.

8. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson

Controls T-4000-119 Allen-Head Adjustment Tool to

tighten the security screw and fasten the network

transmitter assembly to the mounting base.

Wiring

 NOTICE

Risk of Property Damage

Do not apply power to the system before checking

all wiring connections. Short circuited or improperly

connected wires may result in permanent damage to

the equipment.

 NOTICE

Risque de dégâts matériels

Ne pas mettre le système sous tension avant

d'avoir vérifié tous les raccords de câblage. Des

fils formant un court-circuit ou connectés de façon

incorrecte risquent d'endommager irrémédiablement

l'équipement.

Important: 

Use copper conductors only. Make all

wiring connections in accordance with local, national,

and regional regulations.

Keep wires as short as possible to minimize sensor error.

Each 250 ft (76 m) run of 18 AWG wire or 50 ft (15 m) of

24 AWG wire creates 1F° (0.56C°) error for a nickel sensor

or 1.5F° (0.83C°) error for a platinum sensor due to wire

resistance.
To maintain less than 1F° (0.56C°) error for nickel or 1.5F

° (0.83C°) error for platinum, hold the total resistance of

all sensor wiring below 3 ohm. When wiring the HE-6800,

do not run low voltage wiring in the same conduit as

line voltage wiring or other conductors supplying highly

inductive loads.

Internal Wiring Diagrams

Internal wiring diagrams are shown in Figure 1 and Figure

2. Terminal block designations are shown in Figure 3.

The terminals are identified in Table 1. See the 

Setup and

Adjustments

 section and Figure 4 for an explanation of

the LED and Pushbutton (PB) modes. Make connections

pairing the following wires:
• sensor (Terminal 1 and Terminal 2)

• setpoint (Terminal 3 and Terminal 4)

• Zone Bus and Common (COM)(Terminals 6 and 7)
Shielding is not required. If used, follow the system

controller’s recommendations for grounding the shield.

Note: 

The Manual Override PB does not respond

when the DIP switch positions are all down (LED

mode NO PB, as shown in Figure 2 and Figure 4).

Manual Override is selected for either Terminals 1 and 6 to

short sensor (with DIP switch set for LED Off) or Terminal

HE-6800 Series Humidity Transmitters with Temperature Sensor Installation Guide

2

Содержание HE-6800 Series

Страница 1: ...designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy...

Страница 2: ...l to tighten the security screw and fasten the network transmitter assembly to the mounting base Wiring NOTICE Risk of Property Damage Do not apply power to the system before checking all wiring conne...

Страница 3: ...1 The 15 VDC power supply is used only when an HE 6800 Series Humidity Transmitter is connected to a VMA Controller Setup and Adjustments Controller Configuration DIP Switch and LED Mode A DIP switch...

Страница 4: ...r PB LED Switch positions are down up and down The LED remains off at all times ON LED Senso r PB Switch positions are factory set up down and up The controller determines the LED mode NO PB Senso r...

Страница 5: ...vice keep the air vents clean and free from dust or obstruction If an HE 6800 Series Humidity Transmitter fails to operate within its specifications replace the unit For a replacement transmitter cont...

Страница 6: ...Momentary Pushbutton DIP Switch Selectable LED Green LED Indicates Three Modes of Operation VMA12 and VMA14 Series Controllers Only Ambient Operating Conditions 32 to 131 F 0 to 55 C 10 to 95 RH Nonc...

Страница 7: ...s com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEM...

Страница 8: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Отзывы: