P00860Q-rev.2
13
)LJXUH'XFW&RQQHFWLRQ([DPSOH
Outdoor Air
(with Air Filter)
Damper for
Adjusting Air Volume
Silencer
Silencer
Canvas Duct
Canvas Duct
Thermal
Insulation
Damper for
Adjusting Air Volume
Air Outlet
Level
Ceiling
DOAS
Unit
Service Access Panel
(17-11/16 inches x 17-11/16 inches)
An alternative opening
(12) The DOAS unit is designed to process outdoor air intake and should not be used as a standard indoor
unit. If the internal load is higher, additional indoor units need to be added.
(13) The DOAS unit is designed to intake outdoor air only.
Indoor air is not recommended to be returned to the DOAS unit.
(14) Install the ducts with the its air inlet being a lower level than the indoor unit to protect the unit from rain.
Voltage
Model
Static Pressure
in.W.G.(Pa)
208V
(H,Y)DOA096B21S
1.06 (265)
230V
1.24 (310)
5.6 Installation of Remote Sensor
(1) Installing Remote Sensor on Wall
Fixing Screw
Sensor Box
1-1/4
(32)
Unit: inch (mm)
2-M4
Dimension for Fixing Remote Sensor on Wall
1-1/4
(32)
- Cut out the wiring holes in the sensor box and lead the wires for the sensor through the holes.
- Secure the sensor box on the wall with the two screws.
- If the sensor box cannot be secured on the wall with the screws, use double-sided tapes.
(2) Concealing Wires inside Wall
0DNHWKHKROHVIRUVHFXULQJWKHVHQVRUER[RQWKHPHWDOSODWH¿HOGVXSSOLHGDVVKRZQLQWKH¿JXUH
on the right, and secure the sensor box to the plate with screws.
- Make sure that the hole for air intake on the sensor box remains unobstructed.
Sensor Box Cover
Switch Box
(Field-Supplied)
Unit: inch [mm]
Fixing Screw
Sensor Box
Fixing Frame
(Field-Supplied)
Metal Plate
(Field-Supplied)
1-1/4
[32]
(2-3/4 [70])
(4-3/4 [120])
1-1/4
[32]
5/8
[16]
2-M4