Table 3: FX-PCA2611-0 Terminal Blocks, Functions, Ratings, Requirements, and Cables
Determine Wire Size and
Maximum Cable Length
Function, Ratings, Requirements
Terminal
Label
Terminal Block
Label
See Guideline
C
in
Binary Output - 24 VAC Triac
(Internal Power Source)
Sources internal 24VAC power (24~ HOT).
OUTn
BINARY
(Output)
Power Selection
Jumper positioned to
Internal (
INT
) power.
Binary Output - 24 VAC Triac
(Internal Power Source)
Connects OCOM
n
to 24~ when activated.
Internal Power Source:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220BGx-3
40 mA minimum load current
OCOMn
See Guideline
A
in
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or more.
OUTn
CONFIGURABLE
(Outputs)
See Guideline
C
in
Binary Output - 24 VAC Triac
(External Power Source
only)
Connects OUT
n
to OCOM
n
when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220BGx-3
40 mA minimum load current
Same as (Configurable)
OUTn
.
Analog Output Signal Common
All Configurable Outputs
(COs) defined as Analog Outputs (AOs) share a common,
which is isolated from all other commons except the Binary
Input common.
Binary Output Signal Common
All Configurable Outputs
(COs) defined as Binary Outputs are isolated from all other
commons, including other CO commons.
OCOMn
16
FX-PCA2611-0 Advanced Application Programmable Controller Installation Instructions