FD-1600 1-1/2 Hour Dynamic Rated Multi-Blade Fire Dampers Installation Instructions 

5

2.

Double vertical studs are not required for openings 
36 in. wide x 36 in. high (914 mm x 914 mm) or 
smaller.

3.

All construction fasteners must meet the 
requirements of the appropriate wall design and/or 
local codes.

4.

All construction and fasteners must meet the 
requirements of the appropriate wall design and/or 
local codes.   

5.

 Consult the authority having jurisdiction for other 
acceptable framing methods.

The metal stud construction and wood stud 
construction figures that follow depict mounting angles 
installed on both sides of the partition. A single angle 
may be sufficient. Refer to the instructions for single 
angle installation requirements.    

Figure 4: Metal Stud Wall Framing

Figure 5: Wooden Stud Wall Framing

Figure 6: Wood Stud Construction

Figure 7: Metal Stud Construction