Mounting / Wiring
Function Descriptions
-
16
-
Function
Description
AUX Power Output
Power supply outputs used for power auxiliary devices. Each is supply limited to 100
ma.
LON Communications
LON FTT-10A Free Topology Network building automation system can access the
status and the configuration of the unit. Also used by configuration software to
configure unit.
Analog Output
Unit has 4 analog outputs which can be configured for 0-5 VDC or 0-10VDC.
Analog Input
Unit has 4 analog inputs which can be configured for 4-20 mA, 0-5VDC, or 0-10VDC.
Power
The FMS-1655L can be powered by either 24 VAC or 24 VDC. A 120 VAC to 24 VAC
Step Down Isolation Transformer is provided and recommended. This power must be
from a Class 2 supply only.
Digital Input
The unit has 4 digital inputs with selectable pull-up voltages of 0V, +5V and +20V.
Relay Output
The unit has 3 SPDT relay outputs with normally open contacts.