background image

 

 

 

 

Johnson Controls 

 

 

 

FURNACE SAFETY CONTROL DEVICES 

The following Safety Devices are included in the design of the furnace (* Depending on Age of the Unit) 

 

A. 

HIGH-TEMPERATURE LIMIT CONTROLS

 - This is an automatic reset control that provides 

over-temperature protection due to high temperatures typically caused by reduced airflow.  If 

high-limit switch trips occur, the equipment must be inspected to diagnose and resolve failures or 

faults.  Do not replace controls without ensuring that there are no other associated or underlying 

causes. Always replace defective controls with UPG Source 1 Parts.  The high-temperature limit 

control is located on the furnace vestibule panel near the gas valve. The limit detects rising 

temperature in the airstream and opens at a specific temperature.  

Associated fault codes are either 4 (four) or 11 (eleven) RED FLASHES. 

 

a.  4 RED FLASHES: indicates that the main limit switch has opened its normally closed 

contacts. The control operates the supply air blower and inducer while the open limit condition 

exists. If the limit switch has not closed within 5 min, the control operates as if the blower is 

not functioning. The control starts a hard lockout and begins to flash the 11 Red Flashes error 

code. Power must be cycled off and on to reset the control after the problem is corrected. 

 

b.  11 RED FLASHES: indicates that the main limit switch has opened its normally closed 

contacts and has remained open for more than 5 min. This condition is usually caused by a 

failed blower motor or blower wheel.  The control enters a hard lockout and power must be 

cycled off and on to reset the control after the problem is corrected.  

 

Diagnostics and Trouble Shooting Guide.

  This fault may be caused by one or more of the 

following, and each should be verified as to being either a potential cause or not: 

a.  A dirty filter – check and replace as necessary. 

b.  Improperly sized duct system or too many supply or return registers closed or blocked off 

– check and open or balance supply and return airflow as necessary.  

c.  Improper indoor blower motor speed selection - Proper gas manifold pressure must be set 

and firing rate verified.  Indoor heating blower motor speed must be set to maintain proper 

temperature rise as indicated on the unit rating plate.  The heating blower speed is set at 

the factory to the default blower speed, which is the blower speed that delivers the correct 

airflow for proper heating operation in most applications. The default heating blower speed 

for each model is shown in its instruction manual.  In certain circumstances, it may be 

necessary to change the heating blower speed to a different motor speed.  Not all motor 

speeds are appropriate for gas heating operation.  Also, do not energize more than one 

motor speed at a time (PSC motors only) or damage to the motor will result.  A change in 

motor speed will typically require a remeasurement of the Temperature Rise (temperature 

difference between the return air and the supply air) from the furnace.  Follow the 

instructions for Measurement of Temperature Rise in the instruction manual.    

d.  Loose limit switch wiring or faulty limit switch – verify field wiring to the unit is properly 

grounded, re-verify ground wires and conductor connectors are tight and secure, and that 

the limit switch exhibits proper electrical continuity, and is not shorted to chassis.    

e.  Faulty Blower Motor - Confirm line and in some cases low voltage (depending on motor 

type) to the motor to confirm if motor should be operating or not.  Replace faulty blower 

motor as necessary. 

Содержание GG8S

Страница 1: ...ls takes product safety seriously We provide safe and reliable products designed and manufactured to applicable quality and safety standards As an effort to improve consistency in diagnosing and resolving failures or faults related to Safety Controls and specifically to the high temperature limit controls as well as the flame proving sensor controls the following troubleshooting guide is being pro...

Страница 2: ...ouble Shooting Guide This fault may be caused by one or more of the following and each should be verified as to being either a potential cause or not a A dirty filter check and replace as necessary b Improperly sized duct system or too many supply or return registers closed or blocked off check and open or balance supply and return airflow as necessary c Improper indoor blower motor speed selectio...

Страница 3: ...to ensure proper combustion It helps protect the burner from buildup of gas without flame If the flame is not detected within 7 s of the gas valve opening the gas valve is shut off and a retry operation begins Also if the flame is lost for 2 s during the 10 s stabilization period the gas valve is shut off and a retry operation begins During a retry operation the vent motor starts a 15 s inter purg...

Страница 4: ...ollow steps in the manual to adjust the manifold pressure In addition examine the burner flames to make sure they are in good adjustment Look to a pure blue flame with a light blue cone at its center that burns full steady and straight If yellow or orange partial diverted or unsteady flame is detected then turn off gas valve and clean any debris from nozzles and burners If condition still exists t...

Страница 5: ... supply to this unit is dependent upon the panel that covers the blower compartment being in place and properly positioned E PRESSURE SWITCH This furnace is equipped with a pressure sensor in the burner compartment near the combustion blower This sensor monitors combustion airflow through furnace and piping systems If any of the conditions listed below are detected by the pressure sensor the contr...

Отзывы: