Johnson Controls HE-6800 Series Скачать руководство пользователя страница 1

HE-6800 Series Humidity Transmitters with

Temperature Sensor Installation Guide

Applications

The HE-6800 Series Humidity Transmitters with

Temperature Sensor provide both humidity and

temperature sensing in room wall-mount applications.

The transmitter offers local warmer/cooler temperature

setpoint adjustment and temporary occupancy override.

The humidity sensor provides Relative Humidity (RH)

accuracy of ±2% or ±3% RH and measures RH over the

entire range of 0 to 100%.
A warmer/cooler dial is included on certain models for

minor temperature adjustments from the setpoint. All

models feature an occupancy override button that allows

the user to override time-of-day scheduling when the

space is occupied outside of the normal occupied hours

schedule. The transmitter also includes DIP switches to

enable or disable override andLight-Emitting Diode (LED)

functions. In addition, all models feature a user-selectable

0 to 5 VDC or 0 to 10 VDC humidity output switch, and a

power supply selection switch.
The HE-6800 Series Humidity Transmitters include screw

terminal block terminations that provide flexibility for field

wiring. All models include a 6-pin modular jack access port

for connecting accessories to the Zone Bus. This feature

allows a technician to commission or service the controller

via the transmitter.

Important: 

Use the HE-6800 Series Humidity

Transmitter only to provide input to equipment

under normal operating conditions. Where failure

or malfunction of the transmitter could lead

to personal injury or property damage to the

controlled equipment or other property, additional

precautions must be designed into the control

system. Incorporate and maintain other devices,

such as supervisory or alarm systems or safety or

limit controls, intended to warn of or protect against

failure or malfunction of the transmitter. Approved

March 14, 2003.

North American emissions compliance

United States

This equipment has been tested and found to comply with

the limits for a Class A digital device pursuant to Part 15

of the FCC Rules. These limits are designed to provide

reasonable protection against harmful interference when

this equipment is operated in a commercial environment.

This equipment generates, uses, and can radiate radio

frequency energy and, if not installed and used in

accordance with the instruction manual, may cause

harmful interference to radio communications. Operation

of this equipment in a residential area may cause harmful

interference, in which case the users will be required to

correct the interference at their own expense.

Warning (Part 15.21)

Changes or modifications not expressly approved by the

party responsible for compliance could void the user’s

authority to operate the equipment.

Canada

This Class (A) digital apparatus meets all the requirements

of the Canadian Interference-Causing Equipment

Regulations.
Cet appareil numérique de la Classe (A) respecte toutes

les exigences du Règlement sur le matériel brouilleur du

Canada.

Industry Canada Statement(s)

This device complies with Industry Canada licence-exempt

RSS standard(s). Operation is subject to the following two

conditions:

1.  This device may not cause interference, and
2.  This device must accept any interference, including

interference that may cause undesired operation of

the device.

Le présent appareil est conforme aux CNR d'Industrie

Canada applicables aux appareils radio exempts de

licence. L'exploitation est autorisée aux deux conditions

suivantes :

1.  L'appareil ne doit pas produire de brouillage, et
2.  L'utilisateur de l'appareil doit accepter tout

brouillage radioélectrique subi, même si le

brouillage est susceptible d'en compromettre le

fonctionnement.

Installation

Special Tools Needed

A 1/16 in. (1.5 mm) Allen wrench or a Johnson Controls

®

T-4000-119 Allen-Head Adjustment Tool is required during

installation.

Accessory

Installing the HE-6800 Series Humidity Transmitter on

a wallbox requires accessory NS-WALLPLATE-0, ordered

separately.

Mounting

About this task:

Locate the HE-6800 Series Humidity Transmitter:
• on a partitioning interior wall, and approximately

5 ft (1.5 m) above the floor in a location of average

temperature

• away from direct sunlight, radiant heat, outside walls,

behind doors, air discharge grills, stairwells, or outside

doors

*241040928F*

Part No. 24-10409-28   Rev. F

2021-04-02

HE-68xx-xN00WS

Содержание HE-6800 Series

Страница 1: ...designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy...

Страница 2: ...l to tighten the security screw and fasten the network transmitter assembly to the mounting base Wiring NOTICE Risk of Property Damage Do not apply power to the system before checking all wiring conne...

Страница 3: ...1 The 15 VDC power supply is used only when an HE 6800 Series Humidity Transmitter is connected to a VMA Controller Setup and Adjustments Controller Configuration DIP Switch and LED Mode A DIP switch...

Страница 4: ...r PB LED Switch positions are down up and down The LED remains off at all times ON LED Senso r PB Switch positions are factory set up down and up The controller determines the LED mode NO PB Senso r...

Страница 5: ...vice keep the air vents clean and free from dust or obstruction If an HE 6800 Series Humidity Transmitter fails to operate within its specifications replace the unit For a replacement transmitter cont...

Страница 6: ...Momentary Pushbutton DIP Switch Selectable LED Green LED Indicates Three Modes of Operation VMA12 and VMA14 Series Controllers Only Ambient Operating Conditions 32 to 131 F 0 to 55 C 10 to 95 RH Nonc...

Страница 7: ...s com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEM...

Страница 8: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Отзывы: