FD-1600 1-1/2 Hour Dynamic Rated Multi-Blade Fire Dampers Installation Instructions

1

Applications

Johnson Controls, Inc., provides a dynamic rated 
multi-blade fire damper for up to 2,000 feet per minute 
(fpm) and 4 in. Water Column (w.c.) static pressure in 
either direction.

Underwriters Laboratories, Inc. ®(UL)

File No. R11172

National Fire Protection Association (NFPA)

Standards 90A, 92A, 92B and 101

The FD-1600 Fire Dampers are listed under 
UL Standard 555, dated 2006, and carry the UL/cUL 
label.

FD-1600 1-1/2 hour fire-rated dampers are approved 
for mounting in walls constructed of masonry or 
gypsum wallboard (metal or wood studs) and mounting 
in cement floors or ceilings.

The FD-1600 Fire Damper meets specifications 
requiring one damper to provide a 1-1/2 hour fire 
rating. The FD-1600 Fire Damper is tested according to 
UL Standard 555 for dampers intended for use in 
Heating, Ventilating, and Air Conditioning (HVAC) duct 
systems passing through fire-resistant assemblies.

Install the FD-1600 Fire Damper according to the 
manufacturer’s instructions. 

NFPA-90A

 and

 

Sheet Metal 

and Air Conditioning Contractors’ National Association

 

SMACNA Fire Damper Guide

 provide additional 

reference guidelines.

The FD-1600 damper meets the requirements for the 
International Code Council (ICC) building code.

The standard FD-1600 Fire Damper includes a fusible 
link rated at 165

F (74

C). Fusible links rated at 212

(100

C) and 285

F (141

C) are available.

FD-1600 dampers up to 72 in. wide x 96 in. high or 
120 in. wide x 48 in. high meet rating requirements for 
mounting in walls, cement floors, or ceilings.

Installation

Refer to the 

Electric Fuse Link/SP100 Application 

Note, LIT-1201604

 for additional information or special 

requirements.

Notes

Use the following notes as guidelines when installing 
this product.

1.

Opening Clearance

The opening in the wall or floor shall be larger than
the damper/ sleeve assembly to permit installation
and expansion. For two angle installations, the
opening shall be a minimum of 1/8 in. per ft (3 mm
per 305 cm) larger than the overall size of the
damper/sleeve assembly. The maximum opening
size shall not exceed 1/8 in. per ft (3 mm per
305 cm) plus 2 in. (51 mm), nor shall the opening
be less than 1/4 in. (6 mm) larger than the damper/
sleeve assembly. For one angle installations, the
opening shall be a minimum of 1/4 in. (6 mm) to a
maximum of 1 in. (25 mm) larger than the overall
size of the damper/sleeve assembly. The opening
may be as much as 2 in. (51 mm) larger than the
damper/sleeve assembly if a 16 ga (1.6 mm)
mounting angle is utilized.

Table 1:  FD-1600 Maximum UL Classified Size

Sections

Vertical and Horizontal Installation

Single

30 in. w x 48 in. (762 mm x 1219 mm) 
Vertical or Horizontal Mount

Multiple

60 in. w x 96 in h (1524 mm x 2438 mm) or 
120 in. w x 48 in. h (3,048 mm x 
1,219 mm) Vertical or Horizontal Mount

FD-1600 1-1/2 Hour Dynamic Rated Multi-Blade Fire 
Dampers

Installation Instructions

Part No. 44-1121-67, Rev. B

Issued March 2016

44- 1121- 67,  Rev .  B