Table 4: Cable Length Guidelines for Recommended Wire Sizes for Low-Voltage (<30V) Inputs and Outputs

Assumptions

Maximum Cable
Length and Type

Wire Size/Gauge and Type

Guideline

100 mV maximum voltage drop

Depending on cable and the connected input
or output device, you may have to define an
offset in the setup software for the input or
output point.

457 m (1,500 ft) twisted
wire

1.5 mm

2

(18 AWG) stranded copper

A

297 m (975 ft) twisted wire

0.8 mm (20 AWG) stranded copper

183 m (600 ft) twisted wire

0.6 mm (22 AWG) stranded copper

107 m (350 ft) twisted wire

N/A (24 AWG) stranded copper

100 mV maximum voltage drop

Depending on cable and the connected input
or output device, you may have to define an
offset in the setup software for the input or
output point.

229 m (750 ft) twisted wire

1.5 mm

2

(18 AWG) stranded copper

B

137 m (450 ft) twisted wire

0.8 mm (20 AWG) stranded copper

91 m (300 ft) twisted wire

0.6 mm (22 AWG) stranded copper

61 m (200 ft) twisted wire

N/A (24 AWG) stranded copper

N/A

See

Figure 8

to determine

cable length. Use twisted
wire cable.

See

Figure 8

to select wire size/gauge.

Use stranded copper wire

C

9

FX-PCX3731 Input/Output Module Installation Instructions

Содержание FX-PCX3731

Страница 1: ...alled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in whic...

Страница 2: ...rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clip inward up to secure the controller on the DIN rail To remove...

Страница 3: ...resses 3 24 VAC Class 2 Supply Power Terminal Block See Supply Power Terminal Block 4 Cover Lift Tab One of Two See Removing the Controller Cover 5 Sensor Actuator SA Bus or Field Controller FC Bus Te...

Страница 4: ...regulations Important Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller...

Страница 5: ...e Table 5 for more information The SA FC bus port pin assignment is shown in Figure 6 Figure 6 Pin Number Assignments for Sensor SA Bus and FC Bus Ports on Controllers Supply Power Terminal Block The...

Страница 6: ...ront of the controller 2 Ensure that the controller s device address DIP switches are set to the correct device address See Setting the Device Addresses 3 Set DIP switch 128 to ON which enables wirele...

Страница 7: ...the wiring guidelines in Table 3 observe these guidelines when wiring controller inputs and outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables...

Страница 8: ...External Power Source Requirements 30 VAC maximum output voltage 0 5 A maximum output current 1 3 A at 25 duty cycle 40 mA minimum load current OUTn BINARY OUPUT External Power Source Only Binary Outp...

Страница 9: ...isted wire 0 6 mm 22 AWG stranded copper 107 m 350 ft twisted wire N A 24 AWG stranded copper 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to de...

Страница 10: ...ines for wire sizes cable types and cable lengths when wiring the controller communication buses and supply power In addition to the guidelines in Table 5 observe these guidelines when wiring an SA or...

Страница 11: ...d FC Bus wiring recommendations in this table are for MS TP bus communications at 38 400 baud For more information refer to the FX PC Series Controller MS TP Communications Bus Technical Bulletin LIT...

Страница 12: ...PC Series Controllers MS TP Communications Bus Technical Bulletin LIT 12011670 for more information on controller device addresses and how to set them on MS TP buses Table 6 SA FC Bus Device Address D...

Страница 13: ...ctrique Important Do not connect an external power source to a BO when the BO power source jumper is in the internal power INT position Connecting external power to a BO that sources internal power ca...

Страница 14: ...OWER Off Steady No Faults On Steady Device Fault no application loaded Main Code download required if controller is in Boot mode or a firmware mismatch exists between the controller and the FX ZFR1811...

Страница 15: ...5 to 95 RH noncondensing Ambient Conditions DIP switch set valid controller device addresses 4 127 Device addresses 0 3 and 128 255 are reserved and not valid addresses Addressing BACnet MS TP RS 485...

Страница 16: ...ternational BACnet Testing Laboratories BTL Protocol Revision 4 Listed BACnet Application Specific Controller B ASC The performance specifications are nominal and conform to acceptable industry standa...

Отзывы: