background image

FX-PCX3721 Expansion Input/Output Module Installation
Instructions

Part No. 24-10144-203, Rev. D

FX-PCX3721-0

Issued December 5, 2014

Refer to the

QuickLIT website

for the most up-to-date version of this document.

Application

The FX-PCX3721 Expansion Input/Output (I/O) Module
is a part of the Facility Explorer FX-PC Series
Programmable Controller family. FX-PCXs expand the
number of points connected to an FX-PCA, FX-PCG, or
FX-PCV programmable controller or to a supervisory
controller to monitor and control a wide variety of HVAC
equipment.

FX-PCX controllers operate on an RS-485 BACnet

®

Master-Slave/Token-Passing (MS/TP) Bus as BACnet
Application Specific Controllers (B-ASCs) and integrate
into Johnson Controls

®

and third-party BACnet systems.

Note:

At FX-PCT Release 10.1, a new capability was
introduced allowing FX-PCVs, FX-PCGs, and
FX-PCAs to communicate by using either the
BACnet or the N2 field bus networking protocol.
The operation of the FX-PCX Input/Output Module
is not affected by the selection of the BACnet or
the N2 protocol in the host controller.

North American Emissions
Compliance

Canada

This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes
les exigences du Règlement sur le matériel brouilleur
du Canada.

United States

This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when this equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction
manual, may cause harmful interference to radio
communications. Operation of this equipment in a
residential area may cause harmful interference, in which
case the users will be required to correct the interference
at their own expense.

Installation

Observe these guidelines when installing the controller:

Transport the controller in the original container to
minimize vibration and shock damage.

Verify that all parts shipped with the controller.

Do not drop the controller or subject it to physical
shock.

Parts Included

one FX-PCX controller with removable terminal blocks
(Power, SA, and FC bus are removable)

one installation instructions sheet

Materials and Special Tools Needed

three fasteners appropriate for the mounting surface
(M4 screws or #8 screws)

one 20 cm (8 in.) or longer piece of 35 mm DIN rail
and appropriate hardware for DIN rail mount (only)

small straight-blade screwdriver for securing wires in
the terminal blocks

Mounting

Observe these guidelines when mounting an FX-PCX
controller:

Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied enclosure.

Mount the controller horizontally on 35 mm DIN rail
whenever possible.

Mount the controller in the proper mounting position
(

Figure 1

).

Mount the controller on a hard, even surface
whenever possible in wall-mount applications.

Use shims or washers to mount the controller securely
and evenly on the mounting surface.

Mount the controller in an area free of corrosive
vapors and observe the Ambient Conditions
requirements in

Table 9

.

Provide for sufficient space around the controller for
cable and wire connections for easy cover removal
and good ventilation through the controller (50 mm

1

FX-PCX3721 Expansion Input/Output Module Installation Instructions

Содержание FX-PCX3721

Страница 1: ...es uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipmen...

Страница 2: ...at the top of the DIN rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on...

Страница 3: ...Removing the Controller Cover 3 Sensor Actuator SA Bus or Field Controller FC Bus Terminal Block See SA FC Bus Terminal Block 4 End of Line EOL Termination Switch See Setting the End of Line EOL Swit...

Страница 4: ...c discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed information on configu...

Страница 5: ...le 5 for more information The SA FC bus port pin assignment is shown in Figure 6 Figure 6 Pin Number Assignments for Sensor SA Bus and FC Bus Ports on Controllers Supply Power Terminal Block The 24 VA...

Страница 6: ...nation diagrams provides details for wiring inputs and outputs to the controllers See Table 2 in this section for the applicable termination diagram Table 2 Termination Details Termination Diagrams Ty...

Страница 7: ...Wire Size Gauge and Type Guideline 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or outpu...

Страница 8: ...rve these guidelines when wiring an SA or FC bus and the 24 VAC supply power Run all low voltage wiring and cables separate from high voltage wiring All SA and FC bus cables regardless of wire size sh...

Страница 9: ...ths for cables 2 The SA Bus and FC Bus wiring recommendations in this table are for MS TP bus communications at 38 400 baud For more information refer to the FX PC Series Controllers MS TP Communicati...

Страница 10: ...P Communications Bus for BCM System Technical Bulletin LIT 12011908 for more information on controller device addresses and how to set them on MS TP buses Table 6 SA FC Bus Device Address Descriptions...

Страница 11: ...switch set to ON the amber EOL LED on the controller cover is lit Commissioning the Controllers You commission controllers with the FX PCT software either via a Bluetooth Commissioning Converter a Zi...

Страница 12: ...r more information Y65T31 0 Power transformer Class 2 24 VAC 50 VA maximum output no enclosure AS XFR050 0 Replacement SA Bus Terminal Blocks 4 Position Brown Bulk Pack AP TBK4SA 0 Replacement FC Bus...

Страница 13: ...preferred or screw mount on flat surface with three integral mounting clips on controller Mounting Enclosure material ABS and polycarbonate UL94 5VB Self extinguishing Plenum Rated Protection Class IP...

Страница 14: ...son Controls is a registered trademark of Johnson Controls Inc All other marks herein are the marks of their respective owners 2014 Johnson Controls Inc www johnsoncontrols com Published in U S A 14 F...

Отзывы: