Technical Specifications
Table 10: FX-PCA2611-0 Advanced Application Programmable Controller
FX-PCA2611-0 Advanced Application Programmable Controller
Product Code Numbers
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply
Class 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)
Supply Voltage
14 VA maximum for FX-PCA2611 only
Note:
VA rating does
not
include any power supplied to the peripheral devices
connected to Binary Outputs (BOs) or Configurable Outputs (COs), which
can consume up to 12 VA for each BO or CO; for a possible total
consumption of an additional 84 VA (maximum).
Power Consumption
Operating:
0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing
Storage:
-40 to 80°C (-40 to 176°F); 5 to 95% RH noncondensing
Ambient Conditions
DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and
128–255 are reserved and not valid controller addresses.)
Controller Addressing for BACnet
MS/TP
DIP switch set; valid control device addresses 1-255
Controller Addressing for N2
RS-485: selectable BACnet MS/TP or N2
3-wire FC Bus between the supervisory controller and other controllers
4-wire SA Bus between controller, network sensors and other sensor/actuator devices,
includes a lead to source 15 VDC supply power (from controller) to bus devices.
Communications Bus
H8SX/166xR Renesas
®
32-bit microcontroller
Processor
4 MB Flash Memory and 1 MB Random Access Memory (RAM)
Memory
Super capacitor maintains power to the onboard real-time clock for a minimum of
72 hours when supply power to the controller is disconnected.
Real-Time Clock Backup Power Supply
6 - Universal Inputs:
Defined as 0-10 VDC, 4-20 mA, 0-600k ohm, or Binary Dry
Contact
2 - Binary Inputs:
Defined as Dry Contact Maintained or Pulse Counter/Accumulator
Mode
3 - Binary Outputs:
Defined as 24 VAC Triac (selectable internal or external source
power)
4 - Configurable Outputs:
Defined as 0-10 VDC or 24 VAC Triac BO
2 - Analog Outputs:
Defined as 0-10 VDC or 4-20 mA
Input and Output Capabilities
Input:
16-bit resolution
Output:
16-bit resolution, +/- 200 mV accuracy in 0-10 VDC applications
Analog Input/Analog Output Resolution
and Accuracy
Input/Output:
Fixed Screw Terminal Blocks
SA/FC Bus and Supply Power:
4-Wire and 3-Wire Pluggable Screw Terminal
Blocks
SA/FC Bus Port:
RJ-12 6-Pin Modular Jacks
Terminations
Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface
with three integral mounting clips on controller
Mounting
Enclosure material:
ABS and polycarbonate UL94 5VB; Self-extinguishing, Plenum
Rated
Protection Class: IP20 (IEC529)
Housing
150 x 190 x 53 mm (5-7/8 x 7-1/2 x 2-1/8 in.) including terminals and mounting clips
Note:
Mounting space requires an additional 50 mm (2 in.) space on top, bottom
and front face of controller for easy cover removal, ventilation and wire
terminations.
Dimensions (Height x Width x Depth)
25
FX-PCA2611-0 Advanced Application Programmable Controller Installation Instructions