Figure 5: Back of FX-WRZ Series Sensor Showing DIP Switches and Batteries
2. Set the DIP switches located on the back of the sensor.
For a
mesh network application using an FX-ZFR18xx Series Router
set the DIP switches as indicated. See
Commissioning Multiple FX-WRZ Sensors
for information
on commissioning multiple FX-WRZ Series Sensors in an FX-ZFR Series Wireless Field Bus Sys-
tem.
a. Set the POWER switch to OFF.
b. Set the MODE switch to MESH.
c. Set the PAN OFFSET switches according to the job or system plans.
Important:
Ensure that the PAN OFFSET is the same for each FX-ZFR18xx Series Coordinator, FX-
ZFR18xx Series Router, and FX-WRZ Series Sensor in a mesh network. See Figure 6.
Temperature and Relative Humidity FX-WRZ Series Wireless Room Sensors Installation Instructions
6