background image

1. Set

all

of the switches on the address DIP switch

block (128 through 1) to Off.

2. Set one or more of the seven address switches (64

though 1) to ON, so that the sum of the switch
numbers set to ON equals the intended device
address. See

Table 6

for valid device addresses.

Set the highest number switch that is less than or
equal to the intended device address to ON. Then
continue setting lower numbered switches until the
total equals the intended address. For example, if the
intended device address is 21, set switch 16 to ON
first, then set switch 4 ON, followed by switch 1
(16+4+1= 21).

3. Set switch 128 to ON

only

for controllers on an

FX-ZFR Series Wireless Field Bus application. For
all hard-wired SA and FC bus applications, ensure
that switch 128 is set to Off.

Note:

Do

not

connect a controller with switch 128

set to ON to an active (hard-wired) SA or FC
bus. When a controller with switch 128 set to
ON and a device address from 4 to 127 is
connected to a wired field bus, the entire field
bus is rendered inoperable until the controller
is disconnected or switch 128 is set to off.

Refer to the

FX-ZFR Series Wirless Field Bus System

Technical Bulletin (LIT-12011660)

for more

information on device addresses in wireless
applications.

4. Set a unique and sequential device address for each

of the controllers connected on the SA or FC bus
starting with device address 4.

To ensure the best bus performance, set sequential
device addresses with no gaps in the device address
range (4, 5, 6, 7, 8, 9, and so on). The controllers do

not

need to be physically connected on the bus in

their numerical device address order.

5. Write each controller's device address on the white

label below the DIP switch block on the controller's
cover.

Refer to the

FX-PC Series Controllers MS/TP

Communications Bus Technical Bulletin
(LIT-12011670)

or

MS/TP Communications Bus for

BCM System Technical Bulletin (LIT-12011908)

for

more information on controller device addresses and
how to set them on MS/TP buses.

Table 6: SA/FC Bus Device Address Descriptions

Use on Description

Device
Address

Reserved for FC Bus Supervisory Controller
(not for use on controllers).

0

(Switch
128 Off)

Reserved for peripheral devices (not for use
on controllers).

1 to 3

(Switch
128 Off)

Used for MS/TP master devices (controllers)
that are hardwired to an SA bus or FC bus.

4 to 127

(Switch
128 Off)

Reserved addresses for wired slave devices
(not for use on controllers).

Note:

Controllers ship with switch 128 ON and

the remaining address switches off rendering
the controllers wired slave devices, which do
not operate on MS/TP buses.

0 to 3

(Switch
128 ON)

Valid for MS/TP Master controllers on

wireless

FC Buses only

.

Note:

Do

not

connect a controller with switch

128 ON to an active (

hard-wired

) SA or FC

bus. When a controller with switch 128 ON
and a device address from 4 to 127 is
connected to a wired field bus, the entire field
bus is rendered inoperable until the controller
is disconnected or switch 128 is set to Off.

4 to 127

(Switch
128 ON)

Removing the Controller Cover

Important:

Electrostatic discharge can damage
controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.

Important:

Disconnect all power sources to the
controller before removing cover and
changing the position of any jumper or the
EOL switch on the controller. Failure to
disconnect power before changing a jumper
or EOL switch position can result in damage
to the controller and void any warranties.

The controller cover is held in place by four plastic latches
that extend from the base and snap into slots on the
inside of the housing cover.

To remove the controller cover:

1. Place your fingernails under the two cover lift tabs

(

Figure 3

on the sides of the housing cover and

10

FX-PCX3721 Expansion Input/Output Module Installation Instructions

Содержание FX-PCX3721

Страница 1: ...es uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipmen...

Страница 2: ...at the top of the DIN rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on...

Страница 3: ...Removing the Controller Cover 3 Sensor Actuator SA Bus or Field Controller FC Bus Terminal Block See SA FC Bus Terminal Block 4 End of Line EOL Termination Switch See Setting the End of Line EOL Swit...

Страница 4: ...c discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed information on configu...

Страница 5: ...le 5 for more information The SA FC bus port pin assignment is shown in Figure 6 Figure 6 Pin Number Assignments for Sensor SA Bus and FC Bus Ports on Controllers Supply Power Terminal Block The 24 VA...

Страница 6: ...nation diagrams provides details for wiring inputs and outputs to the controllers See Table 2 in this section for the applicable termination diagram Table 2 Termination Details Termination Diagrams Ty...

Страница 7: ...Wire Size Gauge and Type Guideline 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or outpu...

Страница 8: ...rve these guidelines when wiring an SA or FC bus and the 24 VAC supply power Run all low voltage wiring and cables separate from high voltage wiring All SA and FC bus cables regardless of wire size sh...

Страница 9: ...ths for cables 2 The SA Bus and FC Bus wiring recommendations in this table are for MS TP bus communications at 38 400 baud For more information refer to the FX PC Series Controllers MS TP Communicati...

Страница 10: ...P Communications Bus for BCM System Technical Bulletin LIT 12011908 for more information on controller device addresses and how to set them on MS TP buses Table 6 SA FC Bus Device Address Descriptions...

Страница 11: ...switch set to ON the amber EOL LED on the controller cover is lit Commissioning the Controllers You commission controllers with the FX PCT software either via a Bluetooth Commissioning Converter a Zi...

Страница 12: ...r more information Y65T31 0 Power transformer Class 2 24 VAC 50 VA maximum output no enclosure AS XFR050 0 Replacement SA Bus Terminal Blocks 4 Position Brown Bulk Pack AP TBK4SA 0 Replacement FC Bus...

Страница 13: ...preferred or screw mount on flat surface with three integral mounting clips on controller Mounting Enclosure material ABS and polycarbonate UL94 5VB Self extinguishing Plenum Rated Protection Class IP...

Страница 14: ...son Controls is a registered trademark of Johnson Controls Inc All other marks herein are the marks of their respective owners 2014 Johnson Controls Inc www johnsoncontrols com Published in U S A 14 F...

Отзывы: