FD-1600 1-1/2 Hour Dynamic Rated Multi-Blade Fire Dampers Installation Instructions
5
2.
Double vertical studs are not required for openings
36 in. wide x 36 in. high (914 mm x 914 mm) or
smaller.
3.
All construction fasteners must meet the
requirements of the appropriate wall design and/or
local codes.
4.
All construction and fasteners must meet the
requirements of the appropriate wall design and/or
local codes.
5.
Consult the authority having jurisdiction for other
acceptable framing methods.
The metal stud construction and wood stud
construction figures that follow depict mounting angles
installed on both sides of the partition. A single angle
may be sufficient. Refer to the instructions for single
angle installation requirements.
Figure 4: Metal Stud Wall Framing
Figure 5: Wooden Stud Wall Framing
Figure 6: Wood Stud Construction
Figure 7: Metal Stud Construction