Table 5: Communications Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and
Cables

Recommended Cable Type

1

Function, Electrical Ratings/Requirements

Terminal
Labels

Terminal
Block/Port Label

FC Bus: 0.6 mm (22 AWG)
stranded, 3-wire twisted, shielded
cable recommended.

SA Bus: 0.6 mm (22 AWG)
stranded, 4-wire (2 twisted-pairs),
shielded cable recommended.

Note:

On the SA Bus, the + and -
wire are one twisted pair,
and the COM and SA PWR
are the second twisted pair
of wires.

FC or SA Bus Communications

+

-

FCBUS

2

or

SABUS

2

Signal Reference (Common) for FC or SA Bus
communications

COM

SHLD on FC Bus:

Isolated terminal (optional shield drain

connection

SAP WR on SA Bus:

15 VDC power lead connection

SHLD

or

SAPWR

Bluetooth Commissioning Converter
retractable cable or 24 AWG 3-pair
CAT 3 Cable <30.5 m (100 ft)

RJ-12 6-Position Modular Connector provides:

FC or SA Bus Communications

FC or SA Bus Signal Reference and 15 VDC Common

Commissioning Converter or an FX-ZFR 1811 Wireless
Router

(Maximum total current draw for SA Bus is 240 mA.)

SA/FC BUS

2

(Port)

0.8 mm to 1.5 mm

2

(18 AWG) 2-wire

24 VAC Power Supply - Hot

Supplies 20-30 VAC (Nominal 24 VAC)

HOT

24~

24 VAC Power Supply - Common

(Isolated from all other Common terminals on controller.)

COM

1

See

Table 4

to determine wire size and cable lengths for cables.

2

The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38,400 baud. For more
information, refer to the

FX-PC Series Controller MS/TP Communications Bus Technical Bulletin (LIT-12011670)

.

Setup and Adjustments

Setting the Device Addresses

FX-PCX controllers are master devices on MS/TP (SA
or FC) buses. Before operating controllers on a bus, you

must

set a valid and unique device address for each

controller on the bus. You set a controller's device
address by setting the positions of the switches on the
DIP switch block at the top of the controller (

Figure 3

).

Device addresses 4 through 127 are the valid addresses
for these controllers.

The DIP switch block has eight switches numbered 128,
64, 32, 16, 8, 4, 2, and 1. Switches 64 through 1 are
device address switches. Switch 128 is a mode switch
that enables a controller to operate on an FX-ZFR Series
Wireless Field Bus. Switch 128 must be set to off for all
hard-wired SA and FC bus applications. Set switch 128
to ON for wireless FC bus applications

only

.

Figure 9: Device Address DIP Switch Block Set to

Address 21

Note:

All FX-PC series devices ship with switch 128 ON
and the remaining address switches off rendering
the controllers wired slave devices, which do not
operate on MS/TP buses, but will not interfere
with bus operation. Set a valid and unique device
address on the controller before applying power
to the controller on the bus.

To set the device addresses on FX-PCX controllers:

11

FX-PCX3731 Input/Output Module Installation Instructions

Содержание FX-PCX3731

Страница 1: ...alled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in whic...

Страница 2: ...rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clip inward up to secure the controller on the DIN rail To remove...

Страница 3: ...resses 3 24 VAC Class 2 Supply Power Terminal Block See Supply Power Terminal Block 4 Cover Lift Tab One of Two See Removing the Controller Cover 5 Sensor Actuator SA Bus or Field Controller FC Bus Te...

Страница 4: ...regulations Important Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller...

Страница 5: ...e Table 5 for more information The SA FC bus port pin assignment is shown in Figure 6 Figure 6 Pin Number Assignments for Sensor SA Bus and FC Bus Ports on Controllers Supply Power Terminal Block The...

Страница 6: ...ront of the controller 2 Ensure that the controller s device address DIP switches are set to the correct device address See Setting the Device Addresses 3 Set DIP switch 128 to ON which enables wirele...

Страница 7: ...the wiring guidelines in Table 3 observe these guidelines when wiring controller inputs and outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables...

Страница 8: ...External Power Source Requirements 30 VAC maximum output voltage 0 5 A maximum output current 1 3 A at 25 duty cycle 40 mA minimum load current OUTn BINARY OUPUT External Power Source Only Binary Outp...

Страница 9: ...isted wire 0 6 mm 22 AWG stranded copper 107 m 350 ft twisted wire N A 24 AWG stranded copper 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to de...

Страница 10: ...ines for wire sizes cable types and cable lengths when wiring the controller communication buses and supply power In addition to the guidelines in Table 5 observe these guidelines when wiring an SA or...

Страница 11: ...d FC Bus wiring recommendations in this table are for MS TP bus communications at 38 400 baud For more information refer to the FX PC Series Controller MS TP Communications Bus Technical Bulletin LIT...

Страница 12: ...PC Series Controllers MS TP Communications Bus Technical Bulletin LIT 12011670 for more information on controller device addresses and how to set them on MS TP buses Table 6 SA FC Bus Device Address D...

Страница 13: ...ctrique Important Do not connect an external power source to a BO when the BO power source jumper is in the internal power INT position Connecting external power to a BO that sources internal power ca...

Страница 14: ...OWER Off Steady No Faults On Steady Device Fault no application loaded Main Code download required if controller is in Boot mode or a firmware mismatch exists between the controller and the FX ZFR1811...

Страница 15: ...5 to 95 RH noncondensing Ambient Conditions DIP switch set valid controller device addresses 4 127 Device addresses 0 3 and 128 255 are reserved and not valid addresses Addressing BACnet MS TP RS 485...

Страница 16: ...ternational BACnet Testing Laboratories BTL Protocol Revision 4 Listed BACnet Application Specific Controller B ASC The performance specifications are nominal and conform to acceptable industry standa...

Отзывы: