5.7 Installation of Wired Controller (Optional Parts)
Refer to “Installation & Maintenance Manual” of optional wired controller.
5.8 Setting of Wired Controller and Remote Sensor
When the function of Indoor Temperature Control is set, a remote thermistor built in optional wired controller
or remote sensor is necessary. Determine the installation location of the wired controller and remote sensor
according to below.
Do not install the wired controller and remote sensor in following places.
- Places where the average temperature of indoor rooms can not be detected.
- Places where are directly subject to the sunlight.
- Places where is near heat sources.
3ODFHVZKHUHDUHVXEMHFWWRDLUGLUHFWO\ÀRZVIURPDLURXWOHW
- Places where are subject to the outdoor air by opening door etc.
Determine how to detect indoor temperature as follows, paying attention the installation location.
(1) Remote Sensor
Connect remote sensor to this unit. The setting is not necessary.
(2) Remote Thermistor Built in Optional Wired Controller
&RQQHFWRSWLRQDOZLUHGFRQWUROOHUWRWKLVXQLW6HOHFW³)XQFWLRQ6HOHFWLRQ´PHQXE\RSWLRQDOZLUHG
controller and follow as shown below.
Item Code
2SWLRQDO)XQFWLRQ
Setting Condition
C8
Thermistor of Wired Controller
01
(3) Combination of Remote Sensor and Remote Thermistor Built in Optional Wired Controller
&RQQHFWUHPRWHVHQVRUDQGRSWLRQDOZLUHGFRQWUROOHUWRWKLVXQLW6HOHFW³)XQFWLRQ6HOHFWLRQ´PHQXE\
optional wired controller and follow as shown below.
Item Code
2SWLRQDO)XQFWLRQ
Setting Condition
C8
Thermistor of Wired Controller
02
NOTES:
1. When the function of Indoor temperature control is set and the operation without optional wired
controller or remote sensor is tried, alarm “16” and “17” will be indicated and operation will be not available.
(Even if the function of Outlet Air Temperature Control is set without them, alarms are not indicated)
2. Refer to “Installation and Maintenance Manual” of the optional wired controller for details.
It works by calculating the average of the two different
temperatures between the remote thermistor built in
optional wired controller and remote sensor.