FX-PCX3721 Expansion Input/Output Module Installation Instructions

Содержание FX-PCX3721

Страница 1: ...es uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipmen...

Страница 2: ...at the top of the DIN rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on...

Страница 3: ...Removing the Controller Cover 3 Sensor Actuator SA Bus or Field Controller FC Bus Terminal Block See SA FC Bus Terminal Block 4 End of Line EOL Termination Switch See Setting the End of Line EOL Swit...

Страница 4: ...c discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed information on configu...

Страница 5: ...le 5 for more information The SA FC bus port pin assignment is shown in Figure 6 Figure 6 Pin Number Assignments for Sensor SA Bus and FC Bus Ports on Controllers Supply Power Terminal Block The 24 VA...

Страница 6: ...nation diagrams provides details for wiring inputs and outputs to the controllers See Table 2 in this section for the applicable termination diagram Table 2 Termination Details Termination Diagrams Ty...

Страница 7: ...Wire Size Gauge and Type Guideline 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or outpu...

Страница 8: ...rve these guidelines when wiring an SA or FC bus and the 24 VAC supply power Run all low voltage wiring and cables separate from high voltage wiring All SA and FC bus cables regardless of wire size sh...

Страница 9: ...ths for cables 2 The SA Bus and FC Bus wiring recommendations in this table are for MS TP bus communications at 38 400 baud For more information refer to the FX PC Series Controllers MS TP Communicati...

Страница 10: ...P Communications Bus for BCM System Technical Bulletin LIT 12011908 for more information on controller device addresses and how to set them on MS TP buses Table 6 SA FC Bus Device Address Descriptions...

Страница 11: ...switch set to ON the amber EOL LED on the controller cover is lit Commissioning the Controllers You commission controllers with the FX PCT software either via a Bluetooth Commissioning Converter a Zi...

Страница 12: ...r more information Y65T31 0 Power transformer Class 2 24 VAC 50 VA maximum output no enclosure AS XFR050 0 Replacement SA Bus Terminal Blocks 4 Position Brown Bulk Pack AP TBK4SA 0 Replacement FC Bus...

Страница 13: ...preferred or screw mount on flat surface with three integral mounting clips on controller Mounting Enclosure material ABS and polycarbonate UL94 5VB Self extinguishing Plenum Rated Protection Class IP...